Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 34

Refinery in Dos

Bocas (R2B) project

Presented By: Dos Bocas Team


Date: March 7th, 2022

Confidential Property of Schneider Electric


Internal
Project Context

• 2019 - Mexico Government announced the construction of the


6.81 B€ (2.13B€) High-Energy Efficiency PEMEX “Dos Bocas Dos Bocas New Refinery in Mexcio
New Refinery”

• Refinery Dos Bocas is the “flagship Project” by current


government of Mexico and It will be the biggest refinery in
Mexico.

• The aims is to reduce Mexico's dependence of fuels imports and


to reactivate the energy sector in the southeast.

• Dos Bocas refinery will have a capacity of 340,000 barrels per


day (bpd) and it will process 22° API maya crude oil.

• The refinery is being developed on a 566 ha site in the Port of


Dos Bocas close maritime terminal in Paraíso, Tabasco

• The project is divided into six packages to include engineering State-owned Petroleos Mexicanos
and construction work: (Pemex) will be the owner and
• 27 processing plants or Units
operator of the refinery
• Power plants
• 93 storage tank and spheres
• A new pipeline will connect to maritime terminal
Confidential Property of Schneider Electric | Page 2
Internal
1.2.2 Site Information

Confidential Property of Schneider Electric | Page 3


Internal
Dos Bocas Project Overview, EPC´s Contracts Value

Package I Package IV
1.7 B US 0.3 BUS
•Distillation Plant • Sulphur recovery plant
•Coking plant • Gas recovery and treatment plant
• Hydrogen-producing plant
• Columna C3 Splitter

Package Package V
Asociados Constructores DBMR II - III
0.4 B US
• Storage facilities
1.7 B US


Diesel hydro desulphurisation (DHDT) Unit
gasoil hydro desulphurisation (HDS) Unit Package VI
• Naphtha hydro-treating (NHT) Unit
• Naphtha reformer Unit
1.8 B US
• Refinery integration services.
1.4 B US
•Fluid catalytic cracking (FCC)

Confidential Property of Schneider Electric | Page 4


Internal
Paquete EPC WBS Planta o Instalación Sector
201 Planta Combinada 1
1 ICAF
202 Planta de Coquización Retardada 2
PLANTS – SECTORS – EPCs 203 Planta Hidrodesulfuradora de Naftas No.1 y No.2 5
204 Planta Hidrodesulfuradora de Diésel No.1 y No.2 4
2 Samsung
205 Planta Hidrodesulfuradora de Gasóleos 4
207 Planta Reformadora de Naftas 5
• The project is divided in 8 sectors, each one of them will be an 3 Samsung 206 Planta de Desintegración Catalítica 3
independent ICSS system 208 Planta Isomerizadora de Pentanos y Hexanos 5

• The systems to be provided are: 3A ICAF -UOP 209 Planta Isomerizadora de Butanos 3
210 3
• DCS Planta de Alquilación
212 Unidad de Tratamiento de Aguas Amargas 6
• ESD 213 Unidad Regeneradora de Amina 6
• FGS 4A Techint 401 y 402 Suministro y Pretratamiento de Agua 8
• SINE (Sistema Integral de Notificación de Emergencias)= 418 Planta Tratamiento de Efluentes 7

Emergency notification system connected to the FGS. 420 Almacenamiento y Recibo de Sosa Caustica 7
211 5
• SIAD (Sistema de Información y Administración de Planta de Tratamiento de Gases
214 Planta Recuperadora de Azufre 6
Datos)= PI OsiSoft? 4B ICAF
215 Planta de Hidrógeno 4
• AVEVA OTS 412 Desfogue 6
• AVEVA OMM & TIS & DBS, Blending package 305 Báculas de Carrotanques y Autotanques  
• Networks are independent between sectors. They only converge 308 Sistema de Drenajes Aceitoso, Químico, Sanitario y Pluvia 7
(Cárcamos)
to the top level through firewalls for the SIAD and the SINE 405 Torres de Agua de Enfriamiento (Equipos Auxiliares)  
systems. 406 Recuperación y Tratamiento de Condensado 8
• Each sector will have dedicated 407 Sistema de Combate Contraincendio NA
• redundant domain controller, 454 Casas de Bombas 7
410 7
• galaxy, 6 PROYECTA
Sistema Mezclado en Línea
411 Patines de Regulación y Medición 7
• historian and 419 Almacenamiento y Distribución de Nitrógeno 8
• redundant of data collectors. 423 Red de Aire de Instrumentos y Aire de Planta 8
• One centralized control room. 424 Suministro de Gas Combustible 8
426 Sistema de Azufre Líquido  
428 Instrumentación Área de Almacenamiento 7
430 Acueducto 8
Confidential Property of Schneider Electric | Page 5 431 Gasoducto  
Internal SN JADIAZ 317 Cuarto de Control Central  
1.1.1 Scope of Work by systems and plants

