Professional Documents
Culture Documents
Chapter 4 - Electricity Intake (2020 Edition)
Chapter 4 - Electricity Intake (2020 Edition)
Training Course- E1
4.1.3 The permissible variation from the nominal Voltage shall be kept
within + 10% and - 6%.
4.1.6 The permitted limits of such disturbances are given in the Electricity
Distribution Code, Annex 1. Owners will be required to install filters
or other equipment to mitigate against such disturbances that are
outside the permitted limits (as explained in the Electricity
Distribution Code).
4.2.1 The Electricity Intake must be positioned in a dedicated room or housing and would
typically be made from concrete block, brick or similar construction.
[Note: where prefabricated enclosures are used, the enclosures must be verified in accordance
with the relevant international standards and be approved by the Distribution Company prior to
installation.]
4.2.3 The Electricity Intake must be positioned in an area which is readily accessible to
Distribution Company staff and other authorised persons, particularly in an
emergency, and must be at or close to the outside perimeter of a Premises.
4.2.4 The Electricity Intake must not be positioned in an area controlled by one of
the tenants in a multi-occupancy building.
4.2.6 The use of Electricity Intake rooms as storage rooms for any tools,
equipment or other materials is prohibited.
4.2.8 The Electricity Intake room must be well ventilated, preferably without the need
for forced air circulation. Where air conditioning is required in the Electricity
Intake room, the requirement for fresh air circulation must also be provided to
avoid condensation.
[Note: consideration must be given to the relevant UAE fire code requirements.]
4.2.9 At least one emergency lighting unit must be fitted in all Electricity Intake
rooms, which must be provided with a battery rated for minimum 3 hours’
illumination, and subject to adequate routine maintenance.
4.2.11 The need for delivery of heavy equipment to the Electricity Intake
room during construction and for future repair or alterations must be
taken into account in the location of the Electricity Intake room.
4.2.12 For Electricity Intake rooms greater than 6 m in length, more than
one door shall be provided as a means of emergency access.
4.2.15 Where a HV/LV substation is required within the Premises, the design and
construction requirements for the substation will be specified by the
Distribution Company.
4.3.2 The Owners’ Main Distribution Board must always include a means of emergency isolation in
the case of a fault or breakdown (e.g. main circuit breaker) which is readily accessible and
clearly labelled so as to be easily operated by the Owner. Such means of emergency
isolation must be left unlocked at all times, except when locked in the open position to allow
access to the Electrical Installation (e.g. for maintenance).
4.4.1 Individual Customers within multiple occupancy Premises may be supplied by the Premises
Owner’s Electrical Installation consisting of rising and lateral mains (cabling or busbars).
Rising and lateral mains will normally be owned and operated by the Premises Owner.
4.4.2 The electricity metering for individual Customers for a rising or lateral mains system will
normally be at the point nearest to each Customer, remote from the main Electricity Intake.
a) 2 metres
b) 2.5 metres
c) 1.0 metres
d) 1.5 metres