Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 79

Busbar Protection:

Busbar
Including High Impedance, Protection
Frame Leakage and
Directional Comparison
Principles

GRID
Technical Institute

This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical
> Busbar Institute. All rights reserved.
Protection 1
Busbar Protection

F1 F2

 There are fewer faults


on busbars than on
other parts of the
power system

Without Busbar Protection


 No dislocation of system due to accidental operation of busbar protection
 Slow Fault Clearance
Busbar faults at F1 and F2 are cleared by remote time delayed protection on circuits feeding the faults:
 Time Delayed Overcurrent or
 Time Delayed Distance Protection

> Busbar Protection 2


Busbar Protection
Busbar
Zone

F1 F2

With Busbar Protection


 Fast clearance by Breakers at the Busbars
 Where Busbars are sectionalised, protection can limit the amount of
system disruption for a Busbar fault

> Busbar Protection 3


Busbar protection must be

 Reliable
 Failure could cause widespread damage to the substation
 Stable
 False tripping can cause widespread interruption of
supplies to customers
 Discriminating
 Should trip the minimum number of breakers to clear the
fault
 Fast
 To limit damage and possible power system instability

> Busbar Protection 4


Busbar faults are usually permanent

 CAUSES
 Insulation failures
 Circuit breaker failures
 Falling debris
 Isolators operated outside their ratings
 Safety earths left connected
 Current transformer failures
 THEREFORE:
CIRCUIT BREAKERS SHOULD BE TRIPPED AND
LOCKED OUT BY BUSBAR PROTECTION

> Busbar Protection 5


Methods of providing Busbar protection

1. Remote Time Delayed Protection


2. Frame to Earth (Leakage) Protection
3. Directional Comparison Protection
4. Phase Comparison Protection
5. Differential Protection: High Impedance
Low Impedance

> Busbar Protection 6


Frame leakage protection

ADVANTAGES
1. Simple and economic form of protection
2. Ideal for the protection of phase segregated switchgear where
earth fault protection only is required

DISADVANTAGES
1. Insulation is required between switchgear sections
2. It is not possible to discriminate between faults on two sets of
busbars running through common switchgear frames
3. Care must be taken in construction of the substation in order to
ensure that the fixing bolts do not come in to contact with the
steel reinforcing of the concrete

> Busbar Protection 7


Frame earth protection scheme

 Only an earth fault system


 Involves measuring fault current from switchgear frame
to earth
 Switchgear insulated by standing on concrete plinth
 Only one earthing point allowed on switchgear
 C.T. mounted on single earth conductor used to energise
instantaneous relay
 All cable glands must be insulated

> Busbar Protection 8


Single Zone Frame - Earth Protection
Switchgear frame

G H J K

Frame-earth
fault relay

64

Trip all circuit breakers


+

> Busbar Protection 9


Current Distribution for External Fault

Switchgear frame
Outgoing feeder
Frame-leakage current Switchgear frame
transformer bonding bar
I F = I 1 + I2

Generator

System earthing resistor

Earth bar
I1 + I2

I1 I1 I2

Frame insulation Earthing electrode


resistance to earth resistance

0 > Busbar Protection 10


Frame leakage Busbar protection

External Fault
IF=I1 +I2

I1+ I2

I1 64

>10Ω I1 I2

<1Ω

I1= < 0.1IF

1 > Busbar Protection 11


Frame leakage Busbar protection
INTERNAL FAULT
 Suitable for phase segregated indoor metalclad switchgear. Only
E/F protection required.

