Professional Documents
Culture Documents
C3: Control of P and F: EEB 453: Power Generation & Control
C3: Control of P and F: EEB 453: Power Generation & Control
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
• Division of Load between gens;
2
Introduction
• Deals with P & f control of the power system.
• Changes in P mainly affect the system f while changes in Q mainly
11/25/2021
depend on changes in |V|.
Dr D. Setlhaolo UBEEB
453_2021/22
The 2 Major Control Loops in large Gens
• Automatic Load Frequency Control (ALFC) controls the P & hence f
• ALFC: Combining the individual blocks of. gen, load, prime mover and speed governing
system. Deals with the regulation of P output of the gen and its freq (speed).
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
4
Fig 1: Ps with ALFC & AVR
Control Loops
Interaction of the 2 control loops in a PS:
• AVR
11/25/2021
• Little interaction between the ALFC loop to the AVR loop.
• The AVR loop tends to be faster than the ALFC loop with time constants (of
the field winding in the excitation) are much smaller that in ALFC.
Dr D. Setlhaolo UBEEB
453_2021/22
• Single loop
• ALFC
• Not a single loop
• A fast primary loop responds to f changes and regulates the steam (water) flow via
the speed governor and control valves to match the P output with that of the load.
The time period is a few seconds. The f is controlled via the control of P, AGC.
• A slower secondary loop maintains fine f adjustment to maintain proper P
exchange with other interconnected networks via tie-lines. This loop does not
respond to fast load changes but instead focuses on changes, which lead to
frequency drifting over several minutes, Tie-line. 5
Control Loops …
• Since the AVR loop is much faster than the ALFC loop, the AVR dynamics settle
down before they affect the ALFC control loop.
11/25/2021
• Hence, cross-coupling between the controls can be neglected.
• With the growth of large interconnected systems, ALFC has gained importance in
Dr D. Setlhaolo UBEEB
453_2021/22
recent times.
6
Power & Freq. Control
• OF P & F CONTROL
AIM
• To maintain the desired gen’s Pout matching with the changing load in real time.
11/25/2021
• To assist in controlling the frequency of larger interconnections.
• To keep the net interchange power between pool members, at the predetermined
values.
Dr D. Setlhaolo UBEEB
453_2021/22
Turbine governor control
Is a component of the turbine control system that regulates speed in response to changing
load conditions. The governor output signal manipulates the position of a steam inlet
valve or nozzles which in turn regulates the steam flow to the turbine.
The in speed is non-linear but a governor mechanism is used to make the decrease in
speed linear with an increase in the power demand i.e. the governor is adjusted to
provide a slight drooping characteristic with increasing load. The speed droop (SD) of a 7
prime mover is defined by;
AGR
• For power sharing between a no. of gens connected to the system, the
governors are designed to permit the speed to drop as the load is
increased. This provides the droop speed-output characteristic as shown in
11/25/2021
Fig. 2.
Dr D. Setlhaolo UBEEB
453_2021/22
8
Fig 2: Speed-Droop characteristics
AGR
• speed regulation R is given by the slope of the speed-output characteristic
The
(1)
11/25/2021
Governor % speed regulation is defined as;
Dr D. Setlhaolo UBEEB
453_2021/22
(2)
: no-load speed
: Full load speed
: Nominal speed
9
AGR
To illustrate how the load is shared between two generators, consider 2
generators with droop characteristics as shown below.
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
Fig 3: Droop of 2 interconnected generators 10
AGR
•
Let;
Initial frequency
The outputs of the two generators
11/25/2021
If the load increases by say, , the units slow down and the governors increase
the output until a common operating frequency is reached. The shared
Dr D. Setlhaolo UBEEB
453_2021/22
amount of picked by each gen depends on the regulation. Governor % speed
regulation is defined as;
(3)
(4)
(5)
11
AGR
The output is shared in the inverse of their speed regulation.
The output of the speed governor is which is the difference between the set
power and the power which is given by the governor speed characteristic.
11/25/2021
(6)
Dr D. Setlhaolo UBEEB
453_2021/22
(7)
(8)
12
AGR
Complete ALFC block diagram;
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
Fig 4: Block diagram of complete governor system
13
…
• Figure 4 shows the complete LFC for an isolated gen. supplying a
The
load.
11/25/2021
Since we are interested in the change in speed for change in load, the
transfer function
Dr D. Setlhaolo UBEEB
453_2021/22
can be obtained from a reduced block diagram;
14
Fig 5: Reduced block diagram of a governor system
AGC
(9)
11/25/2021
(10)
Dr D. Setlhaolo UBEEB
453_2021/22
We can re-write;
(11)
15
AGC
• steady state freq. deviation is given by the limit of As . This can be applied
The
by use of the final value thereon;
11/25/2021
(10)
Dr D. Setlhaolo UBEEB
453_2021/22
Now,
(11)
(12)
11/25/2021
Consider n generators with a composite load damping coefficient D, the ss
deviation after a load change is given as;
Dr D. Setlhaolo UBEEB
453_2021/22
(13)
The stiffness or frequency bias factor of the system, is given by;
(14)
: indicates the change in frequency that would occur for the change in the load.