Systems and Funtions


No. Descripción BLENDING Y
DCS ESD SFG SINE SIAD OTS
TGS
201 COMBINED PLANT X X X X X    
202 DELAYED COKE PLANT X X X X X X  
203 NAPHTHA HYDRODESULFURATION PLANT No. 1 AND No. 2 X X X X X    
204 DIESEL HYDRODESULFURATION PLANT No. 1 AND No. 2 X X X X X    
205 DIESEL HYDRODESULFURATOR X X X X X    
206 FLUID CATALYTIC CRACKING X X X X X X  
207 REFORMER X X X X X    
208 PENTANES AND HEXANS ISOMERIZATION PLANT X X X X X    
209 BUTANES ISOMERIZATION PLANT X X X X X    
210 ALKILATION X X X X X    
211 GAS TREATMENT PLANT X X X X X    
212 SOUR WATER TREATMENT UNIT X   X X X    
213 AMINE REGENERATION X X X X X    
214 SULFUR RECOVERY PLANT X X X X X    
215 HYDROGEN PLANT X X X X X    
305 TANK AND TRUCK SCALES X   X        
317 BUILDINGS X       X     
405 AUXILIARY SERVICES (COOLING TOWER AND PUMPING SYSTEMS) X   X        
407 SECURITY SYSTEM (ACI NETWORK, CI EQUIPMENT, STORAGE TANK AND ACI PUMPS, TRUCKS)     X X      
411 REGULATION AND MEASUREMENT SKATES X X X X X    
451 WATER SUPPLY AND PRE-TREATMENT X            
452 AUXILIARY SERVICES (CONDENSATE, NITROGEN, AIR AND COMBUSTIBLE GAS) X X X X X    

453 EFFLUENTS (WASTE), STORAGE AND RECEIPT OF SULFURIC ACID AND CAUSTIC SODA X   X X X    
454 STORAGE AND MOVEMENT OF PRODUCTS X X X X X   X

Confidential Property of Schneider Electric | Page 6


Internal
ARCHITECTURES

Confidential Property of Schneider Electric | Page 7


Internal
Interconnections between DCS

Confidential Property of Schneider Electric | Page 8


Internal
CNI INTERCONNECTIONS

Signal quantities between sectors are still not defined. Sector 1


In the Feed phase we specify <75 signals per CNIs.

Sector 6 Sector 2

Sector 7 Sector 3

Confidential Property of Schneider Electric | Page 9


Sector 5 Sector 4
Internal
CCR Communications to corporate and emergency information systems

• There are eight sectors, each one of them, provides information to the higher hierarchy data networks.
• SIAD the administration network gets the information through an AIM OPC data server (non-redundant) in each sector
• SINE the emergency notification system gets the information through a Triconex P2P coms with the FGS (redundant)

Confidential Property of Schneider Electric | Page 10


Internal
SECTOR 1:
EPC ICAF Unit 201

UNIT 201
• Six FCP280
• Four FDC280
• Thirteen Tricon CXs for ESD/BMS
• Three Tricon CXs for FGS
• Five V91
• One H90

• I/O:
• 4.2K DCS
• 1.9K ESD/BMS
• 1.3K FGS

Confidential Property of Schneider Electric | Page 11


Internal
SECTOR 2:
EPC ICAF Unit 202

UNIT 202
• Six FCP280
• Four FDC280
• Thirteen Tricon CXs for ESD/BMS
• Three Tricon CXs for FGS
• Five V91
• One H90

