PART 2
CONDENSER WATER SYSTEMS
Chilled Water Plant Design, Part 2 -
4/16/2012 2
Condenser Water Systems
Agenda
• Today • Later
– CDW Pump / Pipe – CHW temps, flow rates,
Configurations pipe sizes
– Refrigerant Head – CDW temps, flow rates,
Pressure Control pipe sizes
– Minimum CT Flow Rates – Select Cooling Towers
– Water Side Economizers – Select Chillers
– Variable Speed Pumping – Pump Selection / Head
for Condenser Water Loss
– Optimize Controls
NEGATIVES
• REDUNDANCY
NEGATIVES
• PUMP TRIP CAN DROP MULTIPLE
CHILLERS
• RELATIVELY EXPENSIVE
• MORE COMPLEX CONTROLS
• COMPLEX ACCOMMODATING
DIFFERENT SIZES
NEGATIVES
• MANUAL OPERATION
40° min
43° min
IC
AT
CONDENSER REFRIGERANT P/T IS RELATED TO THE LEAVING CWT
M
HE
SC
OPTIONS TO MAINTAIN HIGH LEAVING CWT:
CT
• SLOW DOWN FAN OR CYCLE FAN OFF
ON
TYPICALLY NOT ENOUGH IN VERY COLD WEATHER
E
LV
• 3-WAY VALVE TO BYPASS COOLING TOWER
VA
AIR ENTRAINMENT CONCERN ???
AY
3W
HYDRAULIC CHANGES TO SYSTEM
D
MAINTAINS FULL OR NO FLOW TO TOWER
AD
• VARIABLE SPEED CONDENSER WATER PUMPS
• THROTTLE AUTOMATED CONTROL VALVE ON
CONDENSER INLET OR OUTLET
CONTROL VARIABLE:
• CONDENSER LWT
• REFRIGERANT PRESSURE (DIRECT FROM CHILLER CONTROL PANEL)
Chilled Water Plant Design, Part 2 -
4/16/2012 9
Condenser Water Systems
MINIMUM TOWER FLOW
WHY NOT USE ALL THE TOWERS AT LOW LOAD?
• AIR CAN BYPASS WETTED FILL
• SCALING AT WETTED FILL BOUNDARY
POSITIVES
• ELIMINATES AUTOMATED VALVES
• MOST EFFICIENT CHOICE
NEGATIVES
• TURNDOWN TO ⅔ OR ½ OF DESIGN
• (⅓ PROB NOT FEASIBLE)
• N/A FOR > 2 CELL GROUPS
POSITIVES
• FULL FLOW TO FILL
• COMMON BASIN
• MAY ADDRESS BASIN HEATING
NEGATIVES
• COST/COMPLEXITY OF VALVES
• MAKE UP CONTROL
POSITIVES
• TOLERATES A SMALL EQUALIZER
• MAY BE COST EFFECTIVE WHERE
EQUALIZER IS VERY LONG
NEGATIVES
• COST/COMPLEXITY OF VALVES
• TIMING OF VALVES
• BASIN HEATING MAY BE REQUIRED
POSITIVES
• SHARE A CHILLED WATER PUMP
NEGATIVES 45°
• DIFFICULT TO OPERATE WITH CHILLERS
• NEED TO SHUT DOWN IF CHWS IS NOT
SUFFICIENTLY COLD
• CODES MAY NOT ALLOW
55°
POSITIVES
• DON’T NEED TO SHUT DOWN IF CHWS IS NOT 48°
SUFFICIENTLY COLD
MORE HOURS OR OPERATION
SHORTER PAYBACK
• HX ALWAYS “SEES” WARMEST WATER
49° 45°
NEGATIVES
• NEED A DEDICATED CHILLED WATER PUMP or
• NEED AN (ENERGY WASTING) DIVERTER VALVE
FULL FLOW OR PART FLOW?
• MORE PIPING
55°
POSITIVES
• DON’T NEED TO SHUT DOWN IF CHWS IS NOT
/S
SUFFICIENTLY COLD
SP
MORE HOURS OR OPERATION
SA
SHORTER PAYBACK
• HX ALWAYS “SEES” WARMEST WATER
IT
EF
NEGATIVES
EN
•MORE PIPING
SA