Professional Documents
Culture Documents
507 33 Powerpoint-Slides Ch11 DRCS
507 33 Powerpoint-Slides Ch11 DRCS
507 33 Powerpoint-Slides Ch11 DRCS
Concrete Structures
N. Subramanian
For heavy loads or long spans, flat slabs, which have drop panels
around the column (which provide additional resistance to shear), are
used (see Figs 11.1a–c).
© Oxford University Press 2013. All rights reserved.
Fig. 11.1 Flat slabs and flat plates (a) Flat slab with drop and column
head (b) Flat slab with column head (c) Flat slab with drop (d) Flat plate
© Oxford University Press 2013. All rights reserved.
Proportioning of Flat Slabs
Thickness of Slab
The minimum thickness of the slab should be 125 mm and the longer
span should be used in the calculation of the L/d ratio.
3. For exterior panels, the width of the drop panel at a right angle
to the non-continuous edge and measured from the centre line
of columns should be equal to one-half the width of the drop
panel in the interior panels.
© Oxford University Press 2013. All rights reserved.
Drop Panels and Shear Caps
FIG. 11.2 Drop panels and shear caps provide increased shear
Strength (a) Drop panels (b) Shear cap
The concrete in the column head should be placed at the same time
as the slab concrete.
Shear caps are provided to a distance such that the shear capacity on
the critical perimeter outside the shear cap is greater than the applied
shear.
The strips at the middle of the slab, which do not pass through the
columns, are referred to as the middle strips.
Fig. 11.3 Division of flat slabs into column and middle strips
From Fig. 11.3 the column strip AHD will have negative moment at
points A and D and positive moment at point H.
The middle strip EOG will have positive moments at points E, O, and G.
The middle strips are supported by the column strips, which in turn
transfer the load to the columns.
As the column strips are heavily loaded when compared to the middle
strips, they will carry higher bending moments than the middle strips.
© Oxford University Press 2013. All rights reserved.
Fig. 11.4 Variation of bending moment in flat slabs (a) Critical moment sections (b) Moment variation
along the span (c) Moment variation across the width of critical sections (d) Trajectories of principal
moments in flat slabs
© Oxford University Press 2013. All rights reserved.
Behaviour of Flat Slabs
At working loads the slabs have small deflections and stresses.
Upon loading, cracks appear first on the top surface of the slab near
the column, where maximum bending moment occurs, soon followed by
cracking in the mid-span at the bottom.
Further loading causes cracking and yield lines start to form at the end
regions.
Fig. 11.5 Typical crack pattern in flat plates (a) At top (b) At bottom
Fig. 11.6 Typical crack pattern in flat slabs with edge beams (a) At bottom (b) At top
In both the DDM and EFM, a typical panel is divided, for the purpose
of design, into column strips and middle strips.
Fig. 11.7 Division of interior and exterior slab panels into column and middle strips (a) Column
strip for L2 ≤ L1 (b) Column strip for L2a and L2b > L1
6. If beams are used on the column lines, the relative stiffness of the
beams in the two perpendicular directions given by the ratio
1L22/2L12 must be between 0.2 and 5.0, where = EcbIb/EcsIs.
For slabs with beams between supports, the slab portion of the
column strips should be proportioned to resist the portion of column
strip moments not resisted by the beams.
In addition to the load that is transferred by shear from the slab to the
column (along an area around the column), moments and torsion also
have to be transferred to the exterior columns.
Such a transfer may also be there in interior columns, when there are
unbalanced gravity loads or other lateral loads such as wind and
earthquake.
Such moment transfers will be very critical at the edge and exterior
columns.
© Oxford University Press 2013. All rights reserved.
Transfer of Moments to Columns
These moment transfers will cause shear stresses of their own in the
slabs.
The shear stresses due to moment and shear transfers in the interior
columns and edge column–slab joints are shown in Figs 11.15 and 11.16,
respectively.
If there is an unbalanced loading of two adjoining spans, the result will
be an additional moment at the connection of the walls and columns to
slabs. © Oxford University Press 2013. All rights reserved.
Transfer of Moments to Columns
Fig. 11.15 Shear stresses due to transfer of shear and moment at interior columns
(a)Transfer of unbalanced moments to column (b) Total shear stresses (c) Shear stress
(b)due to Vu (d) Shear due to unbalanced moment
© Oxford University Press 2013. All rights reserved.
Transfer of Moments to Edge
Columns
Fig. 11.16 Shear stresses due to transfer of shear and moment at edge
columns (a) Transfer of moment at edge column (b) Total shear stresses
(c) Shear stresses due to Vu (d) Shear stresses due to Mu
© Oxford University Press 2013. All rights reserved.
Transfer Width At Slab-Columns
Connection
Fig. 11.17 Transfer width at slab-column connections (a) Interior column (b) Exterior column—moment
transferred parallel to the edge (c) Exterior column—moment transferred perpendicular to the edge
In almost all tests of such structures, failures have been due to shear
or perhaps shear and torsion. These conditions are particularly serious
around the exterior columns.
The critical section extends in a plane across the entire width of the
slab and is assumed to be located at a distance d (effective slab depth)
from the face of the column or shear capital, as shown in Fig. 11.18(a).
The area from which the load is transferred to the critical section is
termed the tributary area.
Fig. 11.18 Shear in flat plates (a) One-way or beam action (b) Two-way action (punching shear)
In the case of corner columns, the critical section has to be taken
along a straight line located at a distance d from the corner column, as
shown in Fig. 11.19(b).