I1+ I2
Frame

 Setting of
IF=I1 +I2 Instantaneous E/F
System Relay (64)
I2 64 Earthing
Frame
Earth Bar
Resistance  = < 0.3 IF(Min)
Insulation I1 I2  = > 0.1 IF(Max)
>10Ω
Substation
Earthing
Electrode
<1Ω
 Disadvantages:
 Insulation of switchgear frame and between sections
 Insulation of cable glands to prevent spurious currents during through faults

2 > Busbar Protection 12


Frame leakage scheme
with double insulation barrier

Insulation Barrier
Zone 1 Zone 2 Zone 3

A B C

64
Z1
64
Z2

Trip ‘A’ 96 96
A B1 96 96 Trip ‘C’
B2 C
Trip ‘B’

3 > Busbar Protection 13


Frame leakage scheme
with single insulation barrier

Insulation Barrier
Zone 1 Zone 2

A B C

0.2 -1 SEC.

64 64
Z1 Z2

B1 B2

Trip ‘B’

Trip ‘A’ A C Trip ‘C’

4 > Busbar Protection 14


Frame leakage scheme for duplicate Busbars
Insulation Barrier
Zone 1 Zone 2 Zone 3
R
M1 M2
a b
B
A D c d
C

64 64
Z1 Z3
+ -
M1 M2 R a 96
A
b

96
D1
96
D2
96
B1
96
B2
c 96
d C
5 > Busbar Protection 15
Frame leakage protection
Check feature

 To differentiate between a genuine busbar fault and a fault


in the secondary winding of a c.t.
 The check feature provides a second line of defence
 The check relays pick up for both internal and external faults
 Both check and discriminating relays must operate before
tripping can occur
 The various methods of obtaining the check feature are:-
a) Neutral check provided by a relay energised from a single c.t.
in the power system neutral
b) Residual check provided by a relay energised from a residually
connected c.t. on the busbar incomers
c) Residual voltage check provided by a voltage relay energised
from a broken delta v.t. supply
 Check relays are normally self-reset in order to avoid having
to reset the relay after each external fault

6 > Busbar Protection 16


Single Zone Frame – Earth Protection
With Neutral Check
Switchgear frame

G H J K

Frame-earth
fault relay
Neutral check relay

64
64 CH

Trip all circuit


+ breakers

7 > Busbar Protection 17


Typical Trip And Alarm Circuits For Frame Leakage
With Double Insulation Barrier And Check Feature
+ In Out -
64Z1-1 96 64CH-1
A
CSS-Z1
In Out 96
64Z2-1 B1

CSS-Z2 96
B2
96
C
Trip Supply
Supervision
Alarm
64CH-2 64Z1-2 Relay
74
64Z2-2
74-1 Lamp

74-2 Buzzer

In Out
Lamp
CSS-Z1 Lamp

In Out Lamp

CSS-Z2 Lamp
Alarm
Supply
Supervision
8 > Busbar Protection 18
Directional Comparison Scheme

Load
current

R R
Phase to earth external fault,
scheme (a)

+
Trip
(a)

R R

Trip

+ BR
(b)
9 > Busbar Protection 19
Directional Comparison Scheme

R R

+
(a) Trip

Load
current

R R Phase to earth external fault,


scheme (b)

Trip

+ BR
(b)
0 > Busbar Protection 20
Phase Comparison Scheme - External Fault

 Positive Half Cycle  Negative Half Cycle

A A

B B
X Y X Y
Trip + Trip
+

Current Transformer
Secondary Current

B A B Relay Operation A B A

Feeder X Feeder Y

1 > Busbar Protection 21


Phase Comparison Scheme - Internal Fault

 Positive Half Cycle  Negative Half Cycle

A
A

B
B
X Y + Trip
X Y + Trip

Current Transformer
Secondary Current

A B A Relay Operation
A B A
Feeder X Feeder Y

2 > Busbar Protection 22


Basic Circulating Current Scheme

External Fault

Internal Fault

3 > Busbar Protection 23


Differential Protection

 Uses Merz-Price circulating current principle. All currents


entering and leaving Busbar are compared
 One set of CT’s for each circuit associated with a particular
zone are all connected to a relay
 A single element relay gives earth fault protection only
 A three element relay gives phase and earth fault protection

