Commissioning: Dppu Juanda, September 2017 Pertamina Aviation Competence Education
Commissioning: Dppu Juanda, September 2017 Pertamina Aviation Competence Education
This material is solely for the use of partner’s personnel. No part of it may be circulated, quoted, or reproduced for distribution outside the
organization without prior written approval from PT Pertamina(Persero). This material was used by PT Pertamina(Persero) during an oral
www.pertamina.com
presentation; it is not a complete record of the discussion.
AUTHOR
- AGIL FITRANTO (749704)
Pengalaman Kerja:
- Asst Pengisian SHIPS
- Spv. RSD DPPU Hang Nadim
- Spv. Maintenance DPPU Hang Nadim
- Jr Inspector Aviation Quality
Pengalaman Lain:
- Tim STK Pertamina Aviation 2014, 2016
- Tim KKEP 2015, 2017
- Tim Pengadaan Kendaraan Pengisian (Assessment & Quality) 2013, 2016
AGENDA
- Tujuan Pelatihan
- Pendahuluan - Overview Project
- Pendahuluan - Overview Pre-Commissioning
- Pendahuluan – Referensi
- Tahapan Commissioning
- Kriteria Acceptance
- Study Kasus
1. TUJUAN PELATIHAN
www.pertamina.com
2. PENDAHULUAN
Overview Project
Hydrant Facilities
Airport Depot Facilities
Intake Facilities
2. PENDAHULUAN
Overview Project
PC & KONTRAKTOR
MECHANICAL
PRESSURE TESTING FLUSHING/SWABBING COMMISSIONING
COMPLETION
• PSSR (Safety Review) • Hydrotest • Swabbing / Pigging •
• Specification • Pneumatic Test • Cleanliness
Criteria/ Kesesuaian inspection
Desain (borescope)
• Holiday Test, Pull
Test, NDT, X-ray test
2. PENDAHULUAN
PSSR
PSSR
- Acceptance criteria : pig visually clean, tidak ada defect berlebihan, pig dry (tidak ada
perbedaan berat awal dan akhir)
- Untuk kondisi pipa berkelok-kelok digunakan swabbing – intelligence pigging
- Pressure yang digunakan pneumatic < 4 bar
2. PENDAHULUAN
Overview Pre - Commissioning
Cleanliness Inspection
- CCTV dapat digunakan untuk melihat kondisi internal pipa, coating, partikel dll
2. PENDAHULUAN
Referensi
Worldwide Aviation Fuel Standards used :
EI1540 Design, Construction, Operation and Maintenance of Aviation Refueling Facilities
EI1560 Recommended practice for operation, inspection, maintenance and commissioning of aviation fuel
hydrant systems and hydrant system extensions.
EI1581 Specifications and qualification procedures for aviation jet fuel filter/separators
EI1584 Four-inch hydrant system components and arrangements
EI1585 Guidance in the cleaning of airport hydrant systems
EI1596 Design and construction of aviation fuel filter vessels
JIG 1, Issue 11, Aviation Fuel Quality Control & Operating Standards for Into-Plane Fuelling Services
JIG 2, Issue 11, Aviation Fuel Quality Control & Operating Standards for Airport Depots & Hydrants
JIG Bulletin No.35 Soak Testing
JIG Bulletin No.39 Fuel Hydrant Comissioning
3. TAHAPAN COMMISSIONING
DOCUMENTATION
PIPE FILLING LINE FLUSHING SOAK TESTING INTEGRITY TEST
AND HANDOVER
• Prosedur • Flushing avtur • Uji perendaman • Hydrant Integrity
Comissioning dengan dengan durasi Test
• Organisasi kecepatan dan pemeriksaan • Static/Dynamic
Comissioning tertentu dan mutu Test
pemeriksaan
visual
3. TAHAPAN COMMISSIONING
Requirement yang Harus dipenuhi sebelum Commissioning:
4 Co m m issio ning Me tho do lo g y
Do e s th e c o m m issio n in g w o rk h a v e c o n firm e d Ha s th e syste m b e e n d e sig n e d to e n su re th e Do e s th e so a k p e rio d b e in g c o m m issio n e d
a v
th e m e th o d o lo g y to b e a p p lie d k flu sh e d p ro d u c t b e re c e iv e d in th e d e sig n a te d h a v e su ffic ie n t tim e fo r so a k te st
sto ra g e ta n k
Do e s th e fu e l q u a lity c o n tro l p ro c e d u re s Do e s th e re te n tio n sa m p le o f fu e l ta ke n b e fo re
b w
im p le m e n t in th e c o m m issio n in g p ro c e d u re s Ha s th e flu sh je t fu e l to th e a p ro n p a ss th ro u g h fillin g a s a c o n tro l
l
filte r w a te r se p a ra to r
Are th e re th e d o u b le b lo c k b le e d v a lv e s Do e s th e re te n tio n sa m p le o f fu e l ta ke n fro m a ll
c x
p h ysic a lly in sta lle d in th e h yd ra n t c h a m b e rs lo w p o in t in th e syste m a fte r flu sh e d
Ha v e th e c o lo u rm e tric a n d g ra v im e tric
m
e sta b lish e d in th e c o m m issio n in g o f h yd ra n t p it
Are th e re Em e rg e n c y Sto p Bu tto n s p h ysic a lly Do e s th e c o lo rim e tric m e m b ra n e te st ra tin g
d
