Rectifiers Basics V1.2020

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 69

Rectifier Basics

• Rectifier Types.
• Modules Capacity.
• PLD & LVD Bars Inside Rectifiers.
• Loads and Batteries C.B Locations.
• PLD & LVD Settings.
• Most Common Alarms.
• BDT Procedures

Power Operation Team

1 Orange Restricted
Rectifier Basics

• The Aim of this presentation is to let the field engineers get the minimum level of information about the
rectifiers. By this level, FE will be able to identify rectifier types and make the first troubleshooting before
referring to their team leader.

• We will talk at these slides about the common rectifiers:

• Delta 2 (AMS2000) Rectifier.

• Delta 3 (DPS 2000) Rectifier.

• Delta 4 (DPS 2900) Rectifier.

• Power One Rectifier.

• Emerson Rectifier.

• NSN Rectifier.

• Huawei Rectifiers.

2 Orange Restricted
Delta 2 Rectifier (AMS2000)

3 Orange Restricted
Delta 2 Rectifier (AMS)

• Delta 2 Rectifier hold up to 8 modules 2000 W each so the


maximum output power is 16KW (Around 296A).

• Delta 2 Module (FR2000) is 2000 W so it out 37 A DC.

• The name of the Delta 2 controller is PSC1000.

• During any site intervention, you shouldn’t leave the site


with an active alarm appeared.

• To get the active alarm at the controller, from Home Page,


press up arrows.
• To get the alarm history, from Main Menu, 2. Protocol.
PSC1000 controller record the recent 50 alarm.

• After modifying anything at the PSC 1000, you must save the
data. Go to Main Menu, 3. General then, 5. Current Par
Save.

4 Orange Restricted
Delta 2 Rectifier (AMS)

• All loads should be connected to load bars and batteries to battery bar.

• Rectifier AC cable that feeds the rectifier should be 4×10 mm.

5 Orange Restricted
Delta 2 Rectifier (AMS)

LVD & PLD Settings:


• Low voltage disconnection (LVD) function protects the battery
from a deep discharge.

• Partial Load Disconnection (PLD) function is exist to prioritize


separate loads.
• Low priority bar is the bar that connected by the PLD
contactor wherever its place in rectifier.

• To locate the low priority bar in the rectifier, you should


locate the PLD contactor firstly.

• Low Priority Bar should have 2G, 3G and 4G equipment.

• High Priority Bar should have MW links only.

• Password: Up, Up, Down, Exit, Exit, Enter

6 Orange Restricted
Delta 2 Rectifier (AMS)

LVD & PLD Settings:


• To get the settings at the PSC1000 controller, From Home screen Press Exit to go to Main Menu then 11. Auxiliary
Then Enter. You will find below values.

• These values are the default values for all rectifiers.

• LVD Value (UTRIP1 Low) must be 43.2 V for all rectifiers with all batteries brands.

• PLD Value (UTRIP2 Low) is adjusted according to site needs (Site importance and cascaded sites importance).

Value Default Settings Comment


1. UTRIP 1 Low 43.20 V LVD Value - The value at which the batteries will be disconnected from loads
2. UTRIP 1 OK 50.00 V The value at which the batteries will be reconnected to loads
PLD Value - The value at which the low priority bar will be disconnected from the other
3. UTRIP 2 Low 45.60 V load bars
4. UTRIP 2 OK 50.00 V The value at which the low priority loads will be reconnected to the other load bars

7 Orange Restricted
Delta 2 Rectifier (AMS)

• PLD and LVD contactors are not appeared from the


front. Only contactor screws and bolts are appeared as
shown in the photos.

• The rectifier at the upper photo is Delta 2 rectifier


without PLD contactor so all load bars are connected
through copper bars to the main bar.

• PLD Contactor usually installed at the middle bar from


load bars but you may find it at the first or third bar.

• The rectifier at the lower photo is Delta 2 rectifier with


PLD contactor and the contactor is not at the middle
bar as usual. It’s connected at the right bar.

• If Low priority bar has no space to install all low priority


traffic (2G, 3G, 4G), we have to install external DC box
and install its C.B at the low priority bar.

8 Orange Restricted
Delta 2 Rectifier (AMS)

• Battery Bar shouldn’t have load C.B as batteries will deeply discharge without LVD feature. This leads to
batteries damage.

• The Left photo has load C.B connected at battery bar and this is a violation. Load C.B at battery bar should
be removed immediately.
• Batteries bar should be clear from any loads as the photo in the right.

