Professional Documents
Culture Documents
Untitled
Untitled
Untitled
The term zone implies the provision of, or the need for, separate
thermostatic control, whereas the term room implies a partitioned area
that may or may not require separate control.
The basic all-air system concept is to supply air to the room at
conditions such that the sensible and latent heat gains in the space,
when absorbed by supply air flowing through the space, bring the air
to the desired room conditions. Because heat gains in the space vary
with time, a mechanism to vary the energy removed from the space
by the supply air is necessary. There are two such basic mecha-
nisms: (1) vary the amount of supply air delivered to the space by
varying the flow rate or supplying air intermittently; or (2) vary the
temperature of air delivered to the space, either by modulating the
temperature or conditioning the air intermittently.
PARA CONCLUSIONES
Línea divisoria
alrededor de
los 2400 FPM
Retorno
Recomendable
REVISADO
Transformaciones
Unir dos conductos de diferente forma o IMPORTANTE para ubicar ventilador
sección recta. helicoidal dentro del ducto
REVISADO
Cuando se deba modificar la forma del ducto o Se recomienda que las dimensiones de los ductos se
su sección cuadrada, se recomienda una reduzcan de 2 en 2 pulgadas preferentemente en una
pendiente de 15% para las caras laterales de la sola dimensión o cara del ducto (ancho o altura).
transformación y en cualquier caso no deberá
sobrepasarse un máximo de 25%. Estas
pendientes deben usarse también cuando sea
necesario reducir el tamaño de los ductos para
salvar un obstáculo, en cuyo caso es
recomendable también no reducir su sección
más de un 20%.
RUTA CRITICA
Inlet spin may arise from many different approach conditions, and
sometimes the cause is not obvious. Figure 14 shows some common
duct connections that cause inlet spin. Inlet spin can be avoided by
providing an adequate length of duct between the elbow and the fan
inlet, as shown by Figure 15. Two L/Do duct lengths upstream of the
fan inlet reduces swirl and pressure loss (loss coefficient) by approximately
45% (Table 7).
Design duct connections at the fan inlet for uniform and straight
airflow. Both turbulence and flow separation at the fan blades
can
significantly increase fan-generated noise.
REVISADO
TIPOS DE PLENUM
return air grilles are installed on the ceiling without connecting One of the drawbacks of using the ceiling
to any ducts. Some buildings have multiple ceiling openings plenum as the return air plenum is noise
(usually near the windows) instead of return air grilles to allow
air to return back to the respective air conditioners.
Another problem with the ceiling plenum is
Using the space above the ceiling as the plenum for air the infiltration of hot air
conditioners is a clever way to save costs for the air
conditioning system
Usually, air conditioners which are designed to use ceiling
plenum for return air will not need to have a separate return air
plenum box on the air conditioner itself.
The outside air is introduced into the ceiling plenum to mix
with the return air before flowing back to the respective air
conditioners. A damper is still required to limit the amount of
outside air coming into the ceiling plenum.
Linear slot diffusers include 4-slot linear diffusers, 3-slot linear However, when noise is not a concern, linear slot
diffusers, 2-slot linear diffusers and other numbers of slots diffusers are good for high ceiling rooms. They are
depending on the manufacturer or upon request. The more capable of throwing air from the ceiling to the
common ones are 3-slot and 2-slot ground at a height of around 9-12 meters most of the
time. If you allow more air to pass, you can even
Linear slot diffusers always have two lengths; 600mm and throw up to 30 meters vertically.
1200mm. Other lengths such as 1500mm are possible
depending on the manufacturer. As for the width, it's depending
on the number of slots.
The number of slots in linear diffusers corresponds to the
amount of airflow. The higher the airflow requirement, the more
slots it needs to have.
Linear slot diffusers required a rectangular-shaped plenum box
with an opposed-blade damper for airflow control. The plenum
box has a round duct collar for a flexible duct connection.
REVISADO
Linear Slot Diffuser Linear slot diffusers incorporate adjustable
pattern controllers in a multi‑slot configuration. Slot sizes are
available in ½ in. [13 mm], ¾ in. [19 mm] or 1 in. [25 mm]
widths with a choice of one to ten slots. Adjustable pattern
controllers allow horizontal left, horizontal right or vertical
discharge for maximum flexibility. Typically used in ceiling
installations, the linear slot diffuser is architecturally appealing,
particularly when supplied in continuous lengths.