in sta lle d in th e a p ro n a n d o th e r a re a y le ss th a n 4 a t d ry sta g e a n d g ra v im e tric te st
Are th e re te stin g fo r sta tic a n d d yn a m ic o f ra tin g le ss th a n 0.2m g / l
n
Do e s th e fillin g o f a v tu r b y g ra v ity flo w s a n d h yd ra n t p it v a lv e s
e v e n tin g is c a rrie d o u t a c c o rd in g to th e Ha v e th e sig n e d "NO T IN USE" b e e n a p p lie d in
z
m e th o d o lo g y Are th e re te stin g fo r in te g rity le a k te st o f h yd ra n t h yd ra n t p it v a lv e
o
syste m b e p e rfo rm e d
Wh a t is th e flu sh in g q u a n tity a n d h o w m a n y Is th e re n o tific a tio n to a u th o rity a n d
f
tim e s o f fille d a v tu r p Wh a t is th e so a k q u a n tity a a sta ke h o ld e rs o f c o m p le tio n o f c o m m issio n in g
p ro c e d u re s b e e n e sta b lish e d
Do e s th e c irc u la tio n o f h yd ra n t syste m w ill b a c k Are th e syste m d e sig n e d to fillin g in la rg e
g
to a irp o rt d e p o t sto ra g e ta n k q q u a n tity o f fu e l to e n su re a ll m a in su p p ly lin e s Is th e re a n o tific a tio n p ro c e d u re s in p la c e to
a re im m e rs b y je t fu e l fo r so a k e n su re th a t th e c o m m issio n in g p ro c e d u re s
ab
Do e s th e c o n d itio n o f sto ra g e ta n k b e fo re fille d h a v e b e e n c o m p le te d a n d h yd ra n t p it v a lv e s
h
w ith je t fu e l is in sp e c te d Ha s th e c o m m issio n in g p ro c e d u re e sta b lish e d a re a v a ila b le fo r fu e llin g
r
fo r h o w m a n y d a ys o f so a k te st
Do e s th e HH a la rm o f sto ra g e ta n k th a t
d e sig n a te d to re c e iv e flu sh p ro d u c ts a lre a d y Ha v e c o n firm a tio n b e e n g iv e n fro m h yd ra n t
i
in sp e c te d a n d th e v e n t n o zzle o f sto ra g e ta n ks s p u m p a n d FWS sh ip p e d p re se rv a tiv e o il a n d
a lso in o p e n c o n d itio n lin e d w ith ru st in h ib ito r to p re v e n t c o rro sio n
Pipe Filling
- Pengisian pipa dengan avtur secara gravitasi dengan venting dibuka tiap section (10 psi)
- Pengisian menggunakan avtur dari batch yang sama untuk memudahkan acceptance mutu
avtur dengan membandingkan hasil pemeriksaan akhir dengan baseline
- Jaga jarak aman 15 m dari tiap venting point dan persiapkan spill kit dan firex di dekat venting
point
- Siapkan tampungan yang cukup besar seperti HFC atau bridger untuk menampung produk
venting
- Pada tahap ini, filter elemen dilepas
- Mulai dilakukan LOTO pada pompa dan valve pada tahap ini
3. TAHAPAN COMMISSIONING
Line Flushing
- Sebelum flushing, ditentukan tangki sumber dan tangki yang akan menerima product
(sebaiknya tangki storage, bisa juga tangki temporer/HFC/Bridger)
- Flowrate disesuaikan dengan flowrate operasional, dan memperhitungkan kecepatan laminar
produk (minimal 1 m/s ; direkomendasikan 3 m/s ; jika CU rendah, maksimal 5 m/s).
- Kenaikan flowrate secara perlahan dan sebaiknya tidak terhenti s.d selesai proses flushing
3. TAHAPAN COMMISSIONING
Line Flushing
- Dilakukan QC selama proses flushing:
KEGIATAN LOKASI KRITERIA BASELINE
Visual Check (CWD) Downstream (low point Clean & Bright Visual check diambil
dan Hydrant Pit) pada upstream draining
point
Double Membrane Downstream Hydrant 4 (dry), 2 difference Double membrane
Colorimetric Pit, Downstream antara upstream dan upstream dari sarfas
pipe/vessel drain point downstream max
Membrane Grafimetric Downstream Hydrant 0.2 mg/liter max -
Pit
Microbial Test (optional Storage tank Negligible -
jika ada potensi)
Recertification Storage tank On specification dan Last batch quality
komparasi document
- Hasil produk flushing dilakukan draining sampai bersih dan dilakukan resertifikasi. Jika on spek
dan memenuhi kriteria komparasi, produk dapat digunakan kembali
3. TAHAPAN COMMISSIONING
Soak Test
- Soak test bertujuan untuk memastikan tidak ada kontaminasi coating (solvent, rust inhibitor),
welding flux, valve grease
Storage Tank Pipa / Pompa, Refueling
Hydrant* Valve, Hose EI 1529 /
Full Epoxy Sebagian/ Meter, ISO 1825****
Tanpa Epoxy Vessel etc
- Pre Soak sample adalah sample sebelum masa perendaman dan dapat digunakan sebagai
baseline hasil soak testing. Post Soak sample adalah sample yang diambil hasil soak test
SOETTA
- KONSTRUKSI PIPA SOETTA, LINK
- FLUSHING STAGE 1, LINK
- FLUSHING STAGE 2, LINK
- FLUSHING STAGE 3, LINK
- FLUSHING FINAL, LINK