Insulation Systems
All Frame Sizes
PRODUCT TRAINING
GENERATOR RATINGS
(NOTE: Ratings are 3 Phase, Class H, Continuous Base Load, at 40º Ambient)
PRODUCT TRAINING
GENERATOR RATINGS – TEMPERATURE RISE
Cooling
Excitation Copper losses Iron losses
Current (Load current) (Hysteresis
& Eddy currents)
PRODUCT TRAINING
TEMPERATURE RISE LIMITS OF INSULATION SYSTEMS
Medium & High Voltage Generators are usually Class F insulation systems.
However, Class H temperature rise can be achieved with Medium Voltages.
For Class F and B temperature rise, the Generator kVA must be reduced,
(de-rated), to reduce the full load temperature rise within thermal limits.
PRODUCT TRAINING
HALF LIFE OF CLASS H INSULATION SYSTEMS
DEFINED AS - THE TIME TAKEN FOR THE ORIGINAL INSULATION VALUE TO BE REDUCED BY HALF
640,000
O
P 120,000
E
R
A
T
I 20,000
N
G
H
O 3,500
U
R
S
1000
100 110 120 130 140 150 160 170 180 190 200 210 220
CLASS B CLASS F CLASS H CLASS H
PEAK / ST’DBY
THERMAL CLASSIFICATION OF INSULATION SYSTEM oC
PRODUCT TRAINING
OTHER FACTORS EFFECTING RATINGS
400 0.2
TEMPERATURE IN ºC
0 55
350 0.3
0
300 0.4
50
0
250 0.5
0
200 45 0.6
0
150 0.7
0 0.81.0
100 40 0.95 0.90 0.85
0 1.0 0.95 0.9 0.85 0.8 1.0 0.95 0.9 0.85
DERATE MULTIPLIER DERATE MULTIPLIER DERATE MULTIPLIER
A DE-RATE OF 3% FOR EVERY 5°C ABOVE 40°C AT THE GENERATOR AIR INTAKE .
PRODUCT TRAINING
RETURN TO MAIN MENU