Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 2

INTERLOCKS TEST

DAP 107 LINE D


TRIP INITIATION
Trip N° Description Interlock Description Trip Etat

I-100 PRENEUTRALIZER 107DAM01 LIQUID LEVEL HIGH HIGH Pass
A-100 CLOSE WEAK PHOSPHORIC ACID VALV E FV-001
I-179 DUST & FUME EXHAUST FAN 107DAC02 MOTOR STOPPED Pass
I-100 PRENEUTRALIZER 107DAM01 LIQUID LEVEL HIGH HIGH Pass
A-101 CLOSE SCRUBBER LIQUOR VALVE FV-002
I-179 DUST & FUME EXHAUST FAN 107DAC02 MOTOR STOPPED Pass
I-100 PRENEUTRALIZER 107DAM01 LIQUID LEVEL HIGH HIGH Pass
A-102 CLOSE STRONG PHOSPHORIC ACID VALVE FV-003
I-179 DUST & FUME EXHAUST FAN 107DAC02 MOTOR STOPPED Pass
I-100 PRENEUTRALIZER 107DAM01 LIQUID LEVEL HIGH HIGH Pass
A-103 CLOSE 98% SULFURIC ACID VALVE FV-004 I-101 PRENEUTRALIZER 107DAM01 LIQUID LEVEL LOW LOW Pass
I-179 DUST & FUME EXHAUST FAN 107DAC02 MOTOR STOPPED Pass
I-100 PRENEUTRALIZER 107DAM01 LIQUID LEVEL HIGH HIGH Pass
A-105 CLOSE AMMONIA GAS VALVE FV-008 I-101 PRENEUTRALIZER 107DAM01 LIQUID LEVEL LOW LOW Pass
I-179 DUST & FUME EXHAUST FAN 107DAC02 MOTOR STOPPED Pass
A-106 STOP PRENEUTRALIZER AGITATOR 107DAA01 I-101 PRENEUTRALIZER 107DAM01 LIQUID LEVEL LOW LOW Pass
I-101 PRENEUTRALIZER 107DAM01 LIQUID LEVEL LOW LOW Pass
I-104 GRANULATOR 107DAM03 TRIPS Pass
I-162 RECYCLE SOLIDS MASS FLOW LOW LOW Pass
A-107 STOP SLURRY PUMP 107DAP01
I-179 DUST & FUME EXHAUST FAN 107DAC02 MOTOR STOPPED Pass
I-182 DRYER EXHAUST FAN 107DAC01 MOTOR STOPPED Pass
I-383 Low flow of seal water Pass
I-208 DRYER 107DAF02 RUN Pass
A-209 RUN/ STOP DRYER OIL DRIP SUPPLY SYSTEM I-309 DRYER107DAF02 ZERO SPEED (RUNNING) Pass
I-310 DRYER107DAF02 ZERO SPEED (STOPPED) Pass
I-208 DRYER 107DAF02 RUN Pass
A-212 RUN/ STOP DRYER OIL DRIP SUPPLY SYSTEM I-309 DRYER107DAF02 ZERO SPEED (RUNNING) Pass
I-310 DRYER107DAF02 ZERO SPEED (STOPPED) Pass
A-214 CLOSE STEAM VALVE TV-740 TO AIR HEATER 107DAE06 I-161 HOT AIR SYSTEM FAN 107DAC07 STOPPED Pass
I-163 AIR HEATER 107DAE06 OUTLET PRESSURE LOW LOW Pass
I-381 Access door open Pass
A-217 HOT AIR SYSTEM FAN 107DAC07 STOPS I-382 Access door open Pass
I-419 HOT AIR SYSTEM FAN 107DAC07 IN BOARD HIGH TEMPERATURE Pass
I-420 HOT AIR SYSTEM FAN 107DAC07 OUT BOARD HIGH TEMPERATURE Pass
Testing Summary

ISBL OSBL
Test Description
Total Done Remain % Total Done Remain %

Internal Loop Test 752 752 0 100% 731 731 0 100%

Hot loop Test 600 264 336 44% 548 162 386 30%

178 11 167 6% 192 0 192 0%


Interlocks Testing

Testing Summary
ISBL OSBL
100% 100%

44%
30%
6%
0%
Internal Loop Test Hot loop Test Interlocks Testing