Professional Documents
Culture Documents
Busbar Protection
Busbar Protection
Busbar
Including High Impedance, Protection
Frame Leakage and
Directional Comparison
Principles
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical
> Busbar Institute. All rights reserved.
Protection 1
Busbar Protection
F1 F2
F1 F2
Reliable
Failure could cause widespread damage to the substation
Stable
False tripping can cause widespread interruption of
supplies to customers
Discriminating
Should trip the minimum number of breakers to clear the
fault
Fast
To limit damage and possible power system instability
CAUSES
Insulation failures
Circuit breaker failures
Falling debris
Isolators operated outside their ratings
Safety earths left connected
Current transformer failures
THEREFORE:
CIRCUIT BREAKERS SHOULD BE TRIPPED AND
LOCKED OUT BY BUSBAR PROTECTION
ADVANTAGES
1. Simple and economic form of protection
2. Ideal for the protection of phase segregated switchgear where
earth fault protection only is required
DISADVANTAGES
1. Insulation is required between switchgear sections
2. It is not possible to discriminate between faults on two sets of
busbars running through common switchgear frames
3. Care must be taken in construction of the substation in order to
ensure that the fixing bolts do not come in to contact with the
steel reinforcing of the concrete
G H J K
Frame-earth
fault relay
64
Switchgear frame
Outgoing feeder
Frame-leakage current Switchgear frame
transformer bonding bar
I F = I 1 + I2
Generator
Earth bar
I1 + I2
I1 I1 I2
External Fault
IF=I1 +I2
I1+ I2
I1 64
>10Ω I1 I2
<1Ω
I1+ I2
Frame
Setting of
IF=I1 +I2 Instantaneous E/F
System Relay (64)
I2 64 Earthing
Frame
Earth Bar
Resistance = < 0.3 IF(Min)
Insulation I1 I2 = > 0.1 IF(Max)
>10Ω
Substation
Earthing
Electrode
<1Ω
Disadvantages:
Insulation of switchgear frame and between sections
Insulation of cable glands to prevent spurious currents during through faults
Insulation Barrier
Zone 1 Zone 2 Zone 3
A B C
64
Z1
64
Z2
Trip ‘A’ 96 96
A B1 96 96 Trip ‘C’
B2 C
Trip ‘B’
Insulation Barrier
Zone 1 Zone 2
A B C
0.2 -1 SEC.
64 64
Z1 Z2
B1 B2
Trip ‘B’
64 64
Z1 Z3
+ -
M1 M2 R a 96
A
b
96
D1
96
D2
96
B1
96
B2
c 96
d C
5 > Busbar Protection 15
Frame leakage protection
Check feature
G H J K
Frame-earth
fault relay
Neutral check relay
64
64 CH
CSS-Z2 96
B2
96
C
Trip Supply
Supervision
Alarm
64CH-2 64Z1-2 Relay
74
64Z2-2
74-1 Lamp
74-2 Buzzer
In Out
Lamp
CSS-Z1 Lamp
In Out Lamp
CSS-Z2 Lamp
Alarm
Supply
Supervision
8 > Busbar Protection 18
Directional Comparison Scheme
Load
current
R R
Phase to earth external fault,
scheme (a)
+
Trip
(a)
R R
Trip
+ BR
(b)
9 > Busbar Protection 19
Directional Comparison Scheme
R R
+
(a) Trip
Load
current
Trip
+ BR
(b)
0 > Busbar Protection 20
Phase Comparison Scheme - External Fault
A A
B B
X Y X Y
Trip + Trip
+
Current Transformer
Secondary Current
B A B Relay Operation A B A
Feeder X Feeder Y
A
A
B
B
X Y + Trip
X Y + Trip
Current Transformer
Secondary Current
A B A Relay Operation
A B A
Feeder X Feeder Y
External Fault
Internal Fault
G H J K
87
Differential
relay
G H
A
B
C
N
87A 87B 87C
Differential relay
RST
Metrosil
87
RST
Y R ZM X
ZM
RR
RCT RL RL RCT
IF
IF
RS
V
RL RL
MFAC14/34
Voltage calibrated with internal high impedance
VK +50% IeK
ICK
Exciting Current (Ie)
VF RST X
Y Zm Zm
R
IF
VF = IF.R
I
= IF. Y (R CT + R LX )
IR
Effective setting
IP = T.(IR+nIe)
Or IP = T.(IR+ nIe+IM+ISR+IV)
7 > Busbar Protection 37
Use of fault setting resistor
I0P
ISR IR
RST
RSR
RR
I0P = IR + ISR
RST
VM
VS
V RR
For heavy internal faults large voltages may develop across relay +
Stab. Resistor.