4 > Busbar Protection 24


Basic Circulting Current Scheme
Earth Fault Protection Only

G H J K

87

Differential
relay

5 > Busbar Protection 25


Phase And Earth Fault Circulating Current
Scheme Using Three-Element Relay

G H

A
B
C
N
87A 87B 87C

Differential relay

6 > Busbar Protection 26


High Impedance Protection

 This is a versatile and reliable protection system applied to


many different Busbar configurations
 If CT requirements are met, scheme performance may be
predicted by calculation without heavy current conjunctive
tests

7 > Busbar Protection 27


High Impedance Busbar Protection

 Simple system to apply and extend


 High Sensitivity for phase and earth faults
 Extremely stable for external faults

8 > Busbar Protection 28


High Impedance Busbar Protection

RST

Metrosil

87

 CT Requirements: Equal ratios


Class ‘X’
 May require stabilising resistors, RST
 May require non-linear resistors (Metrosils)

9 > Busbar Protection 29


High Impedance Differential Protection

 Uses equal ratio CT’s


 Scheme assumes that with heaviest through fault, one CT
saturates, the other not
 To ensure stability, voltage setting of relay circuit made
higher than voltage developed across relay circuit. To
achieve this an extra relay circuit resistance is required.
This is known as the stabilising resistance

0 > Busbar Protection 30


Equivalent Circuit

RCT RLY RLX RCT

RST
Y R ZM X
ZM

RR

1 > Busbar Protection 31


High Impedance Theory

RCT RL RL RCT
IF

IF
RS
V

RL RL

Assume one CT saturates


Assume relay resistance is high
∴ V = IF (2RL + RCT)
VS > V

2 > Busbar Protection 32


High Impedance Theory

∴ Choose IS from min fault current ( 30%)


IS
∴ VS = ISRS + ISRR
RS
VS ∴
ISRS =VVS – ISRR
S
RR IS
RS = V - RVA
R
S
-
IS IS 2
RS =

Thus we can choose a value of RS:-


Knowing 1) Max. & Min Fault Levels,
2) C.T. Circuit Impedances,
3) Relay Information,
4) C.T. Ratio,

3 > Busbar Protection 33


Primary Operating Current (P.O.C.)

 The value of primary operating current should be around


30% of minimum fault current available. This ensures
sufficient relay current during internal fault conditions for
high speed operation

4 > Busbar Protection 34


Differential Relays

 Relays used for high impedance protection are high


stability, unbiased and tuned to nominal frequency.
 Two modular types are available:-
 MCAG14/34
 Current calibrated with external stabilising resistor

 MFAC14/34
 Voltage calibrated with internal high impedance

5 > Busbar Protection 35


Knee-Point Voltage Definition

Exciting Voltage (VS)


+10% VK

VK +50% IeK

ICK
Exciting Current (Ie)

For High Impedance Protection Choose VK such that:


VK 2VS
This ensures fast operation for all faults greater than the setting
current.
VK is thus dependent on setting voltage and hence on maximum
through fault current.

6 > Busbar Protection 36


Internal fault on high impedance scheme
F

RCT RLY RLX RCT

VF RST X
Y Zm Zm
R
IF

VF = IF.R
I
= IF. Y (R CT + R LX )
IR

Effective setting

IS = IR + 2Ie with 2 circuits


= IR + nIe with n circuits

Primary effective setting

IP = T.(IR+nIe)
Or IP = T.(IR+ nIe+IM+ISR+IV)
7 > Busbar Protection 37
Use of fault setting resistor

I0P

ISR IR

RST
RSR
RR

I0P = IR + ISR

8 > Busbar Protection 38


Metrosil limitation of relay voltage
IOP
Im IR

RST
VM
VS
V RR

For heavy internal faults large voltages may develop across relay +
Stab. Resistor.
>3kV Voltages – must use Metrosil
VP = 2 2VK (VF - VK )
VK = Knee point voltage
VF = Max. RMS voltage if C.T. didn’t saturate
= IF(RCT + 2RL + RST + RR)

