[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22

Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

All the damaged Fire Detector is fixed,


1 High
Fire Detector found in
damage condition
Detectors to be
replace.
And also all detectors
are checked,
Done

This area have to


Fire detection and
Fire detection and dismantle, due to this
2
High
suppression system not
provided at the shop floor
suppression system to
be provided at the
we are not providing
fire detection or

shop floor
suppression system

Instruction and training


Shoes should be wear provided regarding
3
High Some worker found
working without shoes
by each employee
inside the factory.
wear safety shoes.
Now maximum worker
Done

in shoes.

4
High Safety railing not
provided in the area.
Safety railing should
be provided
Railing provided from
stair side.
Done

Done ●
Risk Level : High, Medium , Low Under Progress ●
Pending ●
[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22
Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

Panel Door Locked,


5 High
Electrical panel door found
in open condition.
Panel door must be
lock.
Also instruct
technicians for not
Done

repeat this again

Instructed to MCO
Safety guard must be
6 High
During die maintenance
safety guard not used.
used during die
maintenance.
Workers, for use
safety chain during the
Done

maintenance

Instruct to all Die


During die maintenance Proper PPE’s must be
7
High
worker found without
safety shoes and gloves
adhere during die
maintenance activity.
maintenance workers
for wear safety shoes
Done

and gloves

Safety Guard provided


Also instruct to tool
8
High Grinder found without
safety guard
Safety guard to be
provided for grinder/
room in charge for
take care of this type
Done

unsafe act

Done ●
Risk Level : High, Medium , Low Under Progress ●
Pending ●
[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22
Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

MSDS to be displayed
9
High Gas Cylinder kept without
MSDS
in the gas cylinder
storage area.
MSDS of DA &
Oxygen Displayed
Done

This is silo area, There


Industrial aluminum is no any height work
Wooden Ladder kept
10
High
in use to carried out
height work.
ladder to be provided
for height work and
activities performed,
stair kept here by
Done

other activities. unknown person, now
removed

Automatic Celling
11
High Fire detection not
provided in Silo area.
Fire detection to be mounted FE, Installed
provided in Silo area. at top side of every
Done

sillo.

Welding m/c Rejected


Electrical connection
12
High
without power plug may
risk to electrical hazard.
Power plug to be used by us, and instruct to
to avoid the hazard. concern for never use
Done

naked wire in socket

Done ●
Risk Level : High, Medium , Low Under Progress ●
Pending ●
[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22
Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

Fire pump house


clean,
There should be
13 High
Fire pump house found in
dirt condition.
routine cleaning in fire
pump house.
Also cleaning add in
daily check list. For
Done

avoid this issue in
future

Fire pump house


clean,
There should be Also cleaning add in
14
High Water spillage on floor in
Fire pump house.
routine cleaning in fire daily check list. For
pump house. avoid this issue in
Done

future

This is not off, this is in


Manual mode, All
DG and jockey pump
15
High DG and jockey pump
found off
should be kept in auto
mode
Three pump are
working properly auto
Done

or manual mode.

Leakage arrested &


16
High Water leakage observed
in the area.
Leakage point to be
rectified and corrected.
Rectified Done

Done ●
Risk Level : High, Medium , Low Under Progress ●
Pending ●
[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22
Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

17 Low
Water leakage observed
in the area.
Leakage point to be Leakage arrested &
rectified and corrected Rectified
Done

Welding Machine Not


MCB should be
18 High
Welding machine found
without MCB
provided in welding
machine
in use, another
welding machine
Done

purchased

Leakage arrested.
19 High
Water leakage observed
in fire hydrant pipeline.
Leakage point to be
rectified and corrected.
Hydrant head
Replaced,
Done

Safety cover to be
20
High Motor fan belt found
without safety cover
provided in motor fan
belt.
Motor fan belt cover Done

Done ●
Risk Level : High, Medium , Low Under Progress ●
Pending ●
[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22
Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

Hose Pipe found


21 Medium damaged in Fire Hose
Box.
Damaged Hose pipe to
be replace.
Hose pipe replaced Done

22 Medium
Fire hydrant found blocked
by material.
Fire hydrant way
should be clear
Materials Cleared Done

Fire detection system Heat Detector's


23
High Fire detection system not
provided in mold area.
to be provided in mold available top side of
area. this area
Done

Panel closed also


24 High
Electrical panel door found
open
Electric panel door
should be closed
instruct concern
person for not repeat
Done

again

Done ●
Risk Level : High, Medium , Low Under Progress ●
Pending ●
[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22
Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

Hose reel was open


Hose Reel to be
25 High
Hose Reel found missing
in Fire Hose Reel Drum.
provided in Fire Hose
Reel Drum.
for drum replace, now
hose reel drum
Done

replaced

Proper stair case to be


26 High
Stair case found in
damaged condition.
provided to avoid any
fall hazard.
Emergency stair
repaired
Done

Safety mesh cover not Safety mesh cover to Safety Mesh Cover
27 High provided in exhaust fan
backside.
be provided in exhaust provided in exhaust
fan backside. fan
Done

Fire alarm record


28
High Fire alarm record not
available
Fire alarm record
should be provided
register maintain
started
Done

Done ●
Risk Level : High, Medium , Low Under Progress ●
Pending ●
[E-Pack]SHEE Audit NCRs Audit Date : 25/04/22
Risk
SN Issue Observed NCR Photo Recommendation Action Taken Compliance Photo Target Date Status
Level

CO2 Fire Extinguisher CO2 Fire Extinguisher


29 Medium kept at unidentified
location.
to be kept at identified
location.
extinguisher kept at
identified location.
Done

Safety cover to be
30 High
Motor fan belt found
without safety cover
provided in motor fan
belt.
Safety Cover will be
Provide till target date
Done

Water cooler front side Water Cooler


31
High
safety fencing found
damaged.
Water cooler safety
fencing to be change
Destroyed, due to not
safe for use
Done

This area is OSD


area, this rejected
Scrap EPS material kept Scrap EPS material to
32 High at unidentified location be kept at right
location
material was kept for
segregate
Done

Removed after
segregation done

Done ●