Professional Documents
Culture Documents
Fire Fighting Systems
Fire Fighting Systems
Qatar Chapter
Presented by:
2. System Design
Figure 2.6
P S M E 2. System Design
Qatar Chapter
- Wet-pipe system.
- Dry-pipe system.
- Pre-action system.
- Deluge system.
3.1 General
- Asphalt saturating
- Flammable liquids spraying
- Flow coating
- Open oil quenching
- Plastics processing
- Solvent cleaning
- Varnish and paint dipping
P S M E 3. Hydraulic Design of Sprinkler Systems
Qatar Chapter
= 0.25 gpm/ft2
P S M E 3. Hydraulic Design of Sprinkler Systems
Qatar Chapter
Formulas:
Pressure: ****Where:
P = 0.433 H Q – Flow rate (gpm)
P – Pressure (psi)
Flow; GPM: k – 5.6 Sprinkler discharge
Q = design density x maximum characteristic, ½ nominal
coverage area of sprinkler orifice
C – Hazen Williams C Factor, friction
Q=k√P loss coefficient, 120
d – inside diameter
Pipe Friction Loss (psi/ft): H – height in feet
P fl = 4.52 Q 1.85 PTl – total pipe length (ft)
C 1.85 d 4.87
2400
0.18
Density/Area Curves
P S M E 3. Hydraulic Design of Sprinkler Systems
Qatar Chapter
4.1 General
Purpose
- Class I :
For use by fire departments and those trained in
handling heavy fire streams, 2 ½-in. (65 mm) hose.
- Class II :
For use primarily by the building occupants until the
arrival of the fire department, 1 ½-in (40 mm) hose.
- Class III :
For use either by fire departments and those trained
in handling heavy hose streams, 2 ½-in (65 mm)
hose, or by building occupants,
1 ½-in (40 mm) hose.
P S M E 4. Standpipe Systems
Qatar Chapter
4.4 Sizing
- system configuration,
- local building code requirements,
- the building hazard, and
- the size of the building.
- Provide 500 gpm (31.5 L/s) at a pressure of 100 psi (689.5 kPa) at
the uppermost outlet for the first riser
and
- 250 gpm (15.75 L/s) for each additional riser with a maximum
required water supply of 1250 gpm (78.75 L/s).
Class II:
5.1 General
5.2 Classifications
Vertical turbine pumps (figure 5.2.2) are used when suction lift
is required.
Figure 5.2.1
P S M E 5. Fire Pumps
Qatar Chapter
Figure 5.2.2
P S M E 5. Fire Pumps
Qatar Chapter
1. The fire pump shall furnish not less than 150 percent rated
capacity at 65 percent of total rated head. The shut off head
shall not be exceeding 140 percent of the rated head. These are
both applicable to vertical turbine and horizontal split case
pump. Older edition of the NFPA 20 requires horizontal split
case pump to have a shut-off rating not exceeding 120 percent
of rated load. (see figure 5.1)
P S M E 5. Fire Pumps
Qatar Chapter
Figure 5.1
P S M E 5. Fire Pumps
Qatar Chapter