Professional Documents
Culture Documents
S102 Roles Inertia Fault Level Reactive Power
S102 Roles Inertia Fault Level Reactive Power
Generators contribute to
System stability and power quality
Inertia and fault level
What is Inertia
It is the energy stored in generators because they are rotating.
They continue to rotate after the energy source is removed
Inertia
Large spinning machines provide stored energy due to the rotating mass of their rotor, driving turbine shafts etc. Engineers model this as a number of rotating masses. When a disturbance occurs e.g. the unanticipated loss of a generator, the stored energy is released into the system and arrests the rate at which the system speed or frequency changes.
Without wind
With wind
Restorative power
smaller
smaller
unit2
49.8 49.6
frequency
49.2 49 48.8
unit1
48.6 48.4
Hz
49.4
Frequency trace for the combined NI & RoI System - higher inertia
165MW loss 970MW system load
250 50
unit1
200
150 MW
freq
49.6 49.5 Hz
100
49.4
unit 2
50
49
System effects e.g. traditional generation auxiliary plant trips; CCGT flame outs.
Raised with DG&SEE as requiring investigation
Wind turbines
Fixed speed turbines seem to deliver an inertia of around 4.3MWs/MVA which is similar to traditional plant; so do not reduce system inertia. DFIGs and Fully converted wind farms are presently thought to deliver close to 0MWs/MVA; so at present reduce system inertia.
Work done
In order to understand the problem, we have explored what happens to inertia and rate of change of frequency with very high levels of penetration of wind power on the island of Ireland. This is to understand what we need to tackle rather than alarm the present position.
Our Proposal
To seek a modification to the NI Grid Code to require wind turbines to provide inertia at 4 6MWs/MVA. This would need to be harmonised with an equivalent provision in the EirGrid Grid Code and Distribution Codes. This will be a world first and waiting does not seem an option.
Fault level
With wind farms
Power quality
Very low fault level results in excessive voltage dips when equipment is switched on.
GB results
With the expected penetration of wind farms in GB 2010 the minimum fault level is reduced by a few percentage points on average. In some places because traditional generation is off-the bars the fault level is reduced by 70%. This leads to problems with distance protection (the main 110kV system protection). In particular, resistance faults may result in mal-operation of distance protection. The NI situation is likely to be much worse because we only have 3 traditional generating units operating at periods of low fault level.
Our proposal
To ensure that the fault level tools developed by DG&SEE (which assess fault level throughout the range of generation dispatches) are applied to the NI network and to consider what further action may be needed. At the extremewe may need to convert the distance protection schemes to unit schemes which is very expensive. Also, DG&SEE have not considered the knockon effect of low fault level on the distribution protection systems. This may be more serious and potentially intolerable. Further work is required.
Reactive power
Studying the reactive power balance is more complex when embedded generation is included
~
Transmission System
Gen transformer tapped to pump reactive power into the transmission network. Consumption of Reactive Power