NB** The p.u. speed deviation (p.u. frequency)
17
P& F Control
• Power and Frequency Control of;
•
11/25/2021
Single generator to load
• Generator with another generator in parallel
• Generator to infinite bus
Dr D. Setlhaolo UBEEB
453_2021/22
• Tie-line control
18
P& F Control: 1 Gen to Load
•• When
a sync. gen is operating alone, P & Q supplied by the gen will be the amount
demanded by the load attached to it.
11/25/2021
P & Q supplied cannot be controlled by the gen controls.
For any given P, the governor set points control the gens operating f and,
Dr D. Setlhaolo UBEEB
453_2021/22
• For any given Q, If controls the gens VT .
Fig. shows a gen. supplying a load. A second load is to be connected in parallel with the
first one. The gen has a no-load frequency of 61.0Hz and a slope SP=1 MW/Hz. Load 1
consumes real power of 1000kW at 0.8 p.f. lag, while load 2 consumes P=800kW at 0.707
19
p.f. lag.
P& F Control: 1 Gen to Load
Dr D. Setlhaolo UBEEB
11/25/2021
20
453_2021/22
P& F Control: 1 Gen to Load
Dr D. Setlhaolo UBEEB
11/25/2021
21
453_2021/22
P& F Control: 1 Gen to Load
SUMMARY:
11/25/2021
• P & Q supplied by the generator is the amount demanded by the
attached load.
• The governor set points of the gen. controls the frequency of the
Dr D. Setlhaolo UBEEB
453_2021/22
system.
22
P& F Control: Gen to Gen
What happens if a gen is paralleled with another generator of the same
size?
11/25/2021
Basic constraint is that;
Dr D. Setlhaolo UBEEB
453_2021/22
and the same applies to the Q.
NB**
Here f of the system and P of a
given gen are not constrained to
be constant.
23
P& F Control: Gen to Gen
-• What
happens when the governor set
point of G2 are
- - Curve of G2 shifts
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
Figure
13: Diag. of a Gen. in with
another gen.
Figure
14: Diag. of a Gen. in with another 24
gen. of higher governor set points
P& F Control: Gen to Gen
•• At
the original freq. , the power supplied by G1 & G2 will now be larger
than load demand so the system cannot continue to operate at the same
11/25/2021
f.
• There is only one f at which the sum of the 2 machines (PG1 + PG2) is
equal to the load.
Dr D. Setlhaolo UBEEB
453_2021/22
That frequency is higher than the original frequency and at that freq. G2
supplies more power than before and G1 supplies less power as shown in
Figure 14.
25
Examples…
Example 2
11/25/2021
Two gens supply a load, G1 has a no-load freq. of 61.5Hz and a slope
of Sp1 = 1MW=Hz. G2 has a no-load freq of 61Hz and a slope of
Sp2 = 1MW=Hz. The 2 gens supply a load f 2.5MW @ 0.8 pf lag.
Dr D. Setlhaolo UBEEB
453_2021/22
a) At what frequency is this system operating and how much power is
supplied by each generator? Draw the power house diagram.
c) With the system in configuration (b), what will the system frequency be and gen
powers be if the governor set points on G2 are increased by 0.5Hz?
26
Examples: Example 2
•
Solution
Power produced by the gens with a given slope and fnl.
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
a) ,
Hence
OR
27
Examples: Example 2…
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
Figure 15: Resultant house diagram
28
Examples: Example Solution 2…
b)•
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
Power sharing between the two gens changed.
11/25/2021
A change in the governor set points of one of them changes both the system freq. and the power
sharing. (Normally only 1 is adjusted at a time)
Dr D. Setlhaolo UBEEB
453_2021/22
An increase occurs in the power supplied by the gen whose set points are " while reducing the
power supplied by the other.
Case 1 How can the power sharing of the p.s. be adjusted independently of the system freq and vice-versa?
Case 1: Changing the power sharing while maintaining the system frequency
11/25/2021
Dr D. Setlhaolo UBEEB
453_2021/22
31
Figure 16: House diag. of maintaining while changing power
Sharing
P& F Control: Gen to Gen
• 2: Similarly to adjust without changing power sharing,
Case
simultaneously
11/25/2021
or both set points. ) to change the frequency without changing the power
sharing, ref. Fig 17.
Dr D. Setlhaolo UBEEB
453_2021/22
32
Figure 17: House diag. of maintaining power sharing while changing
• gens should have
Why
11/25/2021
speed, see Fig 18.
Dr D. Setlhaolo UBEEB
453_2021/22
33
Figure 18: A small change in in one of the gens would cause wild shifts
in power sharing.
Exercise
11/25/2021
Each unit is initially operating at its half of its own rating when the
system load suddenly increases by 200MW.
Dr D. Setlhaolo UBEEB
453_2021/22
Determine;
a) The p.u. area frequency response characteristic on a 1000MVA system
base.