Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 9

PURCHASE OF BATTERY BANK SYSTEM

PURCHASE OF BATTERY BANK SYSTEM

Index 01 DESCRIPTION AND IMPORTANCE OF THE BATTERY BANKS

02 DESCRIPTION OF THE ACQUISITION AND SERVICE

03 TECHNICAL COMPARATIVE

04 COMPARATIVE TABLE

05 CONCLUTIONS
DESCRIPTION AND IMPORTANCE OF THE BATTERY BANKS

The battery bank system in the powerhouse serves as backup for the
electrical supply of the critical loads for its operation.

As part of the preventive maintenance, it was detected that batteries


must be replaced, and after the discharge tests that was carried out this
year, additional batteries must be available in case faults occur during
the tests.

2017 18 2

Image 2.- Discharge Test Results from


BTU-02 - PowerHouse

Image 1.- Battery Bank BTU-01


02 DESCRIPTION OF THE ACQUISITION AND SERVICE

What is being requested to acquire and contract?

ACQUISITION SERVICE
BANCO DE BATERIAS 125 Vcc 250 A/H 10 H CON CARGADOR DE
SSEE CHAGLLA 1
BATERIAS MODELO 125-75UA01M
CASA DE MÁQUINAS (DATOS BATERÍAS ACTUALES)
Tensión Máxima admisible en el sistema 137.5V • Delivery
Tensión Mínima admisible en el sistema 105V • Rack
Autonomía Necesaria 750Ah@10h • Capacity Test
Cantidad de Celdas Actuales 60 • Dissasembly and Mounting
Tipo de Batería Actual 2017
• Connection and electrical Test
18 Plomo ácido ventilada 2
Modelo de Batería Actual OPzS FIAMM LM800
• Prevencionist
SSEE CHAGLLA (DATOS BATERÍAS ACTUALES)
Tensión Máxima admisible en el sistema 137.5V
Tensión Mínima admisible en el sistema 105V
Autonomía Necesaria 250Ah@10h
Cantidad de Celdas Actuales 60
Tipo de Batería Actual Plomo ácido ventilada
Modelo de Batería Actual OPzS FIAMM LM250

Image 3.- Battery Banks to Adquire Image 2.- Service of Installation Battery Banks in Power
House and Chaglla SSEE
03 TECHNICAL COMPARATIVE
IMG VOLTA
Model 7 OPzV 700 7 OPzV 700
Capacity 858Ah@10h@1.8V@20°C 858Ah@10h@1.8V@20°C
Float Voltage 2.25 2.25
Nominal Voltage 2V 2V
Brand BAE BAE
Country GERMANY GERMANY
Electrolyte Gel structure Gel structure
Battery Temperature 10°C / 30°C 10°C / 30°C
Standard DIN 40742 DIN 40742
Test Standard IEC 60896-21/-22 IEC 60896-21/-22
Charging Time up to 92% 6h
Check battery voltage, pilot cell voltages,
6h
Check battery voltage, pilot cell voltages,
IMG and VOLTA
Maintenance 6month temepratures
Record battery and cell voltages and
temepratures
Record battery and cell voltages and
offers the same
Maintenance 12 month temperatures temperatures Brand and Model
QUALITY STANDARD 9001 Yes Yes
QUALITY STANDARD 45001 Yes Yes
QUALITY STANDARD 14001 Yes Yes
QUALITY STANDARD 50001 Yes Yes
Service Life 12 years 12 years

Riggid Cupper Riggid Cupper


Connectors
Shipping Delivery 5.5 months 5 months
Warranty 1 year 2 years
700Ah Batterys Price $ 30,600.00 $ 39,500.00
250Ah Batterys Price $ 13,600.00 $ 18,900.00
Rack Earthquake-resistant Yes Yes
Shapes According ASTM Yes Yes
700Ah Rack Price Included in Batterys Price $ 4,620.00
250Ah Rack Price Included in Batterys Price $ 3,300.00
Sub Total Batterys Bank $ 44,200.00 $ 66,320.00
Capacity Test Yes Yes
Dissasembly and Mounting Yes Yes
Conection and electrical test Yes Yes
Prevencionist N.E. Yes
Service 700AH Price $ 9,400.00 $ 3,750.00
Service 250Ah Price Included in Service 1 $ 2,750.00
Sub Total Service $ 9,400.00 $ 6,500.00
Total Price $ 53,600.00 $ 72,820.00
04 COMPARATIVE TABLE

Pending from
Purchases
Department
05 CONCLUTIONS

• It is recommended to purchase the two battery banks units requested and contract the
service of installation and electrical test.

• It is recommended to choose the company IMG for offering the same brand and model
that accomplish our requirements for the best price.

You might also like