• I/O:
• 4.2K DCS
• 1.9K ESD/BMS
• 1.3K FGS

Confidential Property of Schneider Electric | Page 12


Internal
SECTOR 3:
EPC Samsung and ICAF Units 206, 209 & 210

UNIT 206 UNIT 209 UNIT 210


• 3 FCP280 • 2 FCP280 • 4 FCP280
• 5 FDC280 • 4 FDC280 • 4 FDC280
• 2 Tricon CXs for ESD • 1 Tricon CXs for ESD • 2 Tricon CXs for ESD
• 1 Tricon CXs for FGS • 1 Tricon CXs for FGS • 1 Tricon CXs for FGS
• 5 V91 • 1 Thin Client • 1 H90
• 1 H90
• 10 Thin Clients
• I/O: • I/O:
• I/O: • 1K DCS • 1600 DCS
• 2.6K DCS • 200 ESD/BMS • 800 ESD/BMS
• 0.6K ESD/BMS • 300 FGS • 700 FGS
• 0.6K FGS • 200 Soft
• 14K Soft

UNIT 405
• 2 FCP280
• 2 FDC280

• I/O:
• 100 DCS
• 2.2K Soft

Confidential Property of Schneider Electric | Page 13


Internal
SECTOR 4:
EPC Samsung and ICAF Units 204, 205 & 215

UNIT 204 UNIT 205 UNIT 215


• 4 FCP280 • 3 FCP280 • 2 FCP280
• 4 FDC280 • 4 FDC280 • 4 FDC280
• 9 Tricon CXs for ESD • 6 Tricon CXs for ESD • 2 Tricon CXs for ESD
• 2 Tricon CXs for FGS • 3Tricon CXs for FGS • 2 Tricon CXs for FGS
• 5 V91 • 1 H90 • 1 H90
• 1 H90
• 5 Thin Clients
• I/O: • I/O:
• I/O: • 2.7K DCS • 800 DCS
• 4.8K DCS • 1K ESD/BMS • 500 ESD/BMS
• 2K ESD/BMS • 0.7K FGS • 300 FGS
• 0.7K FGS • 2000 Soft

Confidential Property of Schneider Electric | Page 14


Internal
SECTOR 5:
EPC Samsung-ICAF Units 203, 207, 208 & 211

UNIT 203 UNIT 207 UNIT 208 UNIT 211


• 4 FCP280 • 2 FCP280 • 2 FCP280 • 1 FCP280
• 4 FDC280 • 8 FDC280 • 4 FDC280 • 2 FDC280
• 9 Tricon CXs for ESD/BMS • 2 Tricon CXs for ESD/BMS • 1 Tricon CXs for ESD • 1 Tricon CXs for ESD/BMS
• 2 Tricon CXs for FGS • 1 Tricon CXs for FGS • 1 Tricon CXs for FGS • 1 Tricon CXs for FGS
• 1 H90 • 1 H90 • One H90 • 1 H90
• 5 V91 • 2 Thin clients
• 5 Thin clients
• I/O: • I/O: • I/O:
• I/O: • 1.5K DCS • 1.4K DCS • 500 DCS
• 3.5K DCS • 400 ESD/BMS • 300 ESD/BMS • 100 ESD/BMS
• 1.8 ESD/BMS • 400 FGS • 350 FGS • 350 FGS
• 0.7 FGS • 16.4K Soft • 2.1K Soft • 1000 Soft
• 4K Soft

Confidential Property of Schneider Electric | Page 15


Internal
SECTOR 6:
EPC Techint-ICAF Units 212, 213 & 214

UNIT 212 UNIT 213 UNIT 214


• 3 FCP280 • 3 FCP280 • 2 FCP280
• 2 FDC280 • 2 FDC280 • 3 FDC280
• 1 Tricon CXs for FGS • 1 Tricon CXs for FGS • 3 Tricon CXs for ESD
• 1 H90 • 1 H90 • 2 Tricon CXs for FGS
• 5 V91
• 1 H90
• 8 Thin Client

• I/O: • I/O: • I/O:


• 1K DCS • 1K DCS • 1000 DCS
• 300 FGS • 300 FGS • 500 ESD/BMS
• 200 Soft • 300 Soft • 400 FGS
• 1700 Soft

