The document describes the principles and components of air conditioning systems, as well as some common troubleshooting issues. It explains that air conditioning works by transferring heat from inside a space to outside using a refrigeration cycle. The main components are a compressor, condenser, expansion valve, and evaporator. Common issues addressed include reduced cooling, compressor malfunctions, unusual sounds, high or low pressures, and refrigerant issues. Troubleshooting tips are provided for each problem.
The document describes the principles and components of air conditioning systems, as well as some common troubleshooting issues. It explains that air conditioning works by transferring heat from inside a space to outside using a refrigeration cycle. The main components are a compressor, condenser, expansion valve, and evaporator. Common issues addressed include reduced cooling, compressor malfunctions, unusual sounds, high or low pressures, and refrigerant issues. Troubleshooting tips are provided for each problem.
The document describes the principles and components of air conditioning systems, as well as some common troubleshooting issues. It explains that air conditioning works by transferring heat from inside a space to outside using a refrigeration cycle. The main components are a compressor, condenser, expansion valve, and evaporator. Common issues addressed include reduced cooling, compressor malfunctions, unusual sounds, high or low pressures, and refrigerant issues. Troubleshooting tips are provided for each problem.
The document describes the principles and components of air conditioning systems, as well as some common troubleshooting issues. It explains that air conditioning works by transferring heat from inside a space to outside using a refrigeration cycle. The main components are a compressor, condenser, expansion valve, and evaporator. Common issues addressed include reduced cooling, compressor malfunctions, unusual sounds, high or low pressures, and refrigerant issues. Troubleshooting tips are provided for each problem.
inside Accommodation for Human Comfort. (By Cooling, Heating, Humidifying, depending on outside temperature) The desired & Most Comfortable range for Humans is: Temperature: 22-24 Deg. C & Relative Humidity: 40-60%. Comfort Zone Comfort Zone How Its Done Air-con System is like a Heat Pump: I.E. Transferring Heat from inside accommodation to Outside. (Same principle applies to Refrigeration System as well) How Air Conditioners Work Principle of Refrigeration Cycle: Saturation temperature (Boiling Point) of a liquid varies with change in pressure) . At Sat. Point is like Transition phase. An addition of heat will boil (evaporate) the liquid into vapour and an removal of heat will condense it to liquid. Temp. remains same during phase change & the heat added/removed is called latent heat(Panas Laten). At Higher Pressure Boiling Point (Temp.) is higher & at Lower Pressure Boiling Point is lower. E.G. Water boils at 100 deg C at Atm. Pressure. If We reduce pressure (as in FWG), water boils at abt 500 C. Same way in Boiler water boils at 1200 & above (when pressure is higher) Boiling Point Variation with Pressure Principle of Refrigeration Cycle:
When a liquid boils or evaporates it absorbs heat
(from hot surroundings) and when it condenses it is releases heat (to a cooling medium). So we want a Refrigerant material which: Absorbs heat from accommodation while evaporating (for example at 18 Deg C) [ At Low Pressure] and Releases heat to outside atmosphere (Air or Water e.g. at 40 Deg C) while condensing, [at High Pressure]. Boiling Point Variation with Pressure Principle of Refrigeration Cycle: Principle of Refrigeration Cycle: Main Components Compressor: Reciprocating single or two stage compressor is commonly used for compressing and supplying the refrigerant to the system. Condenser: Shell and tube type condenser is used to cool down the refrigerant in the system. Receiver: The cooled refrigerant is supplied to the receiver, which is also used to drain out the refrigerant from the system for maintenance purpose. Drier: The drier connected in the system consists of silica gel to remove any moisture from the refrigerant Main Components Solenoids: Solenoid valves are used to control the flow of refrigerant into the hold or room. Expansion valve: Reduces the pressure & regulates the refrigerant to maintain the correct hold or room temp. Evaporator unit: The evaporator unit act as a heat exchanger to cool down the hold or room area by transferring heat to the refrigerant. Control unit: The control unit consist of different safety and operating circuits for safe operation of the refer plant. Main Components Capacity Controller: Controls the output of the plant depending on the load demand. (e.g. Change in Atmosphere Temperature, Frequent Opening of Doors, More people or fresh food