For Metrosil:
V I=RMSCIβ (D.C.)
2VS  0C 
=
 .52  (A.C.)
9 > Busbar Protection 39
Use of Non Linear Resistors

 Under in zone fault conditions it is possible for voltages above the


relay withstand of 3kV peak to be produced. “Metrosil” non linear
resistors may be necessary to limit the peak voltage below this level
Approx peak volts =
2 2V (V - V )
“Metrosil” characteristic:-K VF = CI
K β
where:- V and I
are peak values
C = constant depending on metrosil
construction
β = constant in range of 0.2 to 0.25

 The values of C and β are chosen to limit metrosil voltage to less


than 3kV peak at maximum fault current

0 > Busbar Protection 40


Metrosil Limitation Of Relay Voltage
IOP

INLR IR

RST
VMLR
VS R
RR

To ensure primary operating current not adversely affected,


metrosil constant ‘C’ must be sufficiently high to restrict metrosil
current at relay setting voltage VS.

Typical currents:-
30mA for use with 1 amp CTs
100mA for use with 5 amp CTs

1 > Busbar Protection 41


CT Wiring Supervision

 Open circuit connections between CT’s and relay circuit result in


unbalance currents which may operate the protection.
 Supervision is applied by a voltage relay across differential relay
circuit
 Supervision relay is time delayed, gives alarm and also shorts out
bus wires to protect differential relay circuit
 Typical effective setting is 25 primary amps or 10% of lowest
circuit rating, which ever is greater.

2 > Busbar Protection 42


Healthy Condition

CT1 CT2 CT3 CT4


RST

ZM1 Super ZM2 ZM3 ZM4


Vision
RR Relay

I1 I2 I3 I4

I1 = I2 + I3 + I4

3 > Busbar Protection 43


Supervision Against Open Circuit C.T.’s

I1

RST I3 I4
I2
V R
Super
ZM2 ZM4 ZM3
Vision RR
Relay

I1

CT1 open circuit, I1 flows through magnetising impedance and relay circuit
in parallel

Voltage measured by supervision relay


V = I1 (R║ZM2║ ZM3║ ZM4)
If Supervision relay setting = VSP
Out-of-balance current to operate the supervision relay
VSP VSP VSP VSP
I= + + +
R Z M2 Z M3 Z M4

4 > Busbar Protection 44


Differential Relay Circuit

A
B Zone bus
C wires
N
95
X
95X
Bus wire shorting contacts
95
X
Supervision
95 relay

Metrosil Stabilising
resistors resistors
V V V

87 87 87

5 > Busbar Protection 45


Current Transformers

 Current transformers must be of low reactance type (classx) and


have identical turns ratio (1 in 100)
 They should be of similar design, or if not, of reasonably matched
magnetic characteristics
 It is common practice to use CT’s having 1 amp secondaries

6 > Busbar Protection 46


Current Transformer Wiring

 Lead burdens between various sets of CT’s must be kept low.


Usually buswires are run in closed ring between breaker control
panels.
 Typical route:-
 CT’s to marshalling kiosk
 Marshalling kiosk to isolator auxiliaries
 Loop between marshalling kiosks
 Conductor size:-
 Normally 2.5mm2

7 > Busbar Protection 47


Effect of C.T. Location
on Busbar Protection Performance

F1
F1 Interlocked
Circuit F1 Overcurrent
Protection Relay
F3
Circuit
F3 Circuit Protection
Protection
Busbar
F4 Busbar Busbar Protection
Protection Protection

Interlocked
F2 Overcurrent F3
Relay

F2
F2
(a)Overlapping C.T.s

(b)All C.T.s on line side of (c)All C.T.s on Busbar side of


circuit breaker circuit breaker

8 > Busbar Protection 48


Zones of Protection for Double Bus Station

Zone G Zone H

BS

BC BC

Zone J

Typical feeder circuits

9 > Busbar Protection 49


Check Feature

Usually provided by duplication of primary protection using second set of CTs on


all circuits other than bus section and coupler units. Check system forms one
zone only, covering whole of busbar systems and not discriminating between
faults on various sections.