Fig. 11.19 Critical section for one-way shear (a) Flat slabs (b) Corner column
Thus, a flat slab or flat plate may possess sufficient ductility if it fails
in flexure but little ductility when punching shear is the failure mode.
© Oxford University Press 2013. All rights reserved.
Two-way or Punching Shear
For the condition of two-way action, the critical section is assumed to
be located at a distance d/2 from the perimeter of the column or drop
panel, with potential diagonal tension cracks occurring along a
truncated cone or pyramid passing through the critical section (see Fig.
11.20).
1. Concrete strength
2. Ratio of the column size to slab effective depth
3. Ratio of shear strength to flexural strength
4. Shape of the column
5. Amount of tension and compression reinforcement
6. Lateral constraints
Other codes, such as Euro code, consider the critical section at 1.5d or
even 2d from the face of the column and rounded shear perimeters
even for rectangular columns, as shown in Fig. 11.21.
See Table 11.7,11.8, and 11.9 for the definition of the terms
© Oxford University Press 2013. All rights reserved.
Combined Shear and Moment Transfer
at Columns
The punching shear failure surface at columns is accompanied by
bending cracks in the same region in circular and radial directions.
A new failure criterion for punching shear based on the critical shear
crack theory has been presented by Prof. Muttoni and associates which
takes into account the size effect (see Ruiz and Muttoni, 2009).
© Oxford University Press 2013. All rights reserved.
Strategies to Avoid Punching Shear Failure
4. Shear bands
Fig. 11.26 Shear stirrups as suggested (a) Closed stirrups (b) Castellated stirrups
© Oxford University Press 2013. All rights reserved.
Disadvantages of Shear Stirrups
1. Congestion of reinforcement, unless they are planned carefully
considering the sequence of layout
Fig. 11.28 Examples of the use of headed shear stud reinforcement (a) Single-headed
stud rail fixed at the bottom of the slab
The steel strip, also called the rail, acts as an anchor and spacer,
holding the studs in a vertical position at the appropriate spacing in the
formwork until the concrete is cast.
(b) The second type is fixed from the top after all the main
reinforcement has been positioned as shown in Fig. 11.28b.
© Oxford University Press 2013. All rights reserved.
Advantages of Headed Shear Studs
1. Relatively easy installation and cost effectiveness
The I-sections are welded fully to form identical arms of equal length
in orthogonal directions.
The arms should have adequate length beyond which (outer critical
section) the shear stresses in concrete are within the permissible limits.
The strip is punched with holes, because this has been demonstrated
experimentally to increase its anchoring characteristics over short
lengths.
Due to its small thickness, the reinforcement can be placed from the
top, after all flexural reinforcement is in place, with minimal loss of
cover.
Fig. 11.30 Shear band reinforcement (a) Placement in slab (b) Flat steel strip
punched with holes (c) Schematic way of representing shear band reinforcement
The UFO increases the punching capacity beyond the level that can be
reached by the punching shear reinforcement. The bottom flange and
the lower part of the product function like a support for the slab in the
outer area.
© Oxford University Press 2013. All rights reserved. shear
Lattice Shear Reinforcement
2. When drop panels are used, the thickness of the drop panel for the
determination of the area of reinforcement should be the lesser of
the thickness of the drop and that of the slab, plus one-fourth the
distance from the edge of the drop panel to the face of the column
or column capital.
At least two of the column strip bottom bars in each direction should
pass within the region bounded by the longitudinal reinforcement of the
column and shall be anchored at the exterior supports.
3. In the area common to one column strip and one middle strip, the
maximum permitted opening size is limited in such a way that a
maximum of one-quarter of the slab reinforcement in either strip
may be interrupted. The equivalent of reinforcement interrupted
should be added on all sides of the openings.
These provisions are explained in Fig. 11.35 for slabs with L2 > L1.
© Oxford University Press 2013. All rights reserved.
Fig. 11.35 Permitted openings in flat slabs
© Oxford University Press 2013. All rights reserved.
Effect of Openings on Shear Strength of
Slabs
The effect of an opening on the concrete shear strength has to be
considered in flat slabs when any opening is located anywhere within
the column strip or within 10 times the slab thickness from the
concentrated load or reaction area.
Fig. 11.36 Effect of opening on shear strength of slabs (a) Opening on the critical
perimeter (b) Opening away from the critical perimeter (c) Large opening near
critical perimeter (d) Column near the edge of building
Fig. 11.37 Effect of opening in slab (a) With drop panel (b) With shear
reinforcement
Without this, separation can occur and the topping may buckle when
subjected to diagonal compression resulting from diaphragm shear and
be unable to transmit the floor inertial forces to the shear walls or
columns.
© Oxford University Press 2013. All rights reserved.
Diaphragm Action
There should be an adequate load path for the forces to be
transferred between a diaphragm and any lateral force resisting
elements, such as walls or frames.
The strut-and- tie method may be used for the design of these details.
The effective width accounts for the behaviour of the slab that is not
fully effective across its transverse width.
Fig. 11.39 Effective slab width model (a) Effective width for strength
(b) Effective width for initial stiffness
Fig. 11.41 Design steps for resisting punching shear in earthquake zones
The bending moments per metre width obtained for solid slabs (in
case of waffle slab supported by beams—see Fig. 11.43c) should be
multiplied by the spacing of the ribs to obtain the bending moments per
rib.
In the case of waffle slabs without beams, as shown in Fig. 11.43(a),
bending moments in column and middle strips can be determined using
the DDM.
At least 50 per cent of the total tension reinforcement at the bottom
should be extended to the support and anchored properly.
They are generally analysed by using grid analysis programs, with the
slab load acting on them as triangular or trapezoidal loads.