Professional Documents
Culture Documents
16 Fault Finding
16 Fault Finding
Lunch
Fault Finding - Basic machine and circuitry break
chaps?
SAFETY NOTICE !!
DANGER!
ELECTRIC SHOCK
[Live Terminals]
The following tests should only be carried out by qualified and/or experienced
engineers who have received SAFETY TRAINING ON LIVE EQUIPMENT.
All test instruments and their leads/connectors/ probes must be checked to ensure
that they are suitable for the voltage levels being tested, and are in good working
order.
Never attempt to test a ‘LIVE’ generator without another competent person present
to shut down the engine or switchgear as necessary.
Ensure that the work area is SAFE, other personnel in the area are advised of what
you are doing, warning notices and tapes are displayed to advise others of the
hazards.
Bearing
Main Rotor
Shaft
PMG
Power
Supply Rectifier
To A.V.R Fan
(When Fitted).
A.V.R
Main Stator
Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
Fault finding can be simplified by breaking the generator down into three separate test
areas :-
1. The windings, and main rectifier diode assembly
2. The AVR and control circuit
3. The Permanent magnet Generator ( PMG), when fitted.
FIRST CHECK THAT THE GENERATOR IS SAFE TO RUN, WITH AN INSULATION CHECK
AVR Sensing W6
& Power supply N U6V6 Neutral
00
100
10 1
M
0.1
.01
from Main Stator 10
W5
6
W2 W W1
Test
V5
7
V2
V V1
3 Phase M 1KV
Output M 500V
U5
8
U2
U U1
EARTH MEGGER
FRAME
A.V.R
Main Stator
Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
Main Stator
Exciter
X+ XX- Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
Output From - +
Battery into 12vA.V.R
BATTERY
Exciter Stator
Main Stator
X+ XX- Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
Centre tap.
2. When separately excited with a Battery, the engine will be ‘loaded’, by the
3. If the generator is run for a short period, the fault area in the windings area
will become VERY HOT. This can be detected by hand, or from insulation
burning (smell) .
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
IF THE VOLTAGES ARE LOWER THAN 10% BELOW THE NOMINAL, THERE IS
A FAULT ON THE DIODES OR EXCITATION WINDINGS.
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
IF THE VOLTAGES ARE LOWER THAN 10% BELOW THE NOMINAL, THERE IS
A FAULT ON THE DIODES OR EXCITATION WINDINGS.
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
IF THE VOLTAGES ARE LOWER THAN 10% BELOW THE NOMINAL, THERE IS
A FAULT ON THE DIODES OR EXCITATION WINDINGS.
Output From - +
Battery into 12vA.V.R
BATTERY
Exciter Stator
Main Stator
X+ XX- Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
THE VOLTAGE WILL BE LOW when separately exciting with a 12V battery.
A SELF EXCITED AVR SYSTEM may not build up voltage on run up.
A PMG AVR SYSTEM may trip on HIGH EXCITATION PROTECTION, when load is
applied, (depending on how many diodes have failed).
Two or more diodes short circuit may OVERHEAT THE EXCITER ROTOR.
SHAFT
SHAFT SHAFT
SHAFT V
Disconnect the 6 ends of the Exciter Rotor connections to the Rectifier Diodes
FLUKE 87
.--
mV
mA
V
SHAFT V
A
OFF
.--
mV
mA
V
SHAFT V
A
OFF
Reverse the Multimeter leads, so that the Positive lead is on the Anode side of the
diode, the Multimeter should now read OL, (no electron flow).
The positive plate diodes will give opposite polarity readings to above.
A faulty diode will give a short circuit reading in both directions, or an open circuit readin
in both directions, (if the solder joint has melted).
The Varistor is a High Voltage transient protection devise for the Diodes. The
Generator will function normally without it.
Failure of the Varistor usually results in the device going SHORT CIRCUIT.
On a Self Excited AVR system, a short circuit Varistor will prevent voltage build
up on initial start - up.
On a PMG AVR system, the PMG may cause the varistor to EXPLODE.
IF THE VARISTOR, OR ONE OR MORE DIODES HAVE FAILED, THE WHOLE SET
SHOULD BE REPLACED WITH NEW COMPONENTS
. --
mV
mA
V
A
SHAFT
V
OFF
Switch the Multimeter to the position indicated for resistance ‘’ testing
The Varistor should read Infinity in both directions, and has no polarity
A faulty Varistor will be short circuit, or burnt (‘blown’) by fault current
Output From
- +
12vA.V.R
BATTERY
Battery into
Exciter Stator
Main Stator
X+ XX- Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
1. After changing DIODES or the VARISTOR, reconnect the battery, (if dis-connected)
2. Run the Generator at nominal speed, and re-check the output voltage
Any fault found with the MAIN STATOR should now be corrected.
