Professional Documents
Culture Documents
6 - BNE32603 POWER QUALITY - Chapter 5
6 - BNE32603 POWER QUALITY - Chapter 5
QUALITY
“ W I T H W I S D O M W E E X P L O R E ”
Common disturbances on equipment
Symptoms Causes
• Power outages Voltage dips & swells
• Tripping circuit breakers and ASDs Transients
Noise interference
• High utility bills
Harmonic distortion
• Flickering lights Under / over voltage or current
• Equipment running noisy and hot
• Premature equipment failure
• Poor performance & unexpected shutdowns
• Lost data in electronics
• Voltage unbalance
Typical facility
problems:
• Loose connections
• Arcing connections
• Overloaded circuits
and transformers
• Unbalanced loads
• Harmonics caused by
modern electronics
• Illegal neutral to
ground bonds
• Ground loops
• Undersized or
shared neutrals
Examples:
• computer networking
• telecommunication facilities
• Many power quality variations that occur within customer facilities are
related to wiring and grounding problems.
4. Ungrounded equipment
Isolated grounds are sometimes used due to the perceived notion of obtaining
a “clean” ground and for sensitive equipment. The proper procedure for using
an isolated ground must be followed. Procedures that involve having an illegal
insulating bushing in the power source conduit and replacing the prescribed
equipment grounding conductor with one to an “isolated dedicated computer
ground” are dangerous, violate code and are unlikely to solve noise problems.
5. Additional ground rods
Ground rods should be part of a facility grounding system and connected where
all the building grounding electrodes (building steel, metal water pipe, etc.) are
bonded together. Multiple ground rods can be bused together at the service
entrance to reduce the overall ground resistance. One very important power
quality problem with additional ground rods is that they create additional paths
for lightning stroke currents to flow. This creates a possible transient voltage
problem for equipment and a possible overload problem for the conductors.
4. Isolated ground
The noise performance of the supply to sensitive loads can sometimes
be improved by providing an isolated ground to the load. This is done
using isolated ground receptacles, which are orange in color. If an isolated
ground receptacle is being used downline from the panel board,
the isolated ground conductor is not connected to the conduit or enclosure
in the panel board, but only to the ground conductor of the supply
feeder. The conduit is the safety ground in this case and is connected to the
enclosure. A separate conductor can also be used for the safety ground in
addition to the conduit.
Simple meters.
• It may sometimes be necessary to make a quick check of harmonic
levels at a problem location. A simple, portable meter for this purpose
is ideal. There are now several hand-held instruments of this type on
the market. Each instrument has advantages and disadvantages in its
operation and design. These devices generally use microprocessor-
based circuitry to perform the necessary calculations to determine
individual harmonics up to the 50th harmonic, as well as the rms, the
THD, and the telephone influence factor (TIF). Some of these devices
can calculate harmonic powers (magnitudes and angles) and can
upload stored waveforms and calculated data to a personal computer.
Situation:
Analysis:
• After the pump installation, the utility called. Plant Power factor had dropped
below 95 %.
• Plant electricians used the Power Clamp Meter and read 93 % power factor!
SO:
Electricians performed a 1-week energy study
They confirmed that the PF drop coincided with the operation of the new pumps