Zone A Zone B
87A 87B

Check Zone

87
CK

0 > Busbar Protection 50


Isolator Auxiliary Switches
R

A B C D

a c d
b

r
m
Buswires

Auxiliary Switches Should:


1) Close before the isolator closes
2) Open after the isolator opens
in order to maintain stability on switching
1 > Busbar Protection 51
Busbar Auxiliary Switches Requirements

Reserve Bar

Main Bar
R

Normal Operating Condition

2 > Busbar Protection 52


Busbar Auxiliary Switches Requirements

Main & reserve zones


Ultimately paralleled by
reserve busbar selector
auxiliary switches

On-Load Transfer

3 > Busbar Protection 53


Circuit Breaker Bypass
R

M
b1 a1 b2 a2

c1 c2

b1
a1

c1

b2
a2

c2
M
R
A.C.
N Buswires
CH

4 > Busbar Protection 54


Circuit Breaker and CT Bypass
R

M
b1 a1

Check
Zone
CTs
Normally
Shorted
b1
a1

M
N AC
R Buswires
CH
N
5 > Busbar Protection 55
Tripping Circuits

 One tripping relay (device 96) is required for each feeder


breaker and 2 for each bus section or bus coupler breakers
 Both main and check relays must be energised before
tripping relays trip all breakers associated with zone

6 > Busbar Protection 56


Typical Trip Relay Arrangement
Double Busbar System
+
In Out M1M2R -
87M1 - 1 96
87CH - 1
D1
96
CSS – M1 87M2 - 1 D2
a1
96E
CSS – M2 87R - 1 c1
96
CSS - R F1
96
F2
b1
96
G

c2 96
H1
96
H2
D.C. Buswires

80T

7 > Busbar Protection 57


Through Fault Stability

 Busbar protection stability is based on maximum through fault


current
 Generally this value is derived from the rating of the associated
switchgear irrespective of existing fault level, since it can be
expected that system will develop up to limit of rating

8 > Busbar Protection 58


Earth-fault protection for busbars and other primary plant
connections (one relay per zone)
Rated stability limit phase to
T
earth external fault

IF

T T
C C C

A A A
B B B

D E F

G H K

Relay Vs Vs > TxIFx(2H+2K+F+C)


Circuit
G H K
OR: -
9 > Busbar Protection 59
Earth-fault protection for busbars and other primary plant
connections (one relay per zone)
Rated stability limit phase to
T
earth external fault

T T
C C C

A A A
B B B

IF D E F

G H K

Relay Vs Vs > TxIFx(A+D+2G)


Circuit
G H K
OR: -
0 > Busbar Protection 60
Earth-fault protection for busbars and other primary plant
connections (one relay per zone)
Rated stability limit phase to
T
earth external fault

T T
C C C

A A A
B B B

D IF E F

G H K

Relay Vs Vs > TxIFx(B+E+2H)


Circuit
G H K whichever is the greatest.

1 > Busbar Protection 61


Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
Rated stability limit phase to T
phase external fault IF

T T
C C C

A A A B B B

E F
D
G H K
G H K

G Vs H
Relay K
Circuit
Relay Vs Vs > TxIFx(H+K+C)
Circuit
Relay
G Circuit H K OR: -
2 > Busbar Protection 62
Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
Rated stability limit phase to T
phase external fault

T T
C C C

IF
A A A B B B

E F
D
G H K
G H K

G Vs H
Relay K
Circuit
Relay Vs Vs > TxIFx(A+G)
Circuit
Relay
G Circuit H K OR: -
3 > Busbar Protection 63
Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
Rated stability limit phase to T
phase external fault

T T
C C C

IF
A A A B B B

E F
D
G H K
G H K

G Vs H
Relay K Vs > TxIFx(B+H)
Circuit
Relay Vs
Circuit
Relay
G Circuit H K whichever is the
greatest
4 > Busbar Protection 64
Busbar Protection With Separate Relays Per Circuit
Breaker – Basic Scheme

