Professional Documents
Culture Documents
Chapter4 Trans
Chapter4 Trans
Transformer
Transformer- Introduction
Two winding transformers Construction and principles Equivalent circuit Determination of equivalent circuit parameters Voltage regulation Efficiency Auto transformer 3 phase transformer
2
Transformer- Introduction
Varieties of transformers
3
Transformer- Introduction
Transformer- Introduction
Transformer is a device that makes use of the magnetically coupled coils to transfer energy It is typically consists of one primary winding coil and one or more secondary windings The primary winding and its circuit is called the Primary Side of the transformer The secondary winding and its circuit is called the Secondary Side of the transformer
5
Transformer- Introduction
If one of those winding, the primary, is connected to an alternating voltage source, an alternating flux will be produced. The mutual flux will link the other winding, the secondary, and will induced a voltage in it.
Transformer- Introduction
Transformers are adapted to numerous engineering applications and may be classified in many ways:
Power level (from fraction of a volt-ampere (VA) to over a thousand MVA), Application (power supply, impedance matching, circuit isolation), Frequency range (power, audio, radio frequency (RF)) Voltage class (a few volts to about 750 kilovolts) Cooling type (air cooled, oil filled, fan cooled, water cooled, etc.) Purpose (distribution, rectifier, arc furnace, amplifier output, etc.).
Transformer- Introduction
Power transmission
Transformer- Introduction
Power transmission
Transformer
4.1 Construction
10
Transformer- construction
Transformer- construction
A)
re ty e
B ) S ell ty e
Transformer- construction
13
Transformer- construction
Primar Winding
econdar Winding
H1 H2
Winding Terminals
14
Transformer
15
Transformer
The emf which induced in transformer primary winding is known as self induction emf as the emf is induced due to to flux which produced by the winding itself. While the emf which induced in transformer secondary winding is known as mutual induction emf as the emf is induced due to to flux which produced by the other winding.
16
i v1 e1 e2 v2
Transformer
Acording to Faraday s Law, the emf which induced in the primary winding is,
i v1 e1 e2 v2
dJ e1 = N1 dt
Since the flux is an alternating flux,
mak
sin [ t
e1 = N1
!
d (J
ak
sin [ t ) dt
17
1 mak
[ cos [ t
Transformer
e1 !
1 mak
2Tf cos [ t
i v1 e1 e2 v2
! E1max cos [ t
where,
! 4.44 1J max f
Transformer
e2 = N 2
dJ dt
i v1 e1 e2 v2
E2 rms
E2 E1
4.44 N 2J max f
2 1
k is transformation ratio
19
Transformer
The voltage ratio of induced voltages on the secondary to primary windings is equal to the turn ratio of the winding turn number of the secondary winding to the winding turn number of the primary winding. Therefore the transformers can be used to step up or step down voltage levels by choosing appropriate number their winding turns. In power system it s necessary to step up the output voltage of a generator which less than 30kV to up 500kV for long distance transmission. High voltage for long distance power transmission can reduce current flow in the transmission lines, thus line losses and voltage drop can be reduced.
20
Winding resistances are zero, no leakage inductance and iron loss Magnetization current generates a flux that induces voltage in both windings
E1 !
!
N1 * m [ 2
2
*m [ 2
21
Transformer
i v1 e1 e2 v2
Transformer on no load.
22
Loaded transformer
i
I2
V1
E1 N1 N2
E2
V2 ZL
When a load is connected to the secondary output terminals of a transformer as shown in Figure 4.5, a current I2 flows into the load and into transformer secondary winding N2. The current I2 which flowing in N2 produces flux 2 which opposite by Lenz s law- to the main magnetic flux in the transformer core. This will weaken or slightly reduce the main flux to .
23
Loaded transformer
i
I2
V1
E1 N1 N2
E2
V2 ZL
The reduction of main flux by Faraday s law- could also reduce the induced voltage in primary winding E1. Consequently E1 is now smaller than the supply voltage V1, then the primary current would be increased due to that potential differences. Therefore on loaded transformer, the primary current has an additional current of I1 .