>3kV Voltages – must use Metrosil
VP = 2 2VK (VF - VK )
VK = Knee point voltage
VF = Max. RMS voltage if C.T. didn’t saturate
= IF(RCT + 2RL + RST + RR)
For Metrosil:
V I=RMSCIβ (D.C.)
2VS 0C
=
.52 (A.C.)
9 > Busbar Protection 39
Use of Non Linear Resistors
INLR IR
RST
VMLR
VS R
RR
Typical currents:-
30mA for use with 1 amp CTs
100mA for use with 5 amp CTs
I1 I2 I3 I4
I1 = I2 + I3 + I4
I1
RST I3 I4
I2
V R
Super
ZM2 ZM4 ZM3
Vision RR
Relay
I1
CT1 open circuit, I1 flows through magnetising impedance and relay circuit
in parallel
A
B Zone bus
C wires
N
95
X
95X
Bus wire shorting contacts
95
X
Supervision
95 relay
Metrosil Stabilising
resistors resistors
V V V
87 87 87
F1
F1 Interlocked
Circuit F1 Overcurrent
Protection Relay
F3
Circuit
F3 Circuit Protection
Protection
Busbar
F4 Busbar Busbar Protection
Protection Protection
Interlocked
F2 Overcurrent F3
Relay
F2
F2
(a)Overlapping C.T.s
Zone G Zone H
BS
BC BC
Zone J
Zone A Zone B
87A 87B
Check Zone
87
CK
A B C D
a c d
b
r
m
Buswires
Reserve Bar
Main Bar
R
On-Load Transfer
M
b1 a1 b2 a2
c1 c2
b1
a1
c1
b2
a2
c2
M
R
A.C.
N Buswires
CH
M
b1 a1
Check
Zone
CTs
Normally
Shorted
b1
a1
M
N AC
R Buswires
CH
N
5 > Busbar Protection 55
Tripping Circuits
c2 96
H1
96
H2
D.C. Buswires
80T
IF
T T
C C C
A A A
B B B
D E F
G H K
T T
C C C
A A A
B B B
IF D E F
G H K
T T
C C C
A A A
B B B
D IF E F
G H K
T T
C C C
A A A B B B
E F
D
G H K
G H K
G Vs H
Relay K
Circuit
Relay Vs Vs > TxIFx(H+K+C)
Circuit
Relay
G Circuit H K OR: -
2 > Busbar Protection 62
Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
Rated stability limit phase to T
phase external fault
T T
C C C
IF
A A A B B B
E F
D
G H K
G H K
G Vs H
Relay K
Circuit
Relay Vs Vs > TxIFx(A+G)
Circuit
Relay
G Circuit H K OR: -
3 > Busbar Protection 63
Phase and earth-fault protection for busbars and other
primary plant connections (one relay per zone)
Rated stability limit phase to T
phase external fault
T T
C C C
IF
A A A B B B
E F
D
G H K
G H K
G Vs H
Relay K Vs > TxIFx(B+H)
Circuit
Relay Vs
Circuit
Relay
G Circuit H K whichever is the
greatest
4 > Busbar Protection 64
Busbar Protection With Separate Relays Per Circuit
Breaker – Basic Scheme
1
+ 2
1 2 +
+
1 +
2
TR
TR
D D
CH CH
+ 1 2 +
1
+ 2 1
1
+ + 2 2 +
+ + +
2 1 2 +
1
TR TR TR
TR
D D
CH CH
+ 1 2 +
+
STN
TR
TR
BT BT
1
+ D 2
+
D D
CH
CH CH
+ 1 + STN 2 +
TR TR TR TR
BT BT
D
2 1 +
D D
CH
CH CH
+ 1 + STN 2 +
Reserve/ Transfer
By-Pass
Isolator By-Pass
Isolator
Reserve
Transfer Transfer
CB. CB.
Transfer
87
87
T1 T3
T4 T2
F4 F2
87 F1 87
R1 F3
R3
T1 T3
T4 T2
87 F4 F2 87
R4 R2
4 > Busbar Protection 74
Busbar Protection and Breaker Fail
F1 F2 BS F3 F4
Z1 Z2
ZCK ZCK
Z1 ZCK Z2
Z3 Z4
BC1 F3 F4 BC2
F1 F2
Z1 Z2
Z3 Z4
ZCK ZCK
Z1 Z3 ZCK Z2 Z4