stored in the fridge rooms). By unloading the Suction Valves. Safety Devices: a)Low Pressure or LP cut off. b)High pressure or HP cut out c)Oil differential cut out d)Relief valves e)Solenoid valves f)Oil heater Common Troubles We shall discuss following common troubles in next session. Please send me the specific problems you are facing on your ships: a)No or reduced cooling Effect b)Compressor Not Working c)Reducing oil level in compressor d)Unusual Sound from Compressor e)High Compressor Discharge Temperature f)Compressor Starts But Stops immediately g)Compressor Start and Stops Frequently h)Compressor is Running Continuously (fridge) i)Discharge Pressure Too Low j)Discharge Pressure Too High Common Troubles k) High Pressure Switch Cuts-Off l) Suction Pressure Too High m) Suction Pressure Too Low n) Low Pressure Switch Cuts-Off o) Evaporator Coil Icing p) Evaporator Not Cooling q) Reduced Cooling Capacity r) Icing on Suction Pipe No or Reduced Cooling Effect Less Refrigerant quantity (undercharged) Too much leakage from the Accommodation (Doors & portholes always kept open) Air conditioner unit is under capacity Compressor valve damage or ineffective compression due to Piston/Liner/Piston ring issues. Expansion valve not effective or incorrect size Filter drier or strainer is clogged (Refrigerant) Air filter is clogged Evaporator is dirty/clogged Fan motor belt loose or slip Temp. setting of thermostat too high or sensor placed at wrong place Duct damper is closed, Duct trunking corroded (leaking), Compressor Not Working A) Check the Power supply, Motor, Belts or any Trip/Alarm on panel.
B) Check if broken: Reasons:
a) No correct assembly. b) Not genuine spare parts c) Alarms & Trip malfunction. d) Suction & Discharge valves problem e) Oil pressure not enough f) Under capacity compressor (Over load) g) System malfunction (Liquid carry over, over charge, air or moisture in the system) Reducing oil level in compressor Due to leakage or increase in consumption of lube oil due to following reasons: Nozzle or filter clogged (Ensure that the nozzle in oil return line or filter in solenoid valve is cleaned and not choked) Foaming of oil due to liquid in suction line (Foaming of oil may arise due to liquid refrigerant entering the crankcase. Replenish oil and troubleshoot cause of liquid in suction of compressor) Drive side seal leaking (The compressor is provided with oil seal at the drive side. Ensure it is not leaking and renew it if required) Worn out piston rings/ liner leading to oil carryover in the system (Renew the compressor piston rings or liner) Oil separator not working properly Unusual Sound from Compressor This may be due to trouble with mechanical components inside the compressor: Incorrect alignment of compressor and motor (Check the alignment and set motor and compressor in one line) Loose foundation (Ensure that the compressor foundation is secured and all foundation bolts are checked for tightness) Loosening of driving belt (Ensure to check the elasticity of the belt and renew if the belt is slack) The capacity control setting is too high, leading to knocking sound during starting (Reduce the capacity control setting) The oil pressure is low (Ensure that the oil level is maintained and no foaming of oil is developed. Replenish or refill the lube oil if required) High Compressor Discharge Temperature Excessive suction temperature due to less refrigerant in the circuit (Recharge the circuit to maintain refrigerant quantity in the circuit. Ensure Expansion valve is of correct type and is set properly and supplying enough to the evaporator. Leak in the discharge valve leads to generation of heat (renew the leaky valve) Leak in the safety valve (Renew safety valve) Compressor Starts But Stops immediately Low pressure cut out gets activated (Ensure that all the suction line valves are in open condition, the refrigeration is properly charged and the low pressure cut out is not defective) Defective oil pressure cut out (Check for proper functioning of oil pressure cut out and replace the defective cutout) Defrosting timer is getting activated frequently (If the defrost timer is getting activated frequently, leading to cutout of compressor, check and repair defrost timer) (Fridge) The lube oil level is below required level (This can be because of leakage of lube oil from seal or carry over of oil. Rectify the leakage and refill the oil level) Foaming of oil leading to reduced oil pressure (Ensure no foaming takes place, renew the oil if required) Motor overload cut outs are activating (Ensure that electrical motor trips are working properly.) Compressor Start and Stops Frequently Applicable mainly for Fridge: Wrong Setting of Cutouts: It may be because the high pressure (HP) cutout is set too low or LP cutout is set too high (Check and change the setting to limit as per makers) Differential Setting Gap is