Professional Documents
Culture Documents
دورة ص0يانة كهربية
دورة ص0يانة كهربية
Luis Gutierrez
LM6000 Controls Engineer
Woodward Tools
2
GAP3 training
08/30/2023
LM6000 Classic
3
GAP3 training
08/30/2023
Woodward GAP
4
GAP3 training
08/30/2023
Monitor GAP
It is a debugging tool included in GAP. To use this functionality a
license is required. The tool allows the engineer or operator to view
and tune the GAP blocks while the application is running, see the
GAP I/O values change. It interfaces with the Ethernet ports via the
included Servlink OPC server tool.
5
GAP3 training
08/30/2023
Servlink OPC Server (SOS)
6
GAP3 training
08/30/2023
LM6000 Classic Architecture
Modbus TCP/IP
iFix HMI
GAP3
SOS OPC
Control Micronet+
Assistant
AppManager
Ethernet TCP/IP
7
GAP3 training
08/30/2023
GAP Introduction
8
GAP3 training
08/30/2023
GAP overview
Menus
Project Index
9
GAP3 training
08/30/2023
GAP Options
10
GAP3 training
08/30/2023
GAP Blocks
The block nomenclature is unique and is used in SOS Servlink, Control Assistant,
Block search and so on.
11
GAP3 training
08/30/2023
GAP 3 Blocks
Block Name Block Description
Tunable input (has a star mark)
Outputs
Inputs
Output connected to
other block
Input coming from other
block Block Type
12
GAP3 training
08/30/2023
GAP 3 Blocks
Double click on any block to open properties:
13
GAP3 training
08/30/2023
GAP 3 Block help
Right click on any block and select “Block Help”. It will display a
detailed description of how the block works, inputs, outputs and
usage. The “block help” can be printed.
14
GAP3 training
08/30/2023
Input
Input Field(s):
• Input wiring or net from another block
• Input connection from another block output
CATEGORY.BLOC_NAME.OUTPUT_FIELD
15
GAP3 training
08/30/2023
How to enter Monitor mode?
Go to menu Monitor, click Monitor and then select Monitor:
16
GAP3 training
08/30/2023
Monitor Mode
It is a licensed software service tool that allows service personnel to
view and edit runtime values for GAP generated application
software. The final control design is displayed as a group of
interconnected blocks that represent the actual functionality of the
code running in the Micronet CPU.
Monitor GAP works in parallel with the GAP graphical display and
superimposes the actual runtime values on that display. In addition.
Monitor GAP runs on a PC and accesses the actual runtime values
from an OPC communication server (SOS Servlink OPC server).
Data is collected in real time so that the values displayed by Monitor
GAP are always current.
17
GAP3 training
08/30/2023
GAP Navigation
SHIFT+CLICK in an input to go to source block:
(Click-only works in Monitor mode only)
18
GAP3 training
08/30/2023
GAP Navigation
It will take you to the source block, highlighting it:
It is highlighted
19
GAP3 training
08/30/2023
GAP Navigation
SHIF+CLICK to go to the output references (places where this
output signal goes):
If the output goes to a single place, it will take you directly to that
block, highlighting it.
20
GAP3 training
08/30/2023
GAP Navigation
SHIF+CLICK to go to the output references (places where this
output signal goes):
If the output goes to multiple places, a list with all those places will
open:
… Or Double-click
on any item to go to
it
21
GAP3 training
08/30/2023
GAP Search
Hit CTRL+F or click the magnifiers icon:
22
GAP3 training
08/30/2023
GAP Search
Block Search dialog window will open. Make sure the filters are set like this
before searching:
23
GAP3 training
08/30/2023
GAP Search
Search by keyword or block name if known. Results appear.
24
GAP3 training
08/30/2023
Hurghada 1&3 GAP site specific
25
GAP3 training
08/30/2023
Hurghada 1&3 GAP site specific
The Revision List is included in the Project Cover Sheet. It lists the
revision letter history, date of implementation and Woodward
Application Engineer name.