24
Loaded transformer
i
I2
V1
E1 N1 N2
E2
V2 ZL
The extra current I1 which flowing in the primary winding N1 produces flux 1 which naturally react according to Lenz s law, demagnetize the flux 2. Therefore the net magnetic flux in the core is always maintained at original value, it is the main flux (the flux which produced by the magnetizing current).
25
Loaded transformer
i
I2
V1
E1 N1 N2
E2
V2 ZL
The magneto motive force (mmf) source N2I2 at the secondary winding produces flux 2, while the mmf N1I1 produces flux 1. Since the magnitude of 1 equal to magnitude of 2 and the reluctance seen by these two mmf sources are equal, thus N1I1 = N2I2
26
Loaded transformer
Turn ratio
If the primary winding has N1 turns and secondary winding has N2 turns, then:
N1 E1 I2 a! ! ! N2 E2 I1
E1 I ! S1 ! S 2 ! E 2 I
* 1
* 2
28
When | a | > 1
29
Transformer Rating
Practical transformers are usually rated based on: Voltage Ratio (V1/V2) which gives us the turns-ratio Power Rating, small transformers are given in Watts (real power) and Larger ones (Power Transformers) are given in kVA (apparent power)
30
Example 4.1
Determine the turns-ratio of a 5 kVA 2400V/120V Power Transformer Turns-Ratio = a = V1/V2 = 2400/120 = 20/1 = 20 This means it is a Step-Down transformer
31
Example 4.2
A 480/2400 V (r.m.s) step-up ideal transformer delivers 50 kW to a resistive load. Calculate: (a) the turns ratio, (0.2) (b) the primary current, (104.17A) (c) the secondary current. (20.83A)
32
Nameplate of transformer
33
Equivalent circuit
! a2 1
load
b) Equivalent circuit when primary source is transferred to secondary side and ideal transformer eliminated
Practical Transformer
37
Transformer
38
39
40
In a practical magnetic core having finite permeability, a magnetizing current Im is required to establish a flux in the core. This effect can be represented by a magnetizing inductance Lm. The core loss can be represented by a resistance Rc.
41
Rc :core loss component, Xm : magnetization component, R1 and X1 are resistance and reactance of the primary winding R2 and X2 are resistance and reactance of the secondary winding
42
The impedances of secondary side such as R2, X2 and Z2 can be moved to primary side and also the impedances of primary side can be moved to the secondary side, base on the principle of: The power before transferred = The power after transferred.
43
45
Transformer- Approximate
circuit
equivalent
For convenience, the turns is usually not shown and the equivalent circuit is drawn with all quantities (voltages, currents, and impedances) referred to one side.
46
Example 4.3
A 100kVA transformer has 400 turns on the primary and 80 turns on the secondary. The primary and secondary resistance are 0.3 ohm and 0.01 ohm respectively and the corresponding leakage reactances are 1.1 ohm and 0.035 ohm respectively. The supply voltage is 2200V. Calculate: (a) the equivalent impedance referred to the primary circuit (2.05 ohm) (b) the equivalent impedance referred to the secondary circuit
47
Transformer
48
The equivalent circuit model for the actual transformer can be used to predict the behavior of the transformer. The parameters R1, X1, Rc, Xm, R2, X2 and N1/N2 must be known so that the equivalent circuit model can be used. These parameters can be directly and more easily determined by performing tests: 1. No-load test (or open-circuit test). 2. Short-circuit test.
49
No load/Open circuit test Provides magnetizing reactance (Xm) and core loss resistance (RC) Obtain components are connected in parallel Short circuit test Provides combined leakage reactance and winding resistance Obtain components are connected in series
50
Equivalent circuit for open circuit test, measurement at the primary side.
51
Q ! Voc I oc sin U 0
2 Voc Xm ! Q
52
Secondary (normally the LV winding) is shorted, that means there is no voltage across secondary terminals; but a large current flows in the secondary. Test is done at reduced voltage (about 5% of rated voltage) with full-load current in the secondary. So, the ammeter reads the full-load current; the wattmeter reads the winding losses, and the voltmeter reads the applied primary voltage.