9 Orange Restricted
Delta 2 Rectifier (AMS)

Most Common Alarms at AMS: (UA: Urgent Alarm, NUA: Non Urgent Alarm, MF: Mains Failure)
• “RM Failure”: Means that there is a problem at rectifier modules. Alarm will clear once remove or replace the
faulty module.

• “TBATT HIGH”: Means that batteries temperature exceeds the adjusted level. Press down arrow then Tbatt. The
default settings at the rectifiers is that high temp alarm will generate at the rectifier screen when Tbatt is higher
than 28° and cleared when Tbatt is lower than 25°. We should check the A/C and the cooling system and Alarm will
clear when the temperature is below 25°.

• “Alarm 1”: Means that rectifier surge arrestor has a problem at the slots or at the surge base. Alarm will clear once
replaced the surge arrestor.
• “HW Failure”: The common problem cause this alarm is faulty temperature sensor. You have to check temperature
sensor and its connector and check the temperature on rectifier. If it appears as ***, means temp sensor faulty and
needs to be replaced.

• “PSYS High”: Means that the rectifier output power is more than adjusted settings. You should check the value from
Menu, then Alarm, then PSYS High. Psys high value should be calculated as number of modules ×2000W. If you have
5M, Psys should be 10000.
10 Orange Restricted
Delta 2 Rectifier (AMS)

Most Common Alarms at AMS: (UA: Urgent Alarm, NUA: Non Urgent Alarm, MF: Mains Failure)
• “Load Fuse”: Means that there is Load C.B tripped off or a problem at Loads C.B alarm chip. To clear it you should
check all load C.Bs and alarm chips.

• “Battery Fuse”: Means that there is battery C.B tripped off or a problem at batteries C.B alarm chip. Also, alarm will
appear if there is a problem at rectifier LVD.

• To clear the alarm, you should check all batteries C.Bs and alarm chips. Also, you should check the DC voltage
at load bars and battery bar.

• If LVD is working, you will find the two voltages are the same. If there is a problem at rectifier LVD contactor,
you will find the two voltages are not the same (the voltage at load bar is around 54 V and the voltage at
battery bar is 51 V).

• “Isys High”: Means that the rectifier output ampere is more than adjusted settings. You should check the value
from Menu, then Alarm, then ISYS High.

• “Us min”: Means that the rectifier output voltage is lower than adjusted settings. You should check the value
from Menu, then Alarm, then Us min. it should be 52.5 V
11 Orange Restricted
12 Orange Restricted
Delta 3 Rectifier (DPS2000)

13 Orange Restricted
Delta 3 Rectifier (DPS2000)

• Delta 3 Rectifier hold up to 8 modules 2000 W each so the


maximum output power is 16KW (Around 296A).
• Delta 3 Module (FR2000) is 2000 W so it out 37 A DC.

• During any site intervention, you shouldn’t leave the site


with an active alarm appeared.

• To get the active alarm at the controller, from Home Page,


press Enter then 3. Alarms then 3.1 Alarm List.

• To get the alarm history, you should login the controller and
extract the log file.

• To get Ibatt max., go to Main Menu, 7. Battery Function,


7.10 Battery Para, Batt 1 or Batt Shunt then Ibatt max.

• Delta 3 rectifier by default doesn’t contain PLD contactor.

• Password: Up, Up, Down, Exit, Exit, Enter.


14 Orange Restricted
Delta 3 Rectifier (DPS2000)

LVD & PLD Settings:


• Low voltage disconnection (LVD) function protects the battery
from a deep discharge.

• Partial Load Disconnection (PLD) function is exist to prioritize


separate loads.

• High priority bar is the bar that connected to the main bar.

• Low priority bar is the bar that connected by PLD contactor


wherever its place in rectifier (at right or left).

• To locate the low priority bar in the rectifier, you should


locate the PLD contactor firstly.

• Low Priority Bar should have 2G, 3G and 4G equipment.

• High Priority Bar should have MW links only.

• Password: Up, Up, Down, Exit, Exit, Enter


15 Orange Restricted
Delta 3 Rectifier (DPS2000)

LVD & PLD Settings:


• To get the settings at the PSC3 controller, From Home screen Press
Enter to go to Main Menu then 6. Configuration Then 6.1. Event
then 6.1.1 Threshold then LVD and PLD. You will find below values.

• From Main Menu, then 1.DC-SYS Status, then LVD Bat1 and LVD
Load1. Inhibit should be No.

• These values are the default values for all rectifiers.

