Professional Documents
Culture Documents
PRODUCT SIZING ACTUATOR Training
PRODUCT SIZING ACTUATOR Training
PRODUCT SIZING ACTUATOR Training
• Scotch-Yoke – continued
– Spring-Return – Fail Close
• SR Fail Close Example
– Spring-Return – Fail Open
• SR Fail Open Example
• Actuator Sizing Program
• Additional Information
Introduction
• Quarter-turn
– A device which rotates a minimum of 90 degrees. All Bettis quarter-turn
actuators will rotate more than 90 degrees
• Position
– That degree of rotation describing an actuator’s current location. The
mid position of a quarter-turn actuator is generally at forty-five (45)
degrees
• CW
– Clockwise rotation. Most quarter-turn valves close in a clockwise
direction.
• CCW
– Counterclockwise rotation. Most quarter-turn valves open in a
counterclockwise direction.
Definitions – General
• Stroke
– A continuous, ninety (90) degree rotation of a quarter-turn actuator. Bettis
spring-return actuators have two (2) different strokes, a pressure stroke and
a spring stroke. Bettis double-acting actuators have two (2) pressure strokes.
Note that rack and pinion actuators have common torque values for both
pressure strokes, while scotch-yoke actuators have different torque values
depending on which side of the piston is doing the work.
• Cycle
– The collective reference to two (2) strokes, one (1) for clockwise (CW)
rotation and one (1) for counterclockwise (CCW) rotation. Bettis actuators
must rotate through two (2) strokes to complete one (1) cycle.
• Safety Factor
– Represents a protection component (an adjustment to torque requirement)
sometimes added to a valve’s required torque value. Often used when the
user/specifier is not certain of the valve’s torque requirement, or because of
other application concerns.
Definitions – Pressure Limits
• Clarifying Comments
– A) MOP – Bettis recommends that regulators be set at the minimum sizing
pressure but never above the MOP value. Generally, to obtain maximum
cycle life, the actual supply pressure to an actuator should be as low as
practical to meet the required valve torques
Definitions – Pressure Limits
• Start: (starting)
– That torque output position, at which an actuator produces its greatest
torque output. The starting torque outputs listed in Bettis scotch-yoke
torque output charts are the lesser of the two (2) pressure strokes, when
there is a difference (different areas).
• Minimum: (min.)
– That torque output, at an intermediate position, at which an actuator
produces its lowest torque output. The minimum torque outputs shown
on Bettis pressure torque output charts are the lowest torque values
produced during the pressure stroke(s). For double-acting actuators,
this is also the mid position.
• End: (ending)
– That torque output position, at which an actuator has reached the limit
of a pressure stroke. For double-acting actuators the end torque output
is equal to the start torque output.
Definitions – Spring Stroke
• Start: (starting)
– That torque output position, at which a spring-return actuator produces
its greatest torque output during the spring stroke. The starting torque
output listed in Bettis spring-return torque output charts is that torque
output position, where the spring is fully compressed, and capable of
transferring its maximum force.
• Minimum: (min.)
– That torque output, at an intermediate position, at which an actuator
produces its lowest torque output. The minimum torque outputs listed on
the Bettis spring torque output charts are the lowest value of torque
output produced at any position, during either stroke (pressure or
spring).
• End: (ending)
– That torque output position, at which an actuator has reached the limit
of the spring stroke. The spring ending torque output values listed on
Bettis spring-return torque output charts is the torque output value
where the spring is fully extended, and is transferring its lowest force
value.
Definitions – Valve Positions
For the sizing examples detailed later in this course, the following terms will be
used to indicate valve position:
• Valve Opening Stroke
– BO = Break Open
– RO = Run Open
– EO = End Open
When sizing actuators it is obviously critical to ensure that the actuator’s torque
output exceeds the valve torques at all of the six valve positions (BO, RO, EO,
BC, RC & EC).
For spring-return actuators it is important to ensure that the Start, Min and End
output torques on the pressure and spring strokes are correctly matched with
the valve torque requirements on the correct valve stroke, i.e. opening or
closing.
The above concept is best explained in the two cases discussed on the
following two slides.
Matching Valve & Actuator Positions
• Case 1) A Spring-Return Actuator is Required to Move a Valve to it’s Closed
Position on Loss of the Actuator’s Supply Pressure
– The actuator will need to be a CW type (i.e. actuator rotates in clockwise direction
on spring stroke) since the spring is required to close the valve (remembering that
typically valves close in the clockwise direction) when the supply pressure is lost
– Due to the above, on the actuator’s pressure stroke it will be opening the valve
and therefore when sizing we need to ensure that:
• Actuator pressure Start torque is greater than the valve’s BO torque
• Actuator pressure Min torque is greater than the valve’s RO torque
• Actuator pressure End torque is greater than the valve’s EO torque
• Actuator spring Start torque is greater than the valve’s BC torque
• Actuator spring Min torque is greater than the valve’s RC torque
• Actuator spring End torque is greater than the valve’s EC torque
Matching Valve & Actuator Positions
• Case 2) A Spring-Return Actuator is Required to Move a Valve to it’s Open
Position on Loss of the Actuator’s Supply Pressure
– The actuator will need to be a CCW type (i.e. actuator rotates in counter-
clockwise direction on spring stroke) since the spring is required to open the
valve (remembering that typically valves open in the counter-clockwise direction)
when the supply pressure is lost
– Due to the above, on the actuator’s pressure stroke it will be closing the valve
and therefore when sizing we need to ensure that:
• Actuator pressure Start torque is greater than the valve’s BC torque
• Actuator pressure Min torque is greater than the valve’s RC torque
• Actuator pressure End torque is greater than the valve’s EC torque
• Actuator spring Start torque is greater than the valve’s BO torque
• Actuator spring Min torque is greater than the valve’s RO torque
• Actuator spring End torque is greater than the valve’s EO torque
Torque Characteristics – Ball Valves
Ball valves typically have high BO, EO, BC and EC torques with RO and RC
torques typically being about 50-55% of the BO torque. Scotch-Yoke type
actuators are best suited for ball valves since they closely match the torque
characteristics of these valves.
Valve Torque
Valve Torque
Requirement
Requirement
Soft-Seated Butterfly valves typically have high BO, and EC torques with RO
and EO torques typically being about 50% of the BO torque. Scotch-Yoke type
actuators are best suited for butterfly valves since they closely match the torque
characteristics of these valves.
Valve Torque
Valve Torque
Requirement
Requirement
Valve Torque
Requirement
Requirement
Valve Torque
Requirement
Requirement
If regulation is permitted then an actuator can be sized that meets the valve
torques but has a lower Maximum Operating Pressure (MOP) than the
maximum actuator supply pressure.
If regulation is not permitted then an actuator has to be sized that meets the
valve torques and has a MOP at least equal (see slide notes) to the maximum
supply pressure.
Bettis recommends that the valve manufacturer supply the maximum required
torque value(s) (including any adjustments or suggested safety factor).
Additionally, the valve manufacturer should identify at which position(s) and
direction(s) of rotation (CCW or CW) these maximum requirements occur.
Minimum Information Required for Sizing
Bettis actuators include stops which will resist the maximum rated torque output
of the actuator. The possibility exists, that should the valve become immobilized
during rotation, the actuator could exceed the maximum stem torque rating. If
this possibility is a concern, your application needs further review.
Once the maximum torque requirement, its position, and direction of rotation
are identified, the appropriate Bettis actuator can be selected from torque
output charts. Note that all Bettis published actuator torque values are
guaranteed minimum values.
Sizing – First Steps
• Using this information, select the applicable torque rating table and see the
appropriate following examples.
Sizing – Procedures Introduction
The sizing procedures detailed on following slides are designed to aid in sizing
Bettis quarter-turn pneumatic and hydraulic actuators for specific valve
requirements. The six examples that follow assume a valve/device which
closes in a CLOCKWISE DIRECTION (CW) and has a maximum torque
requirement at the unseating (Start) position.
For all procedures, please note that valve’s torque requirements must be
exceeded by the actuator’s torque output at all corresponding positions and
directions of rotation.
Do not proceed past this point if you are not qualified or do not understand the
application and use of Bettis actuators. Contact your local Authorized Bettis
VAC or a Bettis manufacturing facility if you require assistance.
Rack & Pinion – Double-Acting
From the torque table below for double-acting RPC actuators, we can see that
the smallest actuator that will meet the required valve torques with a minimum
supply pressure of 80 psig is a RPC3650-DA.
Rack & Pinion – Spring-Return – Fail Close
• Select from the Spring End column an output torque which exceeds the
valve’s maximum seating requirement.
• Proceeding to the right, and using your minimum operating pressure, select
an operating pressure column from the Pressure Torque Rating Section of
less than or equal pressure. The Pressure Start torque output must exceed
the valve’s torque requirement at this position (unseating) and direction of
rotation (CCW). The Pressure End torque output must exceed the valve’s
torque requirement at this position (full flow) and direction of rotation (CCW).
• Once a Bettis actuator model has been selected, use the performance data
tables to ensure your maximum supply pressure does not exceed the
maximum operating pressure (M.O.P.) for your Bettis actuator. If the
actuator selected is not rated for your maximum supply pressure, either the
maximum supply pressure must be reduced or an actuator rated for a higher
M.O.P. pressure must be selected.
Rack & Pinion – SR – Fail Close – Example
The minimum actuator supply pressure is 60 psig and the actuator is required
to fail the valve closed on loss of the supply pressure.
Rack & Pinion – SR – Fail Close – Example
From the torque table below for spring-return RPC actuators, we can see that
the smallest actuator that will meet the required valve torques with a minimum
supply pressure of 60 psig is a RPC2250-SR3-CW.
Rack & Pinion – Spring-Return – Fail Open
• Select from the Spring Start column an output torque which exceeds the
valve’s maximum unseating requirement.
• Proceeding to the right, and using your minimum operating pressure, select
an operating pressure column from the Pressure Torque Rating Section of
less than or equal pressure. The Pressure End torque output must exceed
the valve’s torque requirement at this position (seating) and direction of
rotation (CW). The Pressure Start torque output must exceed the valve’s
torque requirement at this position (full flow) and direction of rotation (CW).
• Once a Bettis actuator model has been selected, use the performance data
tables to ensure your maximum supply pressure does not exceed the
maximum operating pressure (M.O.P.) for your Bettis actuator. If the
actuator selected is not rated for your maximum supply pressure, either the
maximum supply pressure must be reduced or an actuator rated for a higher
M.O.P must be selected.
Rack & Pinion – SR – Fail Open – Example
The minimum actuator supply pressure is 100 psig and the actuator is required
to fail the valve open on loss of the supply pressure.
Rack & Pinion – SR – Fail Open – Example
From the torque table below for spring-return RPC actuators, we can see that
the smallest actuator that will meet the required valve torques with a minimum
supply pressure of 100 psig is a RPC450-SR5-CCW.
Scotch-Yoke – Double-Acting
• Once a Bettis actuator model has been selected, use the performance data
tables to ensure your maximum supply pressure does not exceed the
maximum operating pressure (MOP.) for your Bettis actuator. If the actuator
selected is not rated for your maximum supply pressure, either the
maximum supply pressure must be reduced or an actuator rated for a higher
MOP. must be selected
Scotch-Yoke – Double-Acting – Example
• Select from the Spring Torque column a Spring Ending torque output which
exceeds that of the valve’s maximum seating requirement.
• Proceed to the right using your minimum operating pressure and select an
operating pressure column from the Pressure Torque Rating Section of less
than or equal pressure. The Pressure Start torque output must exceed the
valve’s torque requirement at this position (unseating). The Pressure End
torque output must exceed the valve’s torque requirement at this position
(full flow) and direction of rotation (CCW).
• Once a Bettis actuator model has been selected, use the performance data
tables to ensure your maximum supply pressure does not exceed the
maximum operating pressure (MOP.) for your Bettis actuator. If the actuator
selected is not rated for your maximum supply pressure, either the
maximum supply pressure must be reduced or an actuator rated for a higher
MOP. must be selected
Scotch-Yoke – SR – Fail Close – Example
The minimum actuator supply pressure is 2,500 psig and the actuator is
required to fail the valve closed on loss of the supply pressure.
Scotch-Yoke – SR – Fail Close – Example
From the torque table below for spring-return G-Series actuators, we can see
that the smallest actuator that will meet the required valve torques with a
minimum supply pressure of 2,500 psig is a G01002.2-SR1-CW
Scotch-Yoke – Spring-Return – Fail Open
• Select from the Spring Torque column a Spring Start torque output which
exceeds that of the valve’s maximum unseating requirement.
• Proceed to the right using your minimum operating pressure and select an
operating pressure column from the Pressure Torque Rating Section of less
than or equal pressure. The Pressure End torque output must exceed the
valve’s torque requirement at this position (seating). The Pressure Start
torque output must exceed the valve’s torque requirement at this position
(full flow) and direction of rotation (CW).
• Once a Bettis actuator model has been selected, use the performance data
tables to ensure your maximum supply pressure does not exceed the
maximum operating pressure (MOP.) for your Bettis actuator. If the actuator
selected is not rated for your maximum supply pressure, either the
maximum supply pressure must be reduced or an actuator rated for a higher
MOP. must be selected
Scotch-Yoke – SR – Fail Open - Example
What would be the smallest spring-return actuator suitable to operate a valve
with the following torque requirements (inclusive of required safety factor)?
The minimum actuator supply pressure is 50 psig and the actuator is required to
fail the valve open on loss of the supply pressure.
Scotch-Yoke – SR – Fail Open - Example
From the torque table below for spring-return G-Series actuators, we can see
that the smallest actuator that will meet the required valve torques with a
minimum supply pressure of 50 psig is a G7032-SR4-CCW