The Output voltage from the main Main Stator should be balanced across phases and
within 10 % of the nominal Voltage.
If the Output Voltage Is Balanced Phase to Phase, but is reading LOW, (MORE THAN
10% BELOW THE NOMINAL), there is a fault in the excitation winding.
The EXCITER STATOR, ROTOR, AND MAIN ROTOR WINDINGS should be checked for
faults.
The winding RESISTANCE VALUES must be checked against correct values given in
the Generator O & M manuals.
Output From - +
Battery into 12vA.V.R
BATTERY
Exciter Stator
Main Stator
X+ XX- Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
1. Stop the Generator Set and disconnect the battery from X+ (F1), and XX- (F2).
2. Check the Exciter Stator winding resistance across leads X+ (F1), and XX- (F2).
The correct values are given in the Generator O & M manual.
If the winding is OPEN CIRCUIT, the Generator will produce very LOW voltage only,
(RESIDUAL VOLTAGE), irrespective of AVR type.
SHORTS TO EARTH in the Exciter Stator can cause AVR INSTABILITY and may
OVERHEAT THE PMG STATOR WINDING.
A SEVERE EARTH FAULT may cause the AVR POWER DIODES to fail, due to
excessive leakage current. This fault can BURN OUT THE PMG STATOR
X+ (F1)
X+ F1)
XX- (F2)
XX- (F2)
. --
mV
mA
V
A
V
OFF
Check the Exciter Stator resistance across X+ & XX- with a multi-meter set on the
range.
The correct resistance figures are given in the Operation and Maintenance Manual
supplied with the Generator.
XX- (F2)
Test
M 1KV
M 500V
MEGGER
EARTH
1. Check the Exciter Stator insulation with a 500V or 1000V Insulation tester,
2.The MINIMUM insulation value should be 1.0 Megohm to Earth (Ground).
3. Below 1 Megohm,The windings should be cleaned,dried, and re- coated with
anti-track varnish.
With a Self Excited AVR system, the Generator may not be able to build up Voltage on
start- up, (Residual Voltage is too low.)
With a PMG powered AVR, a short in the exciter rotor may cause repeated tripping of
the AVR EXCITATION PROTECTION circuit on load. This is caused by HIGH
EXCITATION VOLTAGE.
When separately excited with a 12 Volt battery, the VOLTAGE WILL BE LOW.
W
U
DUCTER Digital Ohmmeter
MILLIOHMS OHMS
V
SHAFT
V
The correct resistance figures are given in the Operation and Maintenance Manual
supplied with the Generator.
- +
12vA.V.R
BATTERY
Main Stator
X+ XX- Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
A Self Excited AVR system, may be unable to build up Voltage on start- up,
( from Residual Magnetism).
A PMG powered AVR, may trip out repeatedly on AVR EXCITATION PROTECTION on
load, due to HIGH EXCITATION VOLTS.
When separately excited with a 12 Volt battery, the VOLTAGE WILL BE LOW.
The LOW VOLTAGE will be proportional to the LOSS OF WINDING TURNS, i.e, if
50% of the rotor windings are SHORT CIRCUIT, the RESISTANCE and the OUTPUT
VOLTAGE will be 50% OF THE NOMINAL VALUE.
A rotor winding fault MAY NOT BE VISABLE, as the outer turns are cooled by the air-
flow, and may appear to be undamaged.
SHAFT D.C
Disconnect ONE lead of the Main Rotor connection to the Rectifier Assembly
The main rotor resistance should be checked against values given in the Operation
and Maintenance Handbooks
Main Rotor
. --
mV
mA
V
A
V
OFF
The Main Rotor resistance is checked with a multi-meter set on the range.
If the resistance readings are LOW, a further test to confirm results may be
necessary using a more accurate Low Resistance bridge meter.
- +
12vA.V.R
BATTERY
X+ XX- Exciter
Rotor
& Stator
Main Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
Loss of residual magnetism effects SELF EXCITED AVR control systems ONLY.