53
Equivalent circuit for short circuit test, measurement at the primary side
54
Re 1 ! R1 a R2
2
X e1 ! X 1 a X 2
2
Psc Re 1 ! 2 I sc X e1 ! Z R
2 e1 2 e1
Z e1
V sc ! I sc
56
Equivalent circuit for a real transformer resulting from the open and short circuit tests.
57
Example 4.4
Obtain the equivalent circuit of a 200/400V, 50Hz 1-phase transformer from the following test data:O/C test : 200V, 0.7A, 70W S/C test : 15V, 10A, 85W - on L.V. side - on H.V. side
Transformer
voltage regulation
Voltage Regulation
Most loads connected to the secondary of a transformer are designed to operate at essentially constant voltage. However, as the current is drawn through the transformer, the load terminal voltage changes because of voltage drop in the internal impedance. To reduce the magnitude of the voltage change, the transformer should be designed for a low value of the internal impedance Zeq The voltage regulation is defined as the change in magnitude of the secondary voltage as the load current changes from the no-load to the loaded condition.
59
Transformer
I2 R1 X1
voltage regulation
Ze2 R2 X2 I2
V12=V20
Rc
Xm
V2
Transformer
I2 R1 X1
voltage regulation
Ze2 R2 X2 I2
V12=V20
Rc
Xm
V2
Applying KVL,
Or
V2 = V20 - I2 (Ze2 )
61
Transformer
I2Xe2
voltage regulation
O
2
A V2
I2Re2 I2
62
Transformer
I2Xe2
voltage regulation
V20 I2Xe2 O
2
A V2 I2Re2 B I2
I2Re2
63
Transformer
I2Xe2
voltage regulation
C V20 I2Xe2
2
O
2
A V2 I2Re2
I2Re2 I2
B
2
Voltage drop = AM = OM
OA
64
= AD + DN + NM
Transformer
I2Xe2
voltage regulation
C V20 I2Xe2
2
O
2
A V2 I2Re2
I2Re2 I2
B
2
AD = I2 Re2 cos
2 2
65
Transformer
I2Xe2
voltage regulation
C V20 I2Xe2
2
O
2
A V2 I2Re2
I2Re2 I2
B
2
Transformer
I2Xe2
voltage regulation
C V20 I2Xe2
2
O
2
A V2 I2Re2
I2Re2 I2
B
2
Therefore NM = (NC)2/2(OC) NC = LC LN = LC
2
BD
2
67
= I2 Xe2 cos
- I2 Re2 sin
Transformer
I2Xe2
voltage regulation
C V20 I2Xe2
2
O
2
A V2 I2Re2
I2Re2 I2
B
2
I 2 X e 2 cos U 2 I 2 Re 2 sin U 2
2 NM =
2V20
I 2 X e 2 cos U 2 I 2 Re 2 sin U 2
2
2V20
68
Transformer
I2Xe2
voltage regulation
C V20 I2Xe2
2
O
2
A V2 I2Re2
I2Re2 I2
B
2
thus, votage regulation = (AM)/V20 per unit In actual practice the term NM is negligible since its value is very small compared with V2. Thus the votage regulation formula can be reduced to:
69
Transformer
I2Xe2
voltage regulation
C V20 I2Xe2
2
O
2
A V2 I2Re2
I2Re2 I2
B
2
Voltage regulation =
Voltage regulation
V 2 NL V 2 L V 2 NL
71
72
Xe2 Re2
Voltage regulation !
I2
e2
cos U 2 s I 2 X e 2 sin U 2 V2 NL
73
Xe1 Re1
Voltage regulation !
I1
e1
cos U 2 s I 1 X e 1 sin U 2 V1
74
Example 4.5 Based on Example 4.3 calculate the voltage regulation and the secondary terminal voltage for full load having a power factor of (i) 0.8 lagging (0.0336pu,14.8V) (ii) 0.8 leading (-0.0154pu,447V)
75
Transformer- Efficiency
Losses in a transformer Copper losses in primary and secondary windings Core losses due to hysteresis and eddy current. It depends on maximum value of flux density, supply frequency and core dimension. It is assumed to be constant for all loads
76
Transformer- Efficiency
As always, efficiency is defined as power output to power input ratio output power ( P out ) L ! input power ( P in )
P out ! P out losses The losses in the transformer are the core loss (Pc) and copper loss (Pcu).