Default Values Comment


Low Threshold 43.2 V The value at which batteries will be disconnected from all loads
LVD
Hysteresis 6.8 V (6.8+43.2=50V) 50V is the value at which the batteries will be reconnected to loads

Low Threshold 45.6 V PLD Value - The value at which low priority bar will be disconnected from the other
load bars
PLD
(4.40+45.6=50V) 50V The value at which the low priority loads will be reconnected to
Hysteresis 4.40 V the other load bar

16 Orange Restricted
Delta 3 Rectifier (DPS2000)

Most Common Alarms at PSC3: (URG: Urgent Alarm, NURG: Non Urgent Alarm, MF: Mains Failure)
• “RFA”: Means that there is a problem at rectifier modules. You need to check all rectifier modules and the number
of modules adjusted at the PSC3.

From Main Menu then 8. Rectifier


Function, then 8.1 Configuration, then
8.1.2 Setup, Then 8.1.2.1 RM Number.
Number of modules in “RM number”
should be the same as the number of
modules installed at the rectifier.

• “Tbatt high”: Batteries temperature exceeds the adjusted level. Go to Main Menu then 1. DC-SYS status then
temperature or Tbatt. The normal settings at the rectifiers is that high temp alarm will activated at the rectifier
screen when Tbatt is higher than 28° and cleared when Tbatt is lower than 25°. We should check the A/C and the
cooling system.
• Alarm will be cleared when the temperature is below 25°.

17 Orange Restricted
Delta 3 Rectifier (DPS2000)

• “VDR True”: means that rectifier surge arrestor has a problem at the slots or at the surge base. Alarm will clear
when replacing the surge arrestor.

• “Load Fuse”: One of load C.Bs trip off or C.B chip board is not inserted at the C.B or touch the rectifier body. Alarm
will clear once trip on the C.Bs or check the C.B chip.

• “Battery Fuse”: Means that there is battery C.B tripped off or there is a problem at batteries C.B alarm chip or touch
the rectifier body. Also, alarm will appear if there is a problem at rectifier LVD.

• You should check all batteries C.Bs and alarm chips. If batteries C.B is down, you should check batteries
charging current limit and make sure that it is within accepted range. Alarm will clear once trip on batteries C.B.

• You should check the DC voltage at load bars and battery bar. If LVD is working, you will find the two voltages
are the same.

• If there is a problem at rectifier LVD contactor, you will find the two voltages are not the same; (the voltage at
load bar is around 54 V and the voltage at battery bar is 51 V). Alarm will clear if LVD problem solved.

18 Orange Restricted
Delta 3 Rectifier (DPS2000)

To get batteries charging current, From


Main Menu then 7. Battery Function,
then 7.10 Battery Para, then Batt1 or
Battery Shunt, Then max Ibatt

• “HW Failure”: The common problem cause this alarm is faulty temperature sensor. You have to check temperature
sensor and its connector and check the temperature on rectifier. If it appears as ***, means temp sensor faulty and
needs to be replaced.
• Usys, Iload, and Ibatt reads ***: You need to clean the controller sockets well with blower and check problem
clearance. If still exist, then controller needs to be checked and repaired if needed.

• Iload, and Ibatt reads ***: You need to clean the controller sockets well with blower and check problem clearance.
If still exist, trip off batteries C.B. if values appeared; it means that there is a problem at LVD. Problem will be
cleared if LVD problem checked.

• “Us min”: Means that the rectifier output voltage is lower than adjusted settings. You should check the value from
Menu, then 7. Battery Function, then 7.4 Usys Supervision then Us min. it should be 52.5 V. Alarm will clear if the
rectifier voltage above the adjusted value.
19 Orange Restricted
Delta 3 Rectifier (DPS2000)

• In Delta 3 Rectifiers, Battery bar is the bar that located


exactly above the controller.

• We have two versions from the Delta 3 rectifiers with two


different C.Bs as per the photos.

• As all rectifiers, Battery Bars shouldn’t have load C.B as


batteries will deeply discharge without LVD feature. This
leads to batteries damage.

Before starting the BDT, you should check batteries charging


current.
• From the Main Menu, 1.DC-SYS Status then 1.1 Overview
then Ibatt. Ibatt is the battery current.
• Make sure that batteries are fully charged (Ibatt = 0A) before
the test.

• We can’t proceed starting the BDT If Ibatt with a value


higher than 1 A as batteries are not fully charged.
20 Orange Restricted
Delta 4 Rectifier (DPS2900)

21 Orange Restricted
Delta 4 (DPS2900) Rectifier

• Delta 4 Rectifier can hold up to 6 modules 2900 W each so


the maximum output power is 17.4KW (Around 316A).

• The output of Delta 4 Module (DPR2900) is 52A DC.

• The controller name of Delta 4 is PSC3.

• During any site intervention, you shouldn’t leave the site


with an active alarm appeared.

• To get the active alarm at the controller, from Home Page,


press Enter then 3. Alarms then 3.1 Alarm List.