REVISADO
Ejemplo Características
REVISADO
Double Deflection Diffuser (Large Airflow)
b) linear bar grille Each linear bar grille has a maximum length
Linear bar grilles are more commonly used in lobbies and halls because of around 2500-2700mm. If you need a longer
they are more aesthetically appealing than louver grilles. one, the supplier will mostly provide you
multiple linear bar grilles for you to join them
They do not have any sort of airflow direction controls together
Usually, linear bar grilles are around 4-5 slots. the downside of using linear bar grilles is that you'll
Linear bar grilles are almost always used as air conditioning need a return air plenum box if you want to have air
return air grilles. volume controls.
REVISADO
CÁLCULO DE RETORNOS
Face velocity is the amount of air volume passing through a
grille. Typically, 500 fpm (2.54 m/s) is optimal and balanced
between air volume and noise.
Free area is the amount of space on a grille available for the air
to pass through. It's depending on the type of grille and the
manufacturer of the grille.
The return air inlet has very little effect on room air diffusion,
regardless of inlet type or location. However, return air inlets
should be located a sufficient distance from the supply outlet so
that short-circuiting of supply air does not occur. It may also be
desirable to locate the returns in the stagnant zone to remove
unwanted warm or cool air. For cooling, a high sidewall or ceiling
return will remove warm air from the space
REVISADO
Drop
The drop of cool total air, as shown in Figure 1, is the result of
vertical spread of the air stream due to entrainment of room
air, and the buoyancy effect due to the density differences
between the total air package and the surrounding primary
room air. The term density is very important as drop is primarily
dependent upon the mass flow of the total air. Drop can be
minimized by spreading air uniformly over the ceiling surface,
thus reducing the mass flow per unit surface area.
Surface Effect
Drop can also be effectively reduced by use of the surrounding
ceiling surface. When supply air velocity is sufficiently high, a
negative or low pressure area is created between the moving
air mass and the ceiling at or near the supply air outlet. This
low pressure area causes the moving air mass to cling to and
flow close to the ceiling surface. This principle is known as the
Coanda effect.
Drop. Vertical distance that the lower edge of a Room Air Finally, we come to the medium through which all
horizontally metabolic heat transfer occurs and therefore is the most critical
projected airstream descends between the outlet factor in controlling human comfort ‑ the room air.
and the end of its It is this constant mixing that provides the mechanisms for heat
throw. transfer between the supply and room air
Whenever cool supply air is introduced into a warmer
space its natural tendency will be downward Noise Level
movement. The vertical distance which the air jet Typically, the noise level of an air outlet is rated with a Noise
extends below the ceiling is called the drop (Figure 5). Criteria (NC) sound pressure value based on an industry
Similar to the throw, we discuss the drop referenced to standard 10 dB default for room absorption. This NC value
a specific terminal velocity. For simplicity we use the assumes an average room and approximate distance of 5 ft [1.5
same three terminal velocities as for throw: 150 [0.75], m] from a single source.
100 [0.50] and 50 fpm [0.25 m/s]. If the supply air An air outlet's noise level (NC rating) is directly proportional to
projects into the occupied space uncomfortable drafts the air volume supplied through the outlet, with the sound
will occur. Drop can be minimized by utilizing the increasing as more air is supplied. Larger size outlets generally
surface effect of the ceilings. Outlets located in or near are quieter at the same air flow than smaller sizes of the same
the ceiling will exhibit less drop than outlets located on model due to higher free area and/or lower inlet velocity.
exposed ductwork. Outlets should be selected so that the resultant NC level does
not exceed the ASHRAE recommended values for the particular
space being considered.
Throw. The distance from the centerline of an outlet It should be noted that most catalog throw data
perpendic- is presented for isothermal conditions (i.e.,
ular to a point in the mixed airstream where the velocity has supply air temperature equals room
been temperature). During cooling the denser supply
reduced to a specified terminal velocity (e.g., 50, 100, 150, or air will shorten the horizontal throw to
200 fpm), defined by ASHRAE Standard 70. approximately 75% of tabulated values (multiply
by 0.75), assuming a temperature differential of
the design supply approximately 15 °F [7.5 °C].
air velocity should be high enough to maintain the jet traveling
in the desired direction, to ensure adequate mixing before it The ceiling or Coanda effect allows the supply air
reaches the occupied zone. Excessively high outlet air velocity jet to be in contact with the ceiling longer,
produces high air velocities in the occupied zone and may reducing induction of room air and consequently
result in termal discomfort. resulting in a longer throw than if the outlet was
mounted in free space.
In addition to physical boundaries created by walls or
partitions, boundaries can be created by the collision of two air
patterns (Figure 24). Where two patterns will meet, the outlets
should be selected so that the throw is equal to one half the
distance between the outlets.
Design Constraints
Space design constraints affect room air distribution system
choices and how air inlets and outlets are used. Space
constraints
may include the following:
• Dimensions
• Heat gain and loss characteristics
• Use
• Acoustical requirements
• Available locations for air inlets and outlets