PMG powered AVR system DO NOT rely upon residual magnetism for initial voltage
build -up
- +
12vA.V.R
BATTERY
Main Stator
X+ XX- Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
1. Check the battery polarity to the Exciter Stator leads X+ (L1) and XX- (L2).
IF REVERSED, RECONNECT the battery,and try again with the A.V.R
AVR Sensing W6
& Power supply N U6V6 Neutral
from Main Stator
W5 3 Phase
6
W2 W W1
Output mV
mA
V5
7
V2
V V1 V
A
V
U5
8
U2
U U1 OFF
1. With the Exciter Stator leads X+ and XX- OPEN CIRCUIT, run the Generator at
nominal speed, (without load).
2. Check the output voltage across the AVR power supply terminals.
3. The AVR requires a MINIMUM voltage of 3.5 VOLTS to begin excitation build up.
4. If the Residual Voltage is lower than 3.5 Volts, the Residual magnetism must be
restored. NOTE : The residual magnetism can be as high as 10 - 15% of nominal volts !!.
Method 1
XX- (F2)
- +
24 V BATTERY
METHOD 1 : ‘FLASH’ the Exciter Stator leads with a 12 or 24V Battery for 1-2 seconds. Run
the Generator and re-check the Residual Voltage, (Minimum 3.5V to the AVR power supply.
If this does not restore residual, try METHOD 2
XX-
Method 2
BLOCKING
DIODE
RUN
+ - GENERATOR
12v BATTERY
DIODE
STOP THE SET, AND DISCONNECT THE EXCITER STATOR LEADS X+ AND XX_
METHOD 2 : If the residual magnetism is totally lost, it can be fully re-charged by
‘FLASHING’ with 110 Volts D.C from a 240VAC supply rectified to half wave 120 VDC.
Residual should be fully restored with 1 - 2 seconds flashing.
A.V.R
Main Stator
Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
This completes the fault finding on the Excitation windings and main rectifier diode
assembly .
The AVR should now be re-connected and the Generator run at nominal speed.
Any further problems must now be in the AVR or the Permanent Magnet
Generator ( when fitted). The next tests check out the AVR SUPPLY CIRCUITS.
HIGH VOLTAGE - This can also be caused by loss of signal (sensing supply), from
the main stator.
NO VOLTAGE - This can also be caused by loss of power supply to the AVR.
UNSTABLE VOLTAGE - This can also be caused by loose wiring or corroded
terminals from the AVR to the Generator.
Run the Generator, with the 12 Volt battery connected to the Exciter Stator,
and check the AVR supply terminals.
- + A.C Sensing
PMG 12v BATTERY and Power
Power Supply from
Supply Main Stator Main Stator
To A.V.R Exciter (2 or 3 Phase)
(when fitted) Rotor
& Stator
XX- (F2)
X+ (F1) Bearing
Main Rotor
Shaft
Rectifier
Fan
Check that the AVR is receiving the correct POWER AND SENSING SUPPLIES
mV
V5 3 Phase
mA
7
V2 V V1 Output
V
A U5
V 8
U2
U U1
OFF
1. Check all three sensing leads into the AVR, using a Multi-meter on AC Volts.
2. The Sensing and Power supply should be Half Line - Line Volts in Series Star.
3. For Single phase and 240 Volt 3 Phase Machines, the Sensing and Power supply
should be the identical to the Line - Line Voltage.
Also check supply at the A.V.R terminals to ensure continuity of wiring.
w v
6 6
1. Using a Multimeter set on A.C volts, check all three sensing leads into the AVR.
To ensure continuity of wiring, check the leads at the A.V.R terminals.
2. The Sensing supply should be 190- 240 Volts, when the line voltage is at its
correct nominal level. This is determined by turns ratio of the sensing transformer.
P1
P1 P2 P2
S1 S2 S1 S2
8 7 6
Primary and Secondary turns ratio is determined by the Primary (input) Voltage.
The Secondary output must be 170 - 240 V to the A.V.R sensing input 6, 7,
8.
mV
mA
V
A
V
OFF
Run the Generator at nominal speed, and set the Multi-meter to read A.C Volts. ,
Check the Permanent Magnet Stator output Voltage across the 3 input terminals to
the AVR. The Voltage across P2,P3,P4, should be 170 VAC to 220 VAC, and balanced
across phases.
A.V.R
Main Stator
Exciter
Rotor
& Stator
Bearing
Main Rotor
Shaft
Rectifier
Fan
This completes the testing of the windings, Main rectifier and AVR supplies.
The final tests are to CHECK if the AVR IS FAULTY
HIGH VOLTAGE
NO VOLTAGE
LOW VOLTAGE.
UNSTABLE VOLTAGE