26
GAP3 training
08/30/2023
Hurghada 1&3 GAP site specific
If the version running in the Micronet+ CPUs is not the same as the
GAP, a red bar will appear while in Monitor mode. Additionally,
some values may display UNAVAILABLE:
27
GAP3 training
08/30/2023
Hurghada 1&3 GAP site specific
GAP Modules:
• 5418-7038GAP_E: Hardware I/O definitions
• 5418-6525_WTR_INJ_INTERFACE: Not used for this project
• 5418-6525_CLUTCH_INTERFACE: Not used for this project
• 5418-6525_EVAP_INTERFACE: Not used for this project
• WHRU_INTERFACE: Not used for this project
• 5418-6075_PFC_H: Not used for this project
• 5418-6525_FF_B: Fin-Fan control logic
• 5418-6499CORE_D: Engine control, fuel schedules, datalogs
• ELO_PURGE_NEW: Not used for this project
• 5418-6526DF_CAN_A: Gas Metering Valves CAN interface logic
• 5418-6525_BLKST: Soft Black Start sequence logic
• 5418-6525SPRINT_C: Sprint Control & alarm module
• 5418-6073_T: Gas Fuel System Control (mainly liquid, N/A for this
project)
• 5418-7038EGD_B: Egypt site specific BOP EGD interface
• 5418-7038SEQ: Sequencer. It contains most of the logic for the
“package” sequencing and alarms. Logic for the following: Modbus
interface with HMI, Speed Control, Timer & totalizers, Start
Permissives, Start sequence, crank sequence, water wash sequence,
stop sequence (ESN, ES, DM, SI, NS), Hyd Starter, ventilation,
lubrication, MW Control, Generator control, AVR interface, DMMF
interface, Bently Interface. 28
GAP3 training
08/30/2023
Start Permissives
Common troubleshooting practice is to verify start permissives. In
GAP, the block to search for is START_PERM.T_READY
29
GAP3 training
08/30/2023
Start Permissives
30
GAP3 training
08/30/2023
Start Permissives
This is the only FALSE
value into the AND gate.
Thus, it is causing the
problem. Trace back.
31
GAP3 training
08/30/2023
Start Permissives
32
GAP3 training
08/30/2023
Start Permissives
33
GAP3 training
08/30/2023
Start Permissives
LinkNet Boolean
LinkNet RTD LinkNet Analog 4-20
FTM Boolean
35
GAP3 training
08/30/2023
Hardware Input Blocks
These blocks are the input lecture from the different devices:
36
GAP3 training
08/30/2023
Hardware Output Blocks
These blocks are the output signal to the different devices:
Boolean LinkNet
37
GAP3 training
08/30/2023
First Out Shutdown
Search for block FIRST_LTCH and
trace back.
38
GAP3 training
08/30/2023
How to trace FO in iFix to GAP source
FO Shutdown: 616
39
GAP3 training
08/30/2023
How to trace FO in iFix to GAP source
40
GAP3 training
08/30/2023
How to trace FO in iFix to GAP source
41
GAP3 training
08/30/2023
How to trace FO in iFix to GAP source
42
GAP3 training
08/30/2023
How to trace FO in iFix to GAP source
Once the BR_V_X row has been selected, click on the arrow to go
to source block:
43
GAP3 training
08/30/2023
How to trace FO in iFix to GAP source
Trace back as
needed
44
GAP3 training
08/30/2023
How to trace an alarm in iFix to GAP
source
The alarm in iFix Alarm Summary has TAG name and description.
Using the description, search for the alarm in the document “ALM
and SD Modbus list.xlsx”. For example alarm below
U1_ALM_MSTR083 – SEQ:GEN RM AIR TMP H
45
GAP3 training
08/30/2023
How to trace an alarm in iFix to GAP
source
The second column in the document will give the information:
46
GAP3 training
08/30/2023
How to trace an alarm in iFix to GAP
source
And then go to input #633 in the RPT section:
47
GAP3 training
08/30/2023
How to trace an alarm in iFix to GAP
source
Input IN_633 in the RPT section. Its source block is
SHUTDOWN.ALM_LAT.SEL_83. Click the arrow to go to that
block.
48
GAP3 training
08/30/2023
How to trace an alarm in iFix to GAP
source
Now, in the RPT list of the SHUTDOWN.ALM_LAT block, search
for item IN_83. Click on the arrow to go to source block:
49
GAP3 training
08/30/2023
How to trace an alarm in iFix to GAP
source
This is source block TAH6402. TE-6402 value is 125.98 °F
50
GAP3 training
08/30/2023
How to trace an alarm in iFix to GAP
source
According to F&ID 571239, If the temperature is greater than 125
°F there will be an alarm
Use manuals to
determine the
possible cause
and solution.
Also, contact GE
in case of doubt.
51
GAP3 training
08/30/2023
Adding values from GAP to Trend in
Control Assistant
52
GAP3 training
08/30/2023
How to run datalogs manually
53
GAP3 training
08/30/2023
How to extract datalog from CPU and
from HMI computer
54
GAP3 training
08/30/2023