V2 I 2 cosU2 L! 2 V2 I 2 cosU2 Pc I 2
e2
77
Transformer- Efficiency
78
Transformer- Efficiency
P n v P oc sc
79
Transformer- Efficiency
Example 4.6
The following results were obtained on a 50 kVA transformer: open circuit test primary voltage, 3300 V; secondary voltage, 400 V; primary power, 430W.Short circuit test primary voltage, 124V;primary current, 15.3 A; primary power, 525W; secondary current, full load value. Calculate the efficiency at full load and half load for 0.7 power factor. (97.3%, 96.9%)
80
Transformer- Efficiency
For constant values of the terminal voltage V2 and load power factor angle 2 , the maximum efficiency occurs when
dL !0 dI 2
P !I
Transformer- Efficiency
82
Autotransformer
83
Same operation as two windings transformer Physical connection from primary to secondary Sliding connection allows for variable voltage Higher kVA delivery than two windings connection
84
Advantages:
A tap between primary and secondary sides which may be adjustable to provide step-up/down capability Able to transfer larger S apparent power than the two winding transformer Smaller and lighter than an equivalent twowinding transformer Lacks electrical isolation
85
Disadvantage:
86
A Step Up Autotransformer:
and
87
Example 4.7 An autotransformer with a 40% tap is supplied by a 400-V, 60-Hz source and is used for step-down operation. A 5-kVA load operating at unity power factor is connected to the secondary terminals. Find: (a) the secondary voltage, (b) the secondary current, (c) the primary current.
88
Solution
89
The three-phase transformer can be built by: the interconnection of three single-phase transformers using an iron core with three limbs The usual connections for three-phase transformers are: wye / wye seldom used, unbalance and 3th harmonics problem
frequently used step down.(345 kV/69 kV) used medium voltage (15 kV), one of the transformer can be removed (open delta) step up transformer in a generation station
90
Each leg has a primary and a secondary winding. The voltages and currents are in phase in the windings located on the same leg. The primary phase-toline voltage generates the secondary line-toline voltage. These voltages are in phase
91
VAN Vab
VB N Vbc
VC N Vca
IA
ICN
IC
Ib
92
VA N VC N
c b
93
94
Transformer
95
Transformer
96
Transformer
97
Transformer
98
Transformer
Transformer Construction Iron Core The iron core is made of thin laminated silicon steel (2-3 % silicon) Pre-cut insulated sheets are cut or pressed in form and placed on the top of each other . The sheets are overlap each others to avoid (reduce) air gaps. The core is pressed together by insulated yokes.
99
Transformer
The winding is made of copper or aluminum conductor, insulated with paper or synthetic insulating material (kevlar, maylard). The windings are manufactured in several layers, and insulation is placed between windings. The primary and secondary windings are placed on top of each others but insulated by several layers of insulating sheets. The windings are dried in vacuum and impregnated to eliminate moisture.
100
Transformer
Transformer Construction Iron Cores The three phase transformer iron core has three legs.
A phase winding is placed in each leg. The high voltage and low voltage windings are placed on top of each other and insulated by layers or tubes. Larger transformer use layered construction shown in the previous slides.
101
Transformer
Transformer Construction
The dried and treated transformer is placed in a steel tank. The tank is filled, under vacuum, with heated transformer oil. The end of the windings are connected to bushings. The oil is circulated by pumps and forced through the radiators.
102
Transformer
Transformer Construction
The transformer is equipped with cooling radiators which are cooled by forced ventilation. Cooling fans are installed under the radiators. Large bushings connect the windings to the electrical system. The oil is circulated by pumps and forced through the radiators. The oil temperature, pressure are monitored to predict transformer performance.
103
Transformer
Transformer Construction
Dry type transformers are used at medium and low voltage. The winding is vacuumed and dried before the molding. The winding is insulated by epoxy resin The slide shows a three phase, dry type transformer.
104