Confidential Property of Schneider Electric | Page 16


Internal
SECTOR 7:
EPC Techint-Proyecta Units 418, 420, 409A, 410 & 428

UNIT 418 UNIT 420 UNIT 409A UNIT 410 UNIT 428
• 3 FCP280 • 2 FCP280 • 2 FCP280 • 2 FCP280 • 2 FCP280
• 3 FDC280 • 4 FDC280 • 4 FDC280 • 4 FDC280 • 4 FDC280
• 2 Tricon CXs for ESD • 2 Tricon CXs for ESD • 2 Tricon CXs for ESD • 2 Tricon CXs for ESD • 2 Tricon CXs for ESD
• 1 Tricon CXs for FGS • 1 Tricon CXs for FGS • 1 Tricon CXs for FGS • 1 Tricon CXs for FGS • 1 Tricon CXs for FGS
• 5 V91 • 1 H90 • 1 H90 • 1 H90 • 1 H90
• 1 H90
• 10 Thin clients

• I/O: • I/O: • I/O: • I/O: • I/O:


• 2.6K DCS • 1.5K DCS • 1.5K DCS • 1.5K DCS • 1.5K DCS
• 700 ESD/BMS • 400 ESD/BMS • 400 ESD/BMS • 400 ESD/BMS • 400 ESD/BMS
• 700 FGS • 400 FGS • 400 FGS • 400 FGS • 400 FGS
• 14K Soft • 16.4K Soft • 16.4K Soft • 16.4K Soft • 16.4K Soft

UNIT 412
• 1 FCP280
• 2 FDC280
• 1 Tricon CXs for FGS
• 1 H90

• I/O:
• 160 DCS
• 96 FGS
• 700 Soft

Confidential Property of Schneider Electric | Page 17


Internal
SECTOR 8:
EPC Techint-Proyecta Units 401, 402, 406, 419, 423 & 424

Pending information, waiting for the PO, part of this sector will be done in Italy, out of the Mexico Office Scope.

Confidential Property of Schneider Electric | Page 18


Internal
The five V91s per sector: Server 1 & 2

  V91 Virtual Server 1 (V914R4440LA0 6 VM) V91 Virtual Server 2 (V914R4440LA0 6 VM)
Slot NAME Role NAME Role

HDD (GB)

HDD (GB)
(C: & D:)
(C: & D:)
Memory

Memory
CPU

CPU
(GB)

(GB)
(#)

(#)
  V91-01-CCC- V91 Licensed for 6 VMs 20 304 3050 V91-01-CCC- V91 Licensed for 6 VMs 18 296 2700
01 02
1 CVM102 SDC CVM 2 8 200 OW2013 Estación de Operación 2 16 200
2 OW2011 Estación de Operación 2 16 200 OW2014 Estación de Operación 2 16 200
3 OW2012 Estación de Operación 2 16 200 SIF101 SIF Manager (PSA OP Core) 2 8 250
4 SIF104 SIF Manager (Console) 2 8 150 SIF102 SIF Manager (Historian) 2 8 300
5 Available --- --- --- --- SIF103 SIF Manager (Collector) 2 8 150
6 Available --- --- --- --- Available --- --- --- ---
7 OW2013' Estación de Operación 2 16 200 OW2011' Estación de Operación 2 16 200
8 OW2014' Estación de Operación 2 16 200 OW2012' Estación de Operación 2 16 200
9   --- --- --- ---   --- --- --- ---
10   --- --- --- ---   --- --- --- ---
11   --- --- --- ---   --- --- --- ---
12   --- --- --- ---   --- --- --- ---
13   --- --- --- ---   --- --- --- ---
14   --- --- --- ---   --- --- --- ---
    Number of core (8/16) 16 --- ---   Number of core (8/16) 16 --- ---
    Hyper threading (y/n) yes --- ---   Hyper threading (y/n) yes --- ---
    CAPACITY 32 384 4200   CAPACITY 32 384 4200
    TOTAL usage in Virtual Machines 12 80 1150   TOTAL usage in Virtual Machines 14 88 1500
  Host Machine snapshot required HDD space --- --- 287.5   Host Machine snapshot required HDD space --- --- 375
  (25% of each VHDD) (25% of each VHDD)
    Minimum for Host OS 6 77 ---   Minimum for Host OS 6 77 ---
    AVAILABLE 14 227.2 2762.5   AVAILABLE 12 219.2 2325

