BASIC CONTROL
50-100 HP SIERRA
BASIC CONTROL
SERVICE DEVELOPMENT PT FAJAR MAS MURNI
WHEN 1SV IS DE-ENERGIZED THE UNIT IS UNLOADED AND 1SV VENTS OIL FROM THE
HYDRAULIC CONTROL CYLINDER, WHICH IS SPRING RETURN, AND ALLOWS THE CYLINDER TO
CLOSE THE BUTTERFLY VALVE AND OPENS THE BLOWDOWN VALVE.
THE BLOWDOWN VALVE OPENS FULLY PRIOR TO COMPLETELY CLOSING THE INLET VALVE,
DUE TO THE MECHANICAL LINKAGE BETWEEN THE TWO COMPONENTS.
WHEN SYSTEM PRESSURE DROPS BELOW THE ON-LINE SET POINT 1SV IS ENERGIZED WHICH
ALLOWS OIL UNDER PRESSURE TO BE FEED TO THE CONTROL CYLINDER. THIS CAUSES THE
BUTTERFLY VALVE TO OPEN AND THE BLOWDOWN VALVE TO CLOSE.
THE BUTTERFLY VALVE BEGINS TO OPEN PRIOR TO CLOSING THE BLOWDOWN VALVE DUE TO
THE MECHANICAL LINKAGE BETWEEN THE TWO COMPONENTS.
SE STYLE CONTROLLER
– Not same part number as SE
THERMISTORS AND RTD
– 1st & 2nd stage temps. are RTDs
– All others are thermistors
Fewer pressure readouts
– Only Package Discharge Pressure
Add oil pressure switch
Auto loader
Adjustable Condensate Valves
STANDARD DISPLAY
SERVICE DEVELOPMENT PT FAJAR MAS MURNI
OFF-LINE PRESSURE
ON-LINE PRESSURE
DISPLAY TIME
STAR DELTA TIME
OPTION SELECTION
SERVICE DEVELOPMENT PT FAJAR MAS MURNI
SENSOR FAILURE
– 7ATT, 3ATT
HIGH PACKAGE DISCHARGE TEMP
– > 140°F
ALARMS
SERVICE DEVELOPMENT PT FAJAR MAS MURNI
CALIBRATION
– ALL PRESSURE RELIEVED FROM UNIT
– UNIT STOPPED PRESS UP & DOWN
ARROWS AT SAME TIME
CUSTOMER SET POINT ROUTINE
– UNIT STOPPED PRESS SET
» USE UP & DOWN ARROWS
» PRESS SET TO LOCK IN CHANGES
DISPLAY SOFTWARE VERSION
– UNIT STOPPED PRESS UNLOADED STOP