Professional Documents
Culture Documents
Per Unit
Per Unit
Per Unit
Chapter 2
Per Unit
• Per unit system is the ratio between the actual value in any unit and
the base or reference value in the same unit.
• In the power systems analysis field of electrical engineering, a per-
unit system is the expression of system quantities as fractions of a
defined base unit quantity.
• Calculations are simplified because quantities expressed as per-unit
do not change when they are referred from one side of a transformer
to the other
Definition
Actual quantity
Per unit Quantity
base value of quantity
Calculation
• Firstly the value of base power and the base voltage are selected, and
their choice automatically fixes the other base values.
•This means that the p.u. impedance is directly proportional to the base
kVA and inversely proportional to square of base voltage.
•Normally the p.u. impedance of various equipment's corresponding to
its own rating voltage and kVA are given.
•Since we choose one common base kVA and voltage for the whole
system, therefore, it is desired to find out the p.u. impedance of the
various equipment's corresponding to the common base voltage and
kVA.
Calculate the per unit impedance in each section For Generator,
Transformer and Motor using
https://ebookcentral.proquest.com/lib/momp/reader.action?docID=3382455&ppg=26
Change the base value
KVgiven-> KVnew
MVAgiven-> MVAnew
Actual Values
Voltage, V - Volts Unit Value = Actual Value/Base Value
Per
Current, I - A
Impedance, Z- Ohm Voltage, Vpu = V/Vb
Reactance, X - Ohm
Apparent Power, S- VA
Actual power,P- W Current per unit, Ipu = I/Ib = Ib = Sb/Vb
Reactive power, Q- VAR
Impedance per unit, Zpu= Z/Zb =
Zb = Vb/Ib = Vb/ (Sb/Vb) =
Base Value
Reactance per unit, Xpu = X/Zb =
Voltage, Vb
Apparent power per unit, Spu=S/Sb
Current, Ib
Impedance, Zb
Actual power per unit ,Ppu = P/Sb
Power, Sb
Reactive power per unit ,Qpu =Q/Sb
Assume-Base Value
Voltage, Vb
Power, Sb
For transmission line per unit impedance using
With p.u. system there is less chance of making mistake in phase and line
voltages, Single phase or three phase quantities.
The computational effort in power system is very much reduced with the
use of per unit quantities.
https://ebookcentral.proquest.com/lib/momp/reader.action?docID=3382455&ppg=27
Problems
1. A three phase 500 MVA, 22 kV generators has winding reactance of 1.065 Ω. Find its per-unit reactance.
2. The reactance of a generator is given as 0.25 per-unit based on the generators of 18 kV, 500 MVA. Find its
per-unit reactance on a base of 20 kV, 100 MVA.
3. A single phase 9.6 kVA, 500 V / 1.5 kV transformers has an impedance of 1.302 Ω with respect to primary
side. Find its per-unit impedance with respect to primary and secondary sides
Reference
• https://
instrumentationtools.com/advantages-disadvantages-per-unit-system
• https://circuitglobe.com/what-is-a-per-unit-system.html
• https://www.electricalpereview.com/per-unit-example-tips-tricks-
watch-electrical-pe-exam/