Furnace Safe Guard Supervisory System
Furnace Safe Guard Supervisory System
SYSTEM
Air and flue gas system COLD PA
HOT PA MILL
CHIMNEY PA-A
HOT SA
FD-B
ID- A
RAH-A
ESP
FURNACE
RAH-B
ID-B
FD-B
HOT SA
HOT PA
PA-B MILL
COLD PA
FURNACE CORNER
COAL F EF SCANNERS 2 3
OIL EF
FURNACE
COAL E
DE SCANNERS
1 4
COAL D
CD SCANNERS
OIL CD
COAL C
BC SCANNERS
COAL B
AB SCANNERS
OIL AB
COAL A
SA DAMPERS ATFURNACE CONER
AUX.AIR DAMPERS EF 3
2
COAL AIR F
AUX.AIR DAMPERS EF FURNACE
COAL AIR E
1 4
AUX.AIR DAMPERS DE
COAL AIR D
AUX.AIR DAMPERS CD
COAL AIR C
AUX.AIR DAMPERS BC
COAL AIR B
AUX.AIR DAMPERS AB
COAL AIR A
AUX.AIR DAMPERS AA
HFO SUPPLY SCHEME
FROM AUXILIARY
FROM HFO STEAM HEADER
DAY TANK
HFO PUMP-1
HFO
s HTR-1 s
HFO PUMP-2
TO BOILER
HFO FRONT
s HTR-2 s
HFO PUMP-3
HFO
s
s
HTR-3
TO HFO
DAY TANK
HFO SCHEME AT BOILER FRONT
HOFCV
HOTV
FT
AB ELEVATION
CD ELEVATION
M EF ELEVATION
GH ELEVATION
SHORT FT
RECIRCULATION
HORV
HFO HFO
SUPPLY RETURN
LINE LINE
ATOMISING STEAM SCHEME AT BOILER FRONT
AB ELEVATION
CD ELEVATION
EF ELEVATION
GH ELEVATION
HFO NOZZLE
VALVE SCAVENGE OIL GUN
VALVE
ATOMISING
STEAM VALVE
MILL-AB COAL
COAL BUNKER
BUNKER B1 T A1
O A2
B2 B
B3 U A3
A4 FEEDER
FEEDER B4 R
N
E
Mix R Mix
Box S Box
CONVEYOR CONVEYOR
Seal Air
HOT PA COLD PA
SCOPE OF FSSS
SECONDARY
MASTER FUEL BOILER OIL
MILLS AIR
TRIP RELAYS PURGE SYSTEM
DAMPERS
FLAME
SCANNERS
FUNCTIONS OF FSSS
PURGE: Prevent any fuel firing unless a satisfactory furnace purge sequence
SECONDARY AIR CONTROL :Control the flow if secondary air into the
furnace during purging,oil firing,coal firing and during boiler trip.
BOILER TRIP:Effect a Master Fuel Trip upon certain adverse Unit operating
INTERLOCKS COVERED UNDER
FSSS
PURGE PERMISSIVES
HOTV OPEN/CLOSE INTERLOCKS
HORV OPEN/CLOSE INTERLOCKS
OIL GUNS START/STOP CYCLE
BOILER PROTECTION LOGICS
COAL MILL START/STOP INTERLOCKS
COAL FEEDER START/STOP INTERLOCKS
SECNDARY AIR DAMPER INTERLOCKS
BOILER TRIP CONDITIONS
Both FD Fans Off
Both ID Fans Off
Reheat Protection
Drum Level High-High (> +167, delay of 10 seconds)
Drum Level Lo-Lo (< - 450 mm, delay 10 seconds)
Less than FB and loss of AC in any elevation.
Furnace Pressure High-High (> + 250 mmWC, 2 / 3 logic)
Furnace Pressure Lo-Lo ( < -200 mmWC, 2 / 3 logic )
Loss Of All Fuel Trip.
Unit Flame Failure
Loss Of 24 V DC For > 2 seconds
Loss Of 220 V DC For > 2 seconds
Trip from COMPUTER(MMI) by the operator
Air Flow < 30 %(230 T/hr)
Trip from Emergency Push Button.
BOILER TRIP
When the boiler trips the following events takes place
Boiler trip red lamp comes on.
MFT A & B trip lamp comes on and reset lamp goes off.
Cause of trip memory can not be reset till the furnace purge is
completed.
F D Fans Control is transferred to manual.
I D fans vane position is transferred to manual.
Pulverizers are tripped.
Coal feeders are tripped.
P A Fans are tripped.
HFO trip valve closes.
All HFO Nozzle valves closes.
Upper and Lower Fuel air damper opens.
Auxiliary air damper opens and control is transferred to manual.
Loss of all fuel trip protection disarms.
S/H and R/H spray block valves S-82 & R-31 closes and can not be
opened unless furnace purge is completed.
Turbine Trips
LESS THAN FIREBALL &LOSS OF AC IN ANY
ELEVATION IN SERVICE
ELEV AB START & LOSS OF PWR
ELEV CD START & LOSS OF PWR
ELEV EF START & LOSS OF PWR
MILL AB START & LOSS OF PWR OR
MILL CD START & LOSS OF PWR
MILL EF START & LOSS OF PWR
2 SEC
ELEVATION AB 2/4
NOZZLE VALVE NOT OPEN
ELEVATION AB 3/4
SCANNERS NO FLAME
ELEVATION B
ELEVATION BC 3/4 NO FLAME VOTE
SCANNERS NO FLAME
FEEDER B OFF
2 SEC
FLAME FAILURE VOTE LOGICS
ELEVATION CD 2/4 NOZ VLVS
NOT OPEN
ELEVATION CD 3/4SCANNERS
NOFLAME
FEEDER C OFF
ELEVATION CD 2/4
NOZZLE VALVE NOT OPEN 2 SEC
ELEVATION CD 3/4SCANNERS
NO FLAME
ELEVATION DE 3/4SCANNERS
ELEVATION D
NO FLAME NO FLAME VOTE
FEEDER F OFF
2 SEC
FLAME FAILURE VOTE LOGICS
ELEVATION EF 2/4 NOZ VLVS
NOT OPEN
ELEVATION EF 3/4SCANNERS
NOFLAME
FEEDER E OFF
FEEDER F OFF
2 SEC
PURGE PERMISSIVE
AFTER 5 MINUTES:
CLOSE ALL SECONDARY AIR DAMPERS
I.e,A,AB,B,BC,C,CD,D,DE,E,EF,F,FF.
SECONDARY AIR DAMPER CONTROL (SADC)
FUEL AIR DAMPERS:
All fuel air dampers (A,B,C,D,E&F)modulate
according to the amount of primary air flow in the
respective Elevation.
All fuelAir dampers will open when boiler trips.
All fuel Air dampers will open 100% during
purging.
AUXILLARY FUEL AIR DAMPERS(A.F.A.Ds)
closed.