1
+ 2
1 2 +
+
1 +
2
TR
TR

D D

CH CH

+ 1 2 +

5 > Busbar Protection 65


Busbar Protection With Separate Relays Per Circuit
Breaker – Basic Scheme With Additional Tripping Route

1
+ 2 1
1
+ + 2 2 +
+ + +
2 1 2 +
1
TR TR TR
TR

D D

CH CH

+ 1 2 +
+
STN

6 > Busbar Protection 66


Busbar Protection With Separate Relays Per Circuit
Breaker – Basic Scheme With Additional Relays Per Zone
And Back Tripping Facilities
1
+
1 2 +
2
+
2 +
1

TR
TR
BT BT
1
+ D 2
+

D D

CH

CH CH

+ 1 + STN 2 +

7 > Busbar Protection 67


Busbar Protection With Separate Relays Per Circuit
Breaker – Basic Scheme With Additional Relays Per Zone
And Back Tripping Facilities With Separate Trip Relays
1 2
+ +
2 + 1 +
+ + +
2 1 2 +1

TR TR TR TR

BT BT

D
2 1 +

D D

CH

CH CH

+ 1 + STN 2 +

8 > Busbar Protection 68


Double Busbar With Transfer Facilities
Main

Reserve/ Transfer

By-Pass
Isolator By-Pass
Isolator

9 > Busbar Protection 69


Triple Busbar
Main

Reserve

Transfer Transfer
CB. CB.
Transfer

0 > Busbar Protection 70


1 ½ Breaker Scheme

1 > Busbar Protection 71


1 ½ Breaker Bus Protection

87

87

2 > Busbar Protection 72


Mesh Busbar
F1 F3

T1 T3

T4 T2

F4 F2

3 > Busbar Protection 73


Mesh Busbar Protection

87 F1 87
R1 F3
R3

T1 T3

T4 T2

87 F4 F2 87
R4 R2
4 > Busbar Protection 74
Busbar Protection and Breaker Fail

 Where breaker fail protection is applied to a system, back


tripping of associated breakers is required in the event of a
breaker failure
 Often, breaker fail protection is arranged in conjunction with
busbar protection tripping circuits to initiate tripping of
breakers on a busbar zone associated with the failed
breaker

5 > Busbar Protection 75


Midos Relays for High Impedance Protection

 Differential Relay MCAG34 or MFAC34


 Supervision Relay MVTP31
 Tripping Relay (Hand Reset) MVAJ13
 No Volt Relay MVAX12
 Zone Indication Relay MVAA13

6 > Busbar Protection 76


Modern Low Impedance Busbar Protection
 Fast
 Modular scheme design allows relays to relate to each circuit and
function of the protection. This enables the user to easily
understand the principles of application
 High sensitivity for phase and earth faults. Protection for each
phase can be relatively independent
 Earlier schemes were less stable than high impedance schemes.
Modern schemes incorporate saturation detectors and are extremely
stable
 Duplicate measuring circuits are included
 Current transformers can be:
 Of different ratio
 Of relatively small output
 Shared with other protections
 Current transformer secondary circuits are not switched
 Continuous supervision of CT circuits and constant monitoring of
vital circuits are included
7 > Busbar Protection 77
MBCZ 10 Single Bus Protection
Z1 Z2

F1 F2 BS F3 F4

FM1 FM2 BSM FM3 FM4

Z1 Z2
ZCK ZCK

Z1 ZCK Z2

8 > Busbar Protection 78


MBCZ 10 Double Bus Protection
BS
Z1 Z2

Z3 Z4

BC1 F3 F4 BC2
F1 F2

BCM FM2 BCM


1 FM1 BSM FM3 FM4 2

Z1 Z2
Z3 Z4
ZCK ZCK

Z1 Z3 ZCK Z2 Z4

9 > Busbar Protection 79

You might also like