Coal Feeder
MEASURING THE MASS OR FLOW RATE OF MATERIAL TRAVELLING
OVER A CONVEYOR BELT OF ANY LENGTH.
TYPES OF FEEDERS :
VOLUMETRIC FEEDER :
THE RATE OF COAL FLOW THROUGH THE FEEDER IS DERIVED AS BY
R=QXBXN
R - RATE OF COAL FLOW IN KG/S
Q - VOL. OF COAL DELIVERED BY THE FEEDER PER ROTATION IN
M3/ROTATION
B - BULK DENSITY OF COAL IN M3/KG
N - SPEED OF FEEDER ROTATION PER SECOND
Q & B - MAKING THESE TWO CONTANT
N - ADJUSTING THE SPEED OR VARYING THE SPEED WE CAN
ABLE TO MAINTAIN THE REQUIRED COAL FLOW IN IT.
GRAVIMETRIC FEEDER:
THE RATE OF COAL FLOW IS OBTAINED BY
R=MXN
R - RATE OF COAL FLOW IN KG/S
M - MASS OF COAL ON UNIT LENGTH OF FEEDER BELT IN KG/M
N - SPEED OF FEEDER BELT IN M/S
WORKING DIAGRAM
Coal Feeder Basic
A BELT BETWEEN TWO FIXED POINTS (SPAN) PRECISELY
LOCATED IN THE FEEDER BODY.
A ROLLER, LOCATED MIDWAY TO THE SPAN AND SUPPORTED
AT EACH END BY PRECISION LOAD CELLS, SUPPORTS HALF THE
WEIGHT ON THE SPAN.
THE LOAD CELLS GENERATE AN ELECTRICAL SIGNAL DIRECTLY
PROPORTIONAL TO THE WEIGHT SUPPORTED.
BELT SPEED IS DETERMINED BY SAMPLING THE OUTPUT OF A
ENCODER ATTACHED TO THE MOTOR SHAFT.
THE MICROPROCESSOR MULTIPLIES THE SPEED AND WEIGHT
SIGNAL FOR THE FEEDER RATE OF FUEL OUTPUT.
THE MICROPROCESSOR MATCHES THE FEEDER OUTPUT TO
THE DEMANDED OUTPUT BY ADJUSTING THE FEEDER MOTOR
SPEED
Feeder Structure
Main Drive
Speed Signal
Four-wire Configuration:
The Excitation : labelled E+ and E−, or Ex+ and Ex−
The Signal : Labelled S+ And S−
SPEED ENCODER PRINCIPLE
1.Zero Calibration:
This is the primary method for performing a zero calibration. run the
belt empty and press the auto zero calibration button on the keypad.
you can cancel the calibration at any time by pressing the exit zero Cal
buttons. the recommended repeating this process as required range.
2.Span Calibration:
This is the primary method for performing a Span calibration. run the
belt with test weight and press the auto span calibration button on the
keypad. you can cancel the calibration at any time by pressing the exit
Cal buttons. the recommended repeating this process as required
range.
Calibration Method
1.WEIGHT CALIBRATION
ZERO CALIBRATION:-
ZERO CALIBRATION TO BE CARRIED WHILE BELT RUNNING WITH EMPTY
BELT
THIS HAS TO BE REPEATED UNTIL ERROR PERCENTAGE IS LESS THAN +/-
0.25%
Span Calibration:-
Span Calibration to be carried by placing test weight of 25.2kg
THIS HAS TO BE REPEATED UNTIL ERROR PERCENTAGE IS LESS THAN
+/- 0.5%.
2. Speed Calibration.
Have to measure the time taken for ten full Belt Revolution during belt
running with maximum speed
Same has to be feed in the Controller and also the total belt length.
3. Demarcate Calibration.
Analog Board calibration from DCS Command (0% -4 mA DC & 100% -
20mA DC)
SPAN CALIBRATION
MENU
CALIBRATION
SPAN CALIBRATION
AUTO CAL
BGIN CAL
ENTR CAL
ZERO CALIBRATION
MENU
CALIBRATION
ZERO CALIBRATION
AUTO ZERO
BGIN ZERO
ENTR ZERO
SAIMO CONTROLLER 6105
Manual Error calculation
Manual Error % Calculation=
(Measured value-Calculated value) / Calculated value
FLOW TOTALIZATION :-
THE TOTAL IS ACCUMULATED BY MULTIPLYING MASS PER UNIT
LENGTH BY INCREMENTAL LENGTH AND TOTALIZING THE RESULT
IN ENGINEERING UNITS
1.SEQ Step
2.Mill Emergency Trip
3.Mill Stopped
4.Outlet Gate Closed.
5.Coal Blockage
6.MFT
7.Temp High (65˚C ) Trip
8. Classifier motor stop
PROTECTION SIGNAL
BELT SWAY SWITCH ALARM :
A PROTECTIVE SWITCH FOR DETECTING THE BELT
DEVIATION OF BELT CONVEYORS.
CLEARING CHAIN BROKEN ALARM :
A SWITCH FOR DETECTING THE CHAIN RUNNING FEEDBACK
AND SIGNAL SEND TO ELECTRICAL TIMER UNIT.
NO COAL ON BELT ALARM :
A SIGNAL TAKEN FROM CONTROLLER OUTPUT ( LESS THAN 5
T/H).
COAL BLOCKAGE SENSOR ALARM :
A PROTECTIVE SWITCH FOR DETECTING THE COAL
BLOCKAGE OF FEEDER OUTLET CHUTE.
HIGH TEMPERATURE ALARM :
A PROTECTIVE TEMPERATURE SENSOR FOR DETECTIVE THE
SAIMO FEEDER SPEC:-
FEEDER CAPACITY: 100 T/H
CONTROLLER: SAIMO, 6105, 230VAC.
MAX. BELT SPEED: 0.49 M/S
BELT LENGTH: 6.37 M
TEST WEIGHT: 25.2 K92G
LOADCELL(2): SAIMO , 2MV/V, 100 KG.
COC: PROXIMITY SENSOR,230VAC, AUTO RUN: 5MIN ,AUTO
STOP: 10MIN. INDUCTIVE PRINCIPLE.2 WIRE
COAL BLOCK: PROXIMITY SENSOR, 24VDC, INDUCTIVE
PRINCIPLE.2 WIRE
INLET/OUTLET GATE: LIMITORQUE MOV.
TEMP SENSOR: HEADMOUNT RTD, 4-20MADC,0-100’C.PT-
100,3WIRE.
BELT SWAY SWITCH(2): NO/NC CONTACT, 230VAC,
BEFORE FEEDER START FOLLOWING STEP CHECK:-
(I). THE BELT CONDITIONS.
(II). LOAD CELL HEALTHINESS.
(III). SPEED SENSOR HEALTHINESS.
(IV). INLET, OUTLET & SEAL AIR GATE CLOSE
CONDITION.
(V). NO COAL ON BELT.