• To get the alarm history, you should login the controller and
extract the log file.

• To get Ibatt max., go to Main Menu, 7. Battery Function,


7.10 Battery Para, Batt 1 or Batt Shunt then Ibatt max.

• Delta 4 rectifier has PLD contactor by default.


22 Orange Restricted
Delta 4 (DPS2900) Rectifier

LVD & PLD Settings:


• Low voltage disconnection (LVD) function protects the
battery from a deep discharge.

• Partial Load Disconnection (PLD) function is exist to


prioritize separate loads.

• Low Priority Bar should have 2G, 3G and 4G equipment.

• High Priority Bar should have MW links only.

• If you have a problem at the PLD functionality, You need


to check the load bars if the two bars are connected to
same DC Box through same –ve bar.
• In Delta 4 rectifiers, there is a fuse for the PLD and for the
controller (PSC3) so you have to check it during the
troubleshooting if you have a problem at them.

• Password: Up, Up, Down, Exit, Exit, Enter.


23 Orange Restricted
Delta 4 (DPS2900) Rectifier

LVD & PLD Settings:


• To get the settings at the PSC3 controller, From Main Menu, then
1.DC-SYS Status, then LVD Bat1 and LVD Load1 (You may find LVD
and PLD instead). Inhibit should be No.

• Also, From Home screen Press Enter to go to Main Menu then 6.


Configuration Then 6.1. Event then 6.1.1 Threshold then LVD and
PLD. You will find below values.

Default Values Comment


Low Threshold 43.2 V The value at which batteries will be disconnected from all loads
LVD
Hysteresis 6.8 V (6.8+43.2=50V) 50V is the value at which the batteries will be reconnected to loads
Low Threshold 45.6 V PLD Value - The value at which low priority loads will be disconnected from batteries
PLD (4.40+45.6=50V) 50V The value at which the low priority loads will be reconnected to
Hysteresis 4.40 V the batteries

24 Orange Restricted
Delta 4 (DPS2900) Rectifier

Most Common Alarms at PSC3: (URG: Urgent Alarm, NURG: Non Urgent Alarm, MF: Mains Failure)

• “RFA”; Rectifier Failure Means that there is a problem at rectifier modules. You need to check all rectifier modules
and check the number of modules adjusted at the PSC3 as below. Alarm will clear once replace the faulty module or
remove the faulty module and adjust the number of modules at the controller.

From Main Menu then 8. Rectifier


Function, then 8.1 Configuration, then
8.1.2 Setup, Then 8.1.2.1 RM Number.
Number of modules in “RM number”
should be the same as the number of
modules installed at the rectifier.

• “Tbatt high”: Batteries temperature exceeds the adjusted level. Go to Main Menu then 1. DC-SYS status then
temp or Tbatt. The normal settings at the rectifiers is that high temp alarm will activated at the rectifier screen
when Tbatt is higher than 28° and cleared when Tbatt is lower than 25°. We should check the A/C and the cooling
system.
25 Orange Restricted
Delta 4 (DPS2900) Rectifier

• “VDR True”: means that rectifier surge arrestor has a problem at its slots or at the surge base.

• “Load Fuse”: One of load C.Bs trip off or C.B chip board is not inserted at the C.B or touch the rectifier body. Alarm
will clear once trip on the C.Bs or check the C.B chip.

• “Battery Fuse”: Means that there is battery C.B tripped off or there is a problem at batteries C.B alarm chip or touch
the rectifier body. Also, alarm will appear if there is a problem at rectifier LVD.

• You should check all batteries C.Bs and alarm chips. If batteries C.B is down, you should check batteries
charging current limit and make sure that it is within accepted range. Alarm will clear once trip on batteries C.B.

• You should check the DC voltage at load bars and battery bar. If LVD is working, you will find the two voltages
are the same.
• If there is a problem at rectifier LVD contactor, you will find the two voltages are not the same; (the voltage at
load bar is around 54 V and the voltage at battery bar is 51 V). Alarm will clear if LVD problem solved.

26 Orange Restricted
Delta 4 (DPS2900) Rectifier

• Battery C.B is always trip off; Means that there is a problem at batteries cables or batteries charging current is
more than C.B rate.

• Batteries C.B rate at Delta 4 is 80 A.

• You have to check battery charge current and make sure that it is within accepted range and trip on batteries C.B.
You can get battery charge current as illustrated below.

From Main Menu then 7. Battery


Function, then 7.10 Battery Para, then
Batt1 or Battery Shunt, Then max Ibatt

• “HW Failure”: The common problem cause this alarm is faulty temperature sensor. You have to check
temperature sensor and its connector and check the temperature on rectifier. If it appears as ***, means temp
sensor faulty and needs to be replaced.

