Professional Documents
Culture Documents
Electrical Substation Interlock System-2
Electrical Substation Interlock System-2
Substation
Interlock
System
Done by:
Eng. Yasir Zyadah
01 – JAN – 2023
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Agenda
01 Introduction
03 Interlocks Types
04 Protection and
Inter-tripping Philosophy
05 Current Situation
06 Mitigation
2 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Introduction
01
Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Introduction
Definitions
• Interlock: is a condition or set of conditions that must hold true for a switch operation to take place. The
switch operation (Opening or Closing) takes place only when the complete set of conditions defined in its
interlock holds true at the same time. Even if one of the conditions of interlock stands false, the switch
operation cannot take place.
• Circuit Breaker (CB): is a high-speed switch used for on load switching in substations.
• Earthing Switch (ES): is an offload switch used to connect and offload equipment to earth.
Cable Feeder
Circuit
Breaker Load
Earth Switch
Figure 1. A simple illustration of a disconnector and earthing switch used in a power system.
4 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Introduction
Propose
Interlocking is installed to protect both the equipment and the operator from dangerous situations caused by
incorrect equipment operation. It can be categorized as operational interlocking and safety, or maintenance,
interlocking. However interlocking logic is not always easy to understand and sometimes hard to design.
Interlocking in switchgear provides safety for personnel and equipment during following procedures:
1. Switching of high, medium and low voltage
2. Switching incomers and feeders
3. Switching earthing systems
4. Maintaining substation equipment
5 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Standard and
Principle 02
Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
• IEC-62271
Medium-voltage (MV) switchgear and control gear
• 32-SDMS-08
(SEC Distribution Material Specification)
7 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Low-voltage
Compartment Busbar Compartment
Circuit Breaker
Compartment
Automatic Shutters
Earth Switch Current Transformers
Earth Bar
a) Isolated / test position b) Service position
Figure 2. Single line diagram of a typical circuit. Figure 3. IEC (MV) Switchgear design.
8 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Interlocks Types
03
9 ---- Electrical
Electrical Substation
Substation
Interlock
Interlock
SystemSystem
---- 01
----
JAN012023
JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Interlocks Types
There are two types of interlock:
1- Electrical 2- Mechanical
Interlock Interlock
10 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021 SEC 13.8 KV SWG
Interlocks Types CB
ES
CB
Interlocks Types
2- Mechanical Interlocks (Safety (maintenance) Interlocking)
This is concerned with the safe operation of switchgear, the Trfr Feeder Trfr Incomer
provision of safe access to plant for maintenance purposes CB Trapped Key lock
and the application of fixed earthing devices. It is usually Earth Switch
achieved by mechanical-interlocking systems utilizing keys Trapped Key Lock
12 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Interlocks Types
2- Mechanical Interlocks (Safety (maintenance) Interlocking)
Figure 7. Padlock on Earth Figure 8. Control Plug in Figure 9. Circuit Breaker Figure 10. Padlock on the
Switch ON. Place. Compartment. Shutter.
13 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Protection and
Inter-tripping
Philosophy 04
Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
15 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Current Situation
05
16 ---- Electrical
Electrical Substation
Substation
Interlock
Interlock
SystemSystem
---- 01----
JAN01
2023
JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Current Situation
SEC 115/13.8 KV
Primary Substation
27-Outgoing Feeders
Modular Substation
All zones (178)
17 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
SEC 13.8 KV Substation
13.8 KV
Current Situation CB
ES
Underground
Cable
MRS 13.8 KV
ES
CB
13.8 KV
CB CB CB
ES ES ES
DS DS
CB
Transformer
13.8/ 0.4 KV
CB
400 V
MCCB MCCB MCCB
18 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
Figure 11. Single line diagram of Modular Substation 13.8 KV.
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Mitigation
06
19 ---- Electrical
Electrical Substation
Substation
Interlock
Interlock
SystemSystem
---- 01----
JAN01
2023
JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Mitigation
Grounding switch of an incoming feeder shall also be interlocked with MV breaker (remote substation) such
that closing operation of grounding switch in low-voltage (LV) (IMI incomer) side shall not be possible
unless MV breaker is open. MV breaker closing operation shall not be possible unless grounding switch in
LV side is open. LV circuit breaker closing shall not be possible unless MV circuit breaker is closed.
In order to achieve this philosophy, two solutions are recommended.
20 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Mitigation
A. In short term (Switching procedures)
1. All planned or unplanned switching schedules must be coordinating with the SEC dispatcher through
an agreed point of contact.
2. Authorized persons or seniors authorized person carrying out switching instructions shall have a copy
of switching procedures.
3. If any doubt could arrive, the operator shall compere understanding of the specific instruction with
the authorized person, senior authorized person prior to switching.
4. Switching procedures shall be record, including a number for the induvial operation, the
identification of the equipment involved, the effect of the operations, this shall be achieved by the
use of the switching schedules.
5. Partial interlocking of earthing switches at circuit-entries to the substation is acceptable where it is
not reasonably practicable to extend the interlocking to the remote end disconnectors. Any partially
interlocked earthing switch shall be provided with a warning label, to the approval of NGC, stating
‘WARNING, THIS EARTH SWITCH IS NOT FULLY INTERLOCKED’.
6. Where an interlocking scheme is being supplied for an extension to an existing substation at the same
operating voltage then, unless otherwise agreed by NGC, the interlocking type and philosophy shall
match that existing.
21 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
INTERNATIONAL MARITIME INDUSTRIES ---- © 2021
Mitigation
B. In long term (IEC 61850)
Into a substation SCADA system. IEC 61850
enables data from all IEDs to modify or added
functions. Figure 12 and 13 shows the architecture
connections inside the substations using IEC 61850
Figure 12. Status indication-base interlocking via the GOOSE
with the protection IEDs. GOOSE is a very flexible messaging.
high-priority reliable mechanism for fast
transmission of substation events such as trip
commands, interlocking and critical status
indications. GOOSE messages are used to replace
the hardwired control signal.
23 ---- Electrical Substation Interlock System ---- 01 JAN 2023 PRIVATE & CONFIDENTIAL
Thank You!
IMI-KSA.COM