Structural Evaluation and Retrofit Design of

Warehouse Building for UDN at Thankot


Architectural Plan
Architectural Section
General Design Criteria
(Gravity Loading)
Dead Loads:
Dead loads for analysis are calculated as per Indian Standard, IS 875 -1987(part1), in which floor
finishes has been assumed as 1.25 kN/m2. Wall loads are taken from architectural drawings, in which
brick wall loadings are applied as line loads over the beams. Also, for internal partition 1KN/m2 is
applied in floor finishes.
9” thk brick wall = 13.28 kN/m - For full external wall load
9” thk brick wall = 10 kN/m - For external wall with 25% opening
4” AAC block wall = 3.5 kN/m - For internal wall with 20% opening
8” AAC block wall = 6 kN/m - For external wall with 20% opening
  Temperature Load
Live Loads:
Temperature Difference of 17˚C is considered in all
Plinth Level = 10 kN/m2
1st Floor Level = 7 kN/m2 Structural element during a day for structural analysis
2nd Floor Level = 7 kN/m2 (Beam, Column, Slab, Shear Wall)
2nd Floor Mezz Level = 6 kN/m2
3rd Floor Level = 7 kN/m2
4th Floor Level = 7 kN/m2
5th Floor Level (Mezz) = 5 kN/m2
6th Floor Level = 5 kN/m2
Staircase and Corridor= 5 kN/m2
Option 1
Load Pattern Definitions
Seismic Parameters Clause
Zone Factor 0.35 Clause 4.1.4
Importance Factor 1 Clause 4.1.5
Ductility Factor 4 Clause 5.3, Table 5-2
Over strength factor for ULS 1.5 Clause 5.4, Table 5-2
Over strength factor for SLS 1.25 Clause 5.4, Table 5-2
Site Subsoil Category D Clause 4.1.3
Height of Structure, H (m) 28.55 m
075
Time period of structure (Ti=0.05H ) 0.926 Clause 5.1.2
Amplification of period, T=1.25Ti 1.157 Clause 5.1.3
Spectral shape factor 2.25 Clause 4.1.2, Figure 6
Design Seismic Coefficient (ULS) 0.1313 Clause 6.1.1
Design Seismic Coefficient (SLS) 0.126 Clause 6.1.2
Story Drift (Eqx SLS)
Story Drift (Eqy SLS)
Eccentricity Calculation

Eccentricity Calculation
Storey XCCM YCCM XCR YCR X diff (CM CR)Y diff (CM CR) %X %Y
m m m m m m
1st Floor Lvl 17.1569 28.5034 16.5924 28.2532 0.5645 0.2502 1.51% 0.46%
2nd Floor Lvl 0 0 0 0 0.00% 0.00%
2nd Floor Mezz Lvl 18.6116 29.997 19.4988 29.5078 0.8872 0.4892 2.38% 0.89%
3rd Floor Lvl 18.7481 30.2771 19.5527 29.5697 0.8046 0.7074 2.15% 1.29%
4th Floor Lvl 0 0 0 0 0.00% 0.00%
5th Floor Lvl 18.6065 30.4875 19.2549 29.5247 0.6484 0.9628 1.74% 1.76%
6th Floor Lvl 17.8352 28.5487 19.0749 29.2329 1.2397 0.6842 3.32% 1.25%
3rd Floor Lvl 18.542 30.3951 19.6299 29.7246 1.0879 0.6705 2.91% 1.23%
Concrete Design
Option 2
Load Pattern Definitions
Seismic Parameters Clause
Zone Factor 0.35 Clause 4.1.4
Importance Factor 1 Clause 4.1.5
Ductility Factor 3 Clause 5.3, Table 5-2
Over strength factor for ULS 1.3 Clause 5.4, Table 5-2
Over strength factor for SLS 1.15 Clause 5.4, Table 5-2
Site Subsoil Category D Clause 4.1.3
Height of Structure, H (m) 28.55 m
075
Time period of structure (Ti=0.05H ) 0.617 Clause 5.1.2
Amplification of period, T=1.25Ti 0.772 Clause 5.1.3
Spectral shape factor 2.25 Clause 4.1.2, Figure 6
Design Seismic Coefficient (ULS) 0.2019 Clause 6.1.1
Design Seismic Coefficient (SLS) 0.1369 Clause 6.1.2
Shear Wall Distribution
Shear Wall Distribution (Plan)
Concrete Design
Shear Wall Concrete Design