12CJT Trip

Prepared by: Nashaat Nasr – Mahmoud Mohamed


Review by: Mr. Tamer El Minshawy
19-12-2022

Siemens Energy is a registered trademark licensed by Siemens AG. Restricted © Siemens Energy, 2020
Restricted
Discussion Outline

Author | Department 2
YYYY-MM-DD Restricted © Siemens Energy, 2020
 Sequence of events: SFