Batteries setting

 New Emerson Rect ,


 Old Emerson Rect,
 Huawei Rect,
 Eltek Rect .
 Arranged By:
 E-Amr AbdelAty
 E-Mohamed Kamel
 E-Ahmed AbdelWahab
Basics

Batteries setting is very important option at rectifiers to save batteries lifetime &
match Backup time criteria . (Power criteria sheet / Attached) .

LLVD: Load Low Voltage Disconnect .


BLVD: Batter Low voltage Disconnect .

LLVD/BLVD

Hardware Software
LLVD/BLVD Hardware

We connect DC cables to the AUX Load for TX .


We connect DC cables to the Load for BTS cabinet .
In case “End of chain” the both is the same .
LLVD/BLVD Software

Each types of rectifiers shown at videos step by step and attached with PP .

Battery setting categories

Capacity LLVD/BLVD

Power source Battery Type Power source Battery Type

Thanks to use the below table to check the case that matched with the site
(Zoom In) for normal view
Battery Settings for All sites of Tiers
High Cyclic Batteries Settings

BLVD LLVD

for Smart rectifier for Smart rectifier


Category Battery Capacity Floating Voltage Boosting Voltage Boosting Time Boosting starts when capacity down Boosting Stops when capacity Charging Current Limit
by % capacity reachs % from total capacity Cascaded More than 4
Cascaded less than 4 sites Cascaded less than 4 sites Cascaded More than 4 sites
sites

10% C10 = 10% from total batteries


Action in Telecom Egypt site ( even action is modernization) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% capacity per cabinet 45.4 V 45.4 V 45.4 V 47 V

10% C10 = 10% from total batteries


Action in site has standby diesel generator (even action is modernization) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% capacity per cabinet 45.4 V 45.4 V 45.4 V 47 V

15% C10 = 15% from total batteries


Action in site has main diesel generator (even action is modernization) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% 45.4 V 45.4 V 45.4 V 47 V
capacity per cabinet

Normal Action ( not DG or TE site) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% 15% C10 = 15% from total batteries 45.4 V 45.4 V 45.4 V 47 V
capacity per cabinet

Modernization action Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% 30% C10 = 30% from total batteries 45.4 V 45.4 V 45.4 V 47 V
capacity per cabinet

Normal Cyclic Batteries Settings

BLVD LLVD

for Smart rectifier for Smart rectifier


Category Battery Capacity Floating Voltage Boosting Voltage Boosting Time Boosting starts when capacity down Boosting Stops when capacity Charging Current Limit
by % capacity reachs % from total capacity Cascaded More than 4
Cascaded less than 4 sites Cascaded less than 4 sites Cascaded More than 4 sites
sites

10% C10 = 10% from total batteries


Action in Telecom Egypt site ( even action is modernization) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% capacity per cabinet 45.9 V 45.9 V 45.9 V 47.5 V

10% C10 = 10% from total batteries


Action in site has standby diesel generator (even action is modernization) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% 45.9 V 45.9 V 45.9 V 47.5 V
capacity per cabinet

15% C10 = 15% from total batteries


Action in site has main diesel generator (even action is modernization) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% capacity per cabinet 45.9 V 45.9 V 45.9 V 47.5 V

Normal Action ( not DG or TE site) Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% 15% C10 = 15% from total batteries 45.9 V 45.9 V 45.9 V 47.5 V
capacity per cabinet

15% C10 = 30% from total batteries


Modernization action Will be sent for each battery cabinet to be adjusted in the Rectifiers 54.5v 56.9v 4 hours 1% 98% capacity per cabinet 45.9 V 45.9 V 45.9 V 47.5 V
New EMERSON Rect
Rect PWD :
(1)

Thanks to check attached video show .

Video discus the way for modify Battery setting to match criteria .
Video shown that LLVD/BLVD can be increase more than 45V
after modify the DC volte , over/Low/Under .
Old EMERSON Rect
Rect PWD :
(11)

Thanks to check attached video show .

Video discus the way for modify Battery setting to match criteria .
Below photos at next slid shown that language problem & solution in 8 steps .
1 2 3

4 5 6
Step 5: PWD/245

7 8
Huawei Rect
Rect PWD :
(000001)

Thanks to check attached video show .

Video discus the way for modify Battery setting to match criteria .
Eltek Rect
Rect PWD :
(0003)

Thanks to check attached video show .

Video discus the way for modify Battery setting to match criteria .
Thanks , And we hop to be useful