Confidential Property of Schneider Electric | Page 19


Internal
The five V91s per sector : Server 3 & 4

V91 Virtual Server 3 (V914V4440LA0 14 VM) V91 Virtual Server 4 (V914V4440LA0 14 VM)
NAME Role NAME Role

HDD (GB)

HDD (GB)
(C: & D:)
Memory

(C: & D:)


Memory
CPU

(GB)

CPU

(GB)
(#)

(#)
V91-01-CCC- V91 Licensed for 14 VMs 16 320 2350 V91-01-CCC- V91 Licensed for 14 VMs 14 312 2200
03 04
EWS101 Galaxy Repository / Estación de Ingeniería 4 16 550 HSS101 Servidor Histórico 4 16 700
DCS101 Colector de Datos Principal 2 8 200 DCS102 Colector de Datos Secundario 2 8 200
SDC101 SDC offmesh.local 2 8 200 PDC101 PDC offmesh.local 2 8 200
Available --- --- --- --- EPO101 McAfee ePO 2 8 150
Available --- --- --- --- Available --- --- --- ---
Available --- --- --- --- Available --- --- --- ---
Available --- --- --- --- Available --- --- --- ---
Available --- --- --- --- Available --- --- --- ---
SIF101' SIF Manager (PSA OP Core) 2 8 250 MW0101' Maintenance Advisor 4 16 200
SIF102' SIF Manager (Historian) 2 8 300 SA0101' System Advisor 4 16 200
SIF103' SIF Manager (Collector) 2 8 150 DCS101' Colector de Datos Principal 2 8 200
DCS102' Colector de Datos Secundario 2 8 200 SIF104' SIF Manager (Console) 2 8 150
  --- --- --- ---   --- --- --- ---
  --- --- --- ---   --- --- --- ---
  Number of core (8/16) 16 --- ---   Number of core (8/16) 16 --- ---
  Hyper threading (y/n) yes --- ---   Hyper threading (y/n) yes --- ---
  CAPACITY 32 384 4200   CAPACITY 32 384 4200
  TOTAL usage in Virtual Machines 16 64 1850   TOTAL usage in Virtual Machines 22 88 2000
  Host Machine snapshot required HDD space --- --- 462.5   Host Machine snapshot required HDD space --- --- 500
(25% of each VHDD) (25% of each VHDD)
  Minimum for Host OS 6 77 ---   Minimum for Host OS 6 77 ---
  AVAILABLE 10 243.2 1887.5   AVAILABLE 4 219.2 1700

Confidential Property of Schneider Electric | Page 20


Internal
The five V91s per sector : Server 5

V91 Virtual Server 5 (V914V4440LA0 14 VM)


NAME Role

HDD (GB)
(C: & D:)
Memory
CPU

(GB)
(#)
V91-01-CCC- V91 Licensed for 14 VMs 10 296 2050
05
CVM101 PDC CVM 2 8 200
MW0101 Maintenance Advisor 4 16 200
SA0101 System Advisor 4 16 200
CMC101 Consola de Administración Central 2 8 150
MRC101 MRC Domain Controller 2 8 150
Available --- --- --- ---
Available --- --- --- ---
Available --- --- --- ---
EWS101' Galaxy Repository / Estación de Ingeniería 4 16 550
HSS101' Servidor Histórico 4 16 700
  --- --- --- ---
  --- --- --- ---
  --- --- --- ---
  --- --- --- ---
  Number of core (8/16) 16 --- ---
  Hyper threading (y/n) yes --- ---
  CAPACITY 32 384 4200
  TOTAL usage in Virtual Machines 22 88 2150
  Host Machine snapshot required HDD space --- --- 537.5
(25% of each VHDD)
  Minimum for Host OS 6 77 ---
  AVAILABLE 4 219.2 1512.5

Confidential Property of Schneider Electric | Page 21


Internal
Question 1:

Data collectors:

As you can see in the architectures, there are a pair of data collectors per sector, and we are planning to create dedicated VMs in order to fulfill
this functionality. One Historian VM Server per sector.

Should they be dedicated VMs?


