• IS: 1904 – Indian Standard code of practice for design and construction
of foundations in Soil – General requirements.
• IS: 2950 – Indian Standard code of practice for design and
construction of raft foundation (Part – I)
• IS: 2911 – Indian Standard code of practice for design and
construction of pile foundations.
Detailing of Structures
Story Output Case Case Type Step Type Step Number Direction Maximum Average Ratio
mm mm
6th Floor Lvl EQx SLS LinStatic Step By Step 1X 19.582 18.48 1.06
5th Floor Lvl EQx SLS LinStatic Step By Step 1X 15.806 14.063 1.124
4th Floor Lvl EQx SLS LinStatic Step By Step 1X 11.621 11.153 1.042
3rd Floor Lvl EQx SLS LinStatic Step By Step 1X 8.945 8.627 1.037
2nd Floor Mezz Lvl EQx SLS LinStatic Step By Step 1X 6.76 6.198 1.091
2nd Floor Lvl EQx SLS LinStatic Step By Step 1X 4.224 3.51 1.203
1st Floor Lvl EQx SLS LinStatic Step By Step 1X 2.66 2.153 1.235
6th Floor Lvl EQy SLS LinStatic Step By Step 1Y 51.647 51.317 1.006
5th Floor Lvl EQy SLS LinStatic Step By Step 1Y 42.67 42.1 1.014
4th Floor Lvl EQy SLS LinStatic Step By Step 1Y 32.097 31.81 1.009
3rd Floor Lvl EQy SLS LinStatic Step By Step 1Y 23.389 23.038 1.015
2nd Floor Mezz Lvl EQy SLS LinStatic Step By Step 1Y 15.516 15.043 1.031
2nd Floor Lvl EQy SLS LinStatic Step By Step 1Y 8.692 8.105 1.072
1st Floor Lvl EQy SLS LinStatic Step By Step 1Y 3.8 3.368 1.128
Modal Patricipating Mass Ratio
TABLE: Modal Participating Mass Ratios
Case Mode Period, sec UX UY Sum UX Sum UY RZ Sum RZ
Modal 1 0.90 0.00 0.55 0.00 0.55 0.00 0.00
Modal 2 0.54 0.58 0.00 0.58 0.55 0.01 0.01
Modal 3 0.44 0.01 0.00 0.59 0.55 0.55 0.55
Modal 4 0.28 0.00 0.16 0.59 0.71 0.00 0.55
Modal 5 0.20 0.18 0.00 0.76 0.71 0.00 0.56 Modal Participating Mass Ratios
Modal 6 0.17 0.00 0.00 0.77 0.71 0.13 0.68 1.20
Modal 7 0.16 0.00 0.01 0.77 0.72 0.00 0.68
Shear Wall Jacket in Lift Walls and new added shear walls
Beam FRP Jacket
Summary of the changes made to structure
during the retrofit design:
1. The design review of building with floor extension has been carried out in accordance with the provisions of NBC
105:2020. For additional analysis and design requirements, international codes such as IS 1893:2016 has been
referred.
2. The design review and retrofit design has been done assuming the importance factor as 1 and the lateral load resisting
system is selected as Structural Wall System for Block A and Moment Resisting Frame System for Block B.
3. New shear walls have been introduced at 5 locations to remedy the torsional irregularity. Shear walls for both the lifts
have been jacketed to avoid the in-plane shear and flexural failure.
4. Few columns have been jacketed using concrete jacket to accommodate the flexural demand. Similarly, few other
columns have also been jacketed using steel jacket to avoid failure.
5. Steel brace in grid 1, 3 and 16 have been added to supplement the shear walls in the upper stories where it was not
practical to provide shear walls due to architectural constraints.
6. Seismic analysis showed that few beams fail in shear as well as flexure. It has been recommended to provide CFRP
jacketing in such beams.
7. Some beams in 4th floor and above (which has not been constructed) also fail so the sizes for these beams have been
increased.
8. It is recommended to consult with Geotech Engineer regarding the foundation design and pile raft interaction.