Small: The low pressure (LP) cut out is provided with starting and stopping pressure setting. If the setting gap is too small, it will lead to frequent cut-in and cut-out of the compressor (Change the setting and increase the span between starting and stopping compressor pressures.) Defective Valves: If the compressor discharge valve is leaky or the line solenoid valve is not closing properly, this will lead to variation in sensor pressure and result in frequent cut-in and cut-out of compressor (Replace all the defective valves) Clogged Suction Filters: Compressor is provided with a filter in the suction line. If that is clogged, it will lead to frequent LP cut out (clean the filter) Compressor is Running Continuously (fridge) Not sufficient Refrigerant for cooling evaporator (Ensure thermostatic expansion valve is working properly and clean the filters inside TEV) Thermostat low pressure cut-out not activated at low temperature/ pressure (Correctly set the LP cut-out to correct setting) Refrigerant charge is low in the circuit (Check for leakage of refrigerant and charge with required refrigerant) Discharge Pressure Too High (High Pressure Switch Cuts-Off) Overcharge of refrigerant Air inside refrigerant circuit Condenser is dirty, water flow too little, inlet water temperature too high, flow direction wrong, cooling water short circuit (broken division plate) Refrigerant discharge valve blocked or closed Air conditioner system is under capacity Discharge Pressure Too Low Refrigerant is undercharged Excessive condenser water flow Condenser outlet water temperature too low Air conditioner unit is over capacity Ineffective compression of compresor or valve is damaged Ambient temperature too low Suction Pressure Too High Refrigerant is overcharged Expansion valve is oversized Air conditioner unit is under capacity Excessive opening of Thermo valve Ineffective compression of compressor or valve is damaged Ineffective contact of sensor bulb of Thermo valve Suction Pressure Too Low / Low Pressure Switch Cuts-Off Refrigerant is undercharged Evaporator coil is dirty Temperature setting of thermostat too low Duct damper is closed Duct resistance too high Supply air short-circuit Expansion valve undersized Air conditioner unit is over capacity Not enough opening of thermo valve Expansion valve clogged Ineffective expansion valve Air filter is clogged Room temperature is too low Both Low Pressure and High Pressure Too High Condenser dirty, not enough water flow, inlet water temperature too high Overcharge of refrigerant Air inside refrigerant circuit Excessive opening of thermo valve Ineffective contact of sensor bulb of thermo valve Condenser water is circulating in the reverse direction Air conditioner unit is under capacity Both Low Pressure and High Pressure Too Low Expansion valve undersized or clogged Refrigerant is undercharged Filter drier or strainer is clogged Evaporator coil is dirty Excessive condenser water flow, cooling water temperature too low Air conditioner unit is over capacity, Not enough opening of thermo valve Temperature setting of thermostat too low Duct damper is closed, Duct resistance too high Air filter is clogged, Supply air short-circuit Room temperature is too low, Ambient temperature too low High Pressure Too Low and Low Pressure Too High
Compressor valve damaged or ineffective
compression Evaporator Coil Icing Too low temperature setting ( Increase the coil temperature by adjusting TEV or it’s sensor) The coil capacity is less (Install large capacity evaporator coils) Defrost is not operational (Check if the defrost system is functioning at regular intervals)
Icing on Suction Pipe Air conditioner unit is over capacity Air filter is clogged Ambient/ accomodation temperature is too low Evaporator is dirty, Fan motor belt loose or slip Fan motor in rotating in the reverse direction Temperature setting of thermostat too low Duct damper is closed, Duct resistance too high Supply air short-circuit Routine Maintenance 1) Leak test by flame or electronic meter. 2) Defrosting evaporator coil. 3) Compressor oil level check and top up as required by Oil Charging pump. 4) Check refrigerant level in compressor 5) Clean condenser routinely. 6) Clean air filter from time to time. 7) Charging the Refrigerant (Gas or Liquid charging) 8) After Compressor maintenance or opening the system (Use Vacuum pump & N2 purging) 9) Replace oil separator cartridge or Silica Gel (as par maker’s recommendation) Symptoms of Good Working System 1) Good cooling with normal parameters 2) No Loss of Refrigerant. (Normal Refrigerant level in condenser is seen) 3) No loss of compressor oil (Normal oil level maintained) 4) No frosting on suction pipe (Should be slight cold). 5) Suction pressure and discharge pressure in normal range. 6) Oil pressure 2-3 bars more than suction pressure. 7) Normal sound and vibrations. To be continued