Can be integrated in the operator VMs?
What is the recommendation in this regards? Is there any specific incompatibility on which host can have these VMs?
Can we have Historian server VM and data collector in the same V91? Galaxy?
Is the replication of the data collector VM possible?

Confidential Property of Schneider Electric | Page 22


Internal
Question 2:

Message manager:

Planning to use MM mode, we need to pick two stations to receive the alarms…
Do we need to have a dedicated VMs for this functionality?
Is it ok to select operator VMs?
What about replicating them?

Confidential Property of Schneider Electric | Page 23


Internal
Question 3: VM for operation - Replication and VM distribution

Operator workstations:

Should we replicate the VM for the operators and put them in different V91, so we lose one of them at a time when we need to
patch the Host server.

Confidential Property of Schneider Electric | Page 24


Internal
Question 4: WW Historian on mesh/off mesh? Replication?

Aveva WW Historian server

1. we discussed to put this VM on the mesh or leave it off mesh. What is recommended? The benefits are time synchronization
and System manager monitoring but the cons are harder to maintain, loss of resources, performance impact, multiple networks,
etc.
2. Should we replicate the VM of the Historian server? Since Data Collectors are redundant, they should be able to store the data
until the Historian server VM is back.

Confidential Property of Schneider Electric | Page 25


Internal
Question 5: Domain Controllers’ Consolidation

Consolidation of Domains controllers

The installation manual does not recommend to install the Domain for the replication in the Foxboro domain controller, but since
they are 8 independent sectors this will mean we will need 32 VMs for domain controller functionality, 16 for the corporate (8
primary and 8 secondary) + 16 CVM (8 PDC and 8 SDC). If we can validate the consolidation of the domains this will be reduced to
16 (two per sector).
 6.3.3. Consolidation of Domains
The consolidation of Domains is not currently an accepted design for Foxboro DCS, ACN, and VHN, it could be part of a future
DCS product scope and eventually involve cost savings in having just one Domain for the overall CVM architecture.

Confidential Property of Schneider Electric | Page 26


Internal
Question 6: VLANS

VLANs:

We are sharing switches between different networks. This will require to create different VLANs and somehow segregate ports in
the switches for the different networks…
How should we prioritize the different networks?  
Switch configuration software alone won’t work…
Should we keep the MESH network isolated from the others?
ESD & FGS networks?

MESH and ACN are sharing the switches. VHN and Backup network are shared.
AIM OPC server or FS Gateway?

Confidential Property of Schneider Electric | Page 27


Internal
Question 6: VLANS

VLANs:

Confidential Property of Schneider Electric | Page 28


Internal
Question 7: OPC servers

There is an OPC server per sector to provide information to the SIAD, (corporate information network) most likely to be PI:

Our proposal was to provide AIM OPC server but thinking in the lifecycle of the product:

Would be a better approach to replace them for FS Gateways?

Confidential Property of Schneider Electric | Page 29


Internal
Question 8: Control software new release

We are almost in the position to start installing the systems… but we were told that CS 7.3 is coming out by the end of the month, to
avoid rework can we get an early release of the software, or we should just wait to the formal release

Confidential Property of Schneider Electric | Page 30


Internal
Question 9: Extra functionality

There is an idea to add Excel and Visio to the operator workstations… Visio for the live view functionality…  Excel for the Query the
Aveva Historian. Do you think we should give the operators this kind of access? Or should be only for the engineer stations?

See B0750AN page 128.

Confidential Property of Schneider Electric | Page 31


Internal
SIS Questions:

1) P2P networks for the ESD, there is one Triconex in the CCR, with a P2P network, sending the CCR pushbuttons to the Triconex’
s for each units.
2) P2P network for the FGS system, all the FGS Triconex send information by P2P network to the centralized Triconex for the SINE
system.

Confidential Property of Schneider Electric | Page 32


Internal
1.3.3 Customer Information - Cyber Security Engineering

• Windows Active Directory

• McAfee ePO (Threat Prevention, Device Control, Rogue System Detection)

• Firewalls (Internal Firewalls Level 2, External Firewalls Level 3)

• BorderGuard

• Guardian

Confidential Property of Schneider Electric | Page 33


Internal
Internal

You might also like