Professional Documents
Culture Documents
Electrical Protection
Electrical Protection
bus bars,
circuit breakers,
power contactors,
power fuses,
protective relays,
Controls and
indicating devices
ELECTRICAL PROTECTION 05/31/2023 2
Switchgear
whereas
For voltages up to 600 V it is often required to use four bus bars, one being
for the neutral.
When a 4-wire system is required the incoming and bus bar section circuit
breakers may be 3-pole with a linked neutral or be 4-pole.
If the SWBD or MCC feeds equipment located in a hazardous area then the
4-pole circuit breakers should be used.
For balanced loads and for voltages above 1000 V a 3-wire source is used
and hence only three bus bars are needed.
Neutral bus bars are usually rated at half the phase bus bar current ratings.
400
630 800
800 1600
1200 2400
1600 3000
2000 3150
2400 3500
3000 4000
3150
Bus bars are mounted on insulated bushes that are strong
enough to withstand the peak short circuit currents and forces.
Short-Circuit Protection
The most commonly used is the Merz–Price scheme. Each sending end and
receiving end line of each cable is equipped with a matched current
transformer. At the sending end switchgear is placed the (87) relay to detect
an out-of-balance current due to a fault within the cable. The operating time
for this scheme is typically 5 or 6 cycles of fundamental frequency current.