• You need to Save the configuration after every modification at the controller. From Main Menu, then 9.Setup,
then 9.1 Save setup.
27 Orange Restricted
Power One Rectifier

28 Orange Restricted
Power One Rectifier

• Power One rectifier hold up to 7 modules.

• Power One module is 2500W so it out about 45 A.

• To get the active alarm at the controller, from Home Page,


press down arrow then Show Alarm. You will get all active
alarms at the controller.

• To get battery temperature, from Home Page, press down


arrow then Show Data then Temperature.

• Power One rectifier doesn’t have PLD by default.


Accept removed parts:
• Removing a module or unit will appear to the controller as
a communication error so you need to inform the
controller that something changed. To get it, from Home
Page, press up arrow then Miscellaneous then Accept
removed parts then Select Yes.

29 Orange Restricted
Power One Rectifier

• At Power One Rectifiers, Battery bar is the bar right to


modules C.Bs.

• Battery Bar usually have 4 C.Bs.

• Battery Bar shouldn’t have load C.B as batteries will deeply


discharge without LVD feature. This leads to batteries
damage.

• Bottoms and LED indications appeared as shown in the


photo.

• Controller Password: 1234.


Before starting the BDT, you must check on batteries charging
current before disconnecting the power.
• From the Home Page, you will find Batcurr.

• Make sure that batteries are fully charged (Batcurr = 0A)


before the test.
30 Orange Restricted
Power One Rectifier

Most Common Alarms at Power One Controller:


• “Temp probe failure”: Check on battery temperature sensor.

• “Communication failure”: Check all rectifier modules and remove the faulty units then make accept removed parts.

• “Battery temp alarm”: Check on battery temperature value.

• “Module failure”: Check on modules operation.

• “Mains error”: Means that rectifier has power alarm.

• “Battery breaker failure”: Means that there is batteries C.B tripped off.

• “Low system voltage”: Check rectifier voltage using Voltmeter and batteries voltage. Problem may be due to high
loads and low number of modules (modules can’t support loads and batteries) or settings not properly adjusted.

• “Distribution breaker failure”: Means that there is Load C.B tripped off.

• In case of the controller screen is shutdown or doesn’t appear any data, it means that the controller is faulty and
needs to be replaced.
31 Orange Restricted
Power One Rectifier

32 Orange Restricted
33 Orange Restricted
Emerson Rectifier

34 Orange Restricted
Emerson Rectifier

• Emerson Rectifier hold up to 5 modules each 2000 W so it


out about 37 A.

• To get the active alarms at the controller, Home Page press


Enter to go to Main Menu, then Status, then Active Alarms.

• To get battery temperature, From Main Menu, then Status,


then Battery, then Battery Group, then you will find BTRM.

• Emerson Rectifier has four bars; Priority bar, Batteries bar,


and 2 normal load bar (low priority bar).

• Battery Bar is the second bar from the left as appeared at


the photo.

• Controller has three level of password: 1, 2 and 640275 for


User Password, Operator Password and Administrator
password respectively.

• This Controller erase its data by reset so don’t hard reset.


35 Orange Restricted
Emerson Rectifier

LVD & PLD Settings:


• Emerson rectifier has PLD by default but its name is LLVD.

• High priority bar is the bar that located at the left of the
rectifier. You should connect MW links only through this bar.

• Low Priority Bars are the two bars that located at the right of
the rectifier and they should have 2G, 3G and 4G equipment.

• From Home Page press Enter to go to Main Menu, then


Parameter Set, then LVD.

• LVD mode is set to voltage mode or time mode.

• BLVD Value is the value at which batteries will be


disconnected from all loads.
• LLVD Value is the value at which low priority loads will be
disconnected from batteries.
36 Orange Restricted
Emerson Rectifier

• Battery Bar shouldn’t have load C.B as batteries will deeply discharge without LVD feature. This leads to batteries
damage.

• The Left photo has load C.B connected at battery bar and this is a violation. Load C.B should be removed
immediately.

• Batteries bar should be clear from any loads as the photo in the right.
37 Orange Restricted
Emerson Rectifier

38 Orange Restricted
NSN Rectifier (FPRA)

39 Orange Restricted
NSN Rectifier (FPRA)

• NSN Rectifier (Flexi Power Rectifier FPRA) hold up to 3


modules (in case of one Shelf).

• NSN module is 2KW so it out about 37A.

• The output power of one NSN rectifier (FPRA) is 6KW.

• NSN rectifier can be installed up to three shelves with


each other (Up to 9 modules).

• NSN rectifier doesn’t support PLD feature.

• NSN rectifier is outdoor solution and it is working


properly in outdoor but when maintaining best model of
installation; when closing the rectifier front and back
covers well and closing all rectifier ports with the glands.
• NSN rectifier is sensitive to the earth leakage so you
should check the earth system at the site.

40 Orange Restricted
NSN Rectifier (FPRA)

• During any intervention at any site have NSN rectifier, you must maintain best model of NSN installation as in the
next photos as all rectifier covers must be covered well with their screws.

41 Orange Restricted
NSN Rectifier (FPRA)

• During any intervention at any site have NSN rectifier, you must maintain the best model of NSN installation as in the
next photos as all rectifier ports must be closed. The same thing should be done at the Ethernet port at rectifier PCB.

42 Orange Restricted
NSN Rectifier (FPRA)
PDA Rectifier Module Module AC Module
• NSN Rectifier consist of three parts; Rectifier Housing, Cable Data Cable
Power Distribution Assembly (PDA) and Three
Modules.

• PDA is the controller of the NSN rectifier and it has PCB


PCB Card
board (Alarm board). Rectifier Housing
Module AC Cable
• PDA unit has five C.Bs. Two C.Bs (C.B 1 and C.B 2) for
loads and three C.Bs (C.B 3, C.B 4 and C.B 5) for
batteries.

• The two loads C.Bs should be connected to the DC box


at each rectifier.

• When we have more than one shelf, Parallel cable


should be connected through C.B 5 at both rectifiers (in
case we have two shelves).

43 Orange Restricted
NSN Rectifier (FPRA)

-54 V Bus bar


-54 Bus bar PDA Input Handle
Module Output
Handle Cover Window of
the
breakers

LED Indicator

LED

Screen

Fan RS485 interface


Case AC input For Data Cable
Cover Modules Data
Connector Earth cable PCB Alarm
of PDA Board Cable

Rectifier Module Rectifier PDA

44 Orange Restricted
NSN Rectifier (FPRA)

• PCB Board: J22 J11

J22 Rosette:
It is consist of 14 port used to connect Temperature sensor at ports (7,8,9,10)
and other ports for connecting the parallel cable between two rectifiers.

• Temperature sensor: consists of 4 wires (red –white –black - cable screen


(thick black)) fixed at J22 as in below photos and table.

• If Temperature degree at rectifier equal - 49 °c this means temp sensor is


faulty or there are a bad connection of its cable. LVD will be disconnected
till fix the sensor problem.
Modules Data Cables

PCB Alarm Board

45 Orange Restricted
NSN Rectifier (FPRA)

J22 Rosette:
• Parallel cables between two rectifiers is connected as shown in the
table.

• We connect two parallel cables as a cross between the two boards.

• Below photos showing the connection for one cable. The other cable
should be connected too but reversed (cross).

• After connecting the two cables you will find that all ports are
connected as in the photo in the right.

The photo after connecting the two


parallel cables and temperature
sensor

46 Orange Restricted
NSN Rectifier (FPRA)

• PCB Board:

J11 Rosette:
• It is consist of 14 port used to connect power alarms (Mains fail,
Major, Minor).

• The two wires of the alarms are sensible of the polarity i.e. the alarm
will not appear if you reverse the two wires.

• We connect mains fail through ports 9,10 and Major alarm at ports
11,12 and Minor alarm at 13,14.

• The other ports are reserved in case we need to connect another


alarm as surge arrestor alarm or use them in case of any of the relays
fail.

47 Orange Restricted
NSN Rectifier (FPRA)

• During any replacement of power modules, you must make sure that the below plastic item is removed from the
output port of the rectifier module and from the rectifier housing.

48 Orange Restricted
NSN Rectifier (FPRA)

• You should login the rectifier to get the


rectifier parameter and know the rectifier
alarms.

• We set the IP address of the windows at


142.120.72.170 and the IP address of the
browser at 142.120.72.172.

• User Name : root

• Password: default

• During your intervention at any site have NSN


rectifier, you should make sure that NSN A/C
Control board is working normally and the
temperature at the software within accepted
range. If not at the range, you should check
the cooling system.

49 Orange Restricted
NSN Rectifier (FPRA)

• You should make sure that the CU and all modules


doesn’t have any alarm (Red) and all green.

• You should make sure that all modules have the same
current (Load is balancing) and no modules have 0 A.

• If you found load at module is 0 A, it means that no


power out from the module and you need to check
the module output port and software version for the
rectifier; it should be R3D.

• Before starting the BDT, you should check on


batteries charging current. From the software, Bat.
Current at the CU must be 0 before the test starting.

• If Bat. Current with a value higher than 1 A, we can’t


proceed conducting battery test till batteries become
fully charged.

50 Orange Restricted
NSN Rectifier (FPRA)

• You must check the rectifier module configuration and make sure that it’s configured (Left photo).

• You must check the CU (control unit) configuration and make sure that it’s configured (Right photo).

• To get these windows, you press left click at the CU or rectifier module part and choose Alarm Configuration.

51 Orange Restricted
NSN Rectifier (FPRA)

• You should check Battery Related Parameter and make sure that it’s configured as the below capture.

• You should check System Related Parameter and make sure that it’s configured as the below capture. Charging
current limit is adjusted to be from 20 to 30 A per string.

• To get these windows, go to System Settings then System related settings then System related Parameter. Also,
System Settings then Batteries related settings then batteries related Parameter.

52 Orange Restricted
NSN Rectifier (FPRA)

• After changing the PDA, You should check on the PDA firmware and make sure that the current version is R3D. If you
changed two PDAs, you must make firmware upgrade at each PDA. From Maintenance, Firmware Upgrade, Current
Version.

• You should make firmware upgrade at each rectifier if you have more than one rectifier.

53 Orange Restricted
NSN Rectifier (FPRA)

• Most Common Problems:

• PDA can’t accessed by laptop. You need to check the PDA LEDs, if it turns on, then you should replace the alarm PCB
board. If problem still exist, then you have to replace the PDA unit.

• Modules loads read 0 A. It means that no power out from the module and you need to check the module output port
and make sure that there it is in good condition and no plastic cover inserted on it. Also check software version for
the rectifier; it should be R3D.

• Modules are not balanced. You have to check the parallel cable between the rectifiers and check the cables at load
C.Bs (all Load C.Bs should be connected to the DC box).

• Temperature degree at rectifier equal - 49°this means that temperature sensor is faulty or there are a bad connection
of its cable. LVD will be disconnected due to this problem.

• If you find any alarm at the home page, you have to check the alarm name from Alarm Information and revise the
alarm configuration mentioned before.

• Power Alarms not appear or appears continuously. You should check alarm cable polarization and check rectifier
settings in Pages 45 and 49.
54 Orange Restricted
NSN Rectifier (FPRA)

• If we have a problem at alarm appearance, you need to check Alarm out allocation menu. From System Settings, then
Signal Out Settings then Alarm Out Allocation. CU PDU Master, Slave 1 and Slave 2 are the same settings and Rec A1
till Rec C3 are the same settings.

55 Orange Restricted
Huawei Rectifiers

56 Orange Restricted
Huawei Rectifiers

• There are a lot of types of Huawei Rectifiers with different


modules capacity.

• We have rectifiers types TP48300A, TP48200A, TP48300B,


TP48400B, ETP48300A, and others. For Micro sites, we have
TP48120A, TP4860H.
• Cabinets Model number is illustrated at the photos.

• Modules capacity varies from 1600 W till 3000 W according


to modules types.

57 Orange Restricted
Huawei Rectifiers

LLVD & BLVD Settings:

• For All Huawei rectifiers, There are two values; BLVD and
LLVD.

• BLVD Value is the value at which batteries will be


disconnected from all loads and BLVD Bar should have MW
links only.

• LLVD Value is the value at which low priority loads only will
be disconnected from batteries.

• LLVD bar should have 2G, 3G and 4G loads.

• LLVD and BLVD Labels are written at the breakers or at the


rectifier bars at all Huawei rectifiers.

• The default values for all Huawei rectifiers are LLVD is 45.6
V and BLVD is 43.2 V.

58 Orange Restricted
Huawei Rectifiers

Huawei (PMU – CPMU01) - White

• Battery Deep Discharge switch must be at Normal not BAT ON.


If this switch is turned at BAT ON, it means that LVD contactor
will not disconnect the batteries from loads and batteries will
got deep discharge then damage.
• Password: 0#.

• To get the active alarms at the rectifier, from Main Menu,


then Status, then Active Alarms.

• To get LLVD and BLVD settings, From Main Menu, then


Settings, then Battery Settings, then LVD Settings then LLVD
(Enable/Disable) and LLVD and BLVD Values.

• This controller doesn’t provide login feature .

59 Orange Restricted
Huawei Rectifiers

Huawei (SMU02B or SMU02C) - Black

• Password: 000001.

• To get Active alarms from the controller; from main Menu then Active
Alarms.

• To get BLVD settings, From Main Menu, then Parameter Settings then,
Battery then, BLVD Parameter then BLVD Voltage.

• To get LLVD settings, From Main Menu, then Parameter Settings then,
Power System then, Basic Parameter then LLVD Voltage.

• You can login at this controller to get Alarm log or more detailed
information using Ethernet cable.

• Browser IP 192.168.0.10 and Laptop IP 192.168.0.11. You can check the


configured IPs from Network Parameter.

• User Name is admin and Password is 000001.


60 Orange Restricted
61 Orange Restricted
Huawei Rectifiers

Alarm Ports at the rectifier:

• Mains Failure (Power Alarm) should be


connected through Alarm 1.

• Major Alarm Should be connected through


Alarm 3.

• Minor Alarm should be connected through


Alarm 5.

• High Temp alarm should be connected through


Alarm 6.

• Door Alarm Should be through Alarm 7.

• Fire Alarm (Smoke Alarm) should be configured


through any available port.

62 Orange Restricted
BDT Procedures

63 Orange Restricted
BDT Procedures

• Firstly please take into your consideration that BDT sheet must be very accurate.

• Any investigation by supplier or by Orange teams resulted by non-defected battery


or fake BDT, A penalty will be applied.

• You have to check your tools (AVO and clamp) before moving to the site.

• Please use the latest version of BDT sheet (2020 BDT sheet).

• Rectifier bus bar reading is the reading between the +ve and –ve bars inside
rectifier. Voltage reading is taken by voltammeter and Ampere reading is taken
from the rectifier screen.

• Check the battery Ampere from rectifier and with DC Clamp Ampere ( Ibatt must
equal zero or less than 1).
• Check the cable connection tightening between batteries and rectifiers .
• Check battery bar inside rectifier and make sure that no loads are connected at
battery bar.
64 Orange Restricted
BDT Procedures

You need to take the needed readings before and after disconnecting
power according to BDT sheets tables as below:
• Rectifier bus bar voltage and Ampere from rectifier screen.
• Voltage readings for all batteries.
• Voltage and Ampere readings for battery strings.
• Make sure that rectifier voltage always equals the summation of
string battery cells readings at any time (equal to string voltage).
Stop the battery test if any of the below cases found:
• Rectifier voltage is 44 V.
• You reached the test time (3Hrs or 4Hrs according to site type).
• Any battery voltage become less that 1.8 V (for 2V batteries).
• Any battery voltage become less than 10.8 V (for 12 V batteries).
65 Orange Restricted
BDT Procedures

After ending your test, you have to complete all the needed data inside the BDT sheet :
• Site power source.
• Rectifier type and model.
• Battery type.
• Number of RF modules 2G, 3G and 4G and number of MW links and types (not number of cells).
• For Huawei rectifiers, Rectifier type and module is written at the rectifier cabinet door (Example, Huawei TP48300A).

Duration of BDTs:
• Battery test for any New site should be 4 Hours.
• Battery test for any replaced batteries should be 4 Hours.
• Battery test for any BSC should be 5 Hours.
• Battery test for any (Macro – Micro – Nodal - VIP) site at the cycle should be 3 Hours.

66 Orange Restricted
BDT Procedures

• Taken readings must be accurate, For 12 V, take two digits after the period like 12.23 V and for 2 V, take three digits
after the period like 2.112 V.
• If you have more than one rectifier, you must take the data corresponding to every rectifier. i.e. Don’t put the same
data and configuration for all rectifiers as every rectifier has different loads.
• BDT sheet must have the correct site name and site code taken from site count.
• BDT sheet should have the current temperature taken from the rectifier screen.
• You should insert the photos at the sheet to be fit at the cell. i.e. the photo shouldn’t be greater than the cell or
smaller than the cell.
• You must clean the batteries surface as the battery surface contains holes and if these holes not cleaned well, the
batteries will be ballooned.
• At Summery sheet, each site should have one BDT only (most recent one) and if you conducted BDT twice due to
any reason, you have to remove the old one.

67 Orange Restricted
BDT Procedures

• You should fill the site equipment table with the working devices
that connected to the rectifier.
• If you have a switch off MW link connected to the rectifier, we don’t
write it at the table.
• If you have two rectifiers at the site or more, the table should be
filled with each rectifier data separately. i.e. to be filled with the
equipment that connected to each rectifier.
• If site has weak batteries, you should take care during the test and
take measures repeatedly and don’t wait till reach the sheet time
(30 Min, 1Hr, ….. ) to avoid site OOS and to stop the test once reach
44 V or 10.8 V/Cell.
• Battery Test must show batteries performance.
• Test that ends at 46 V for example before 3 Hrs without one cell
down will be rejected.

68 Orange Restricted
Thank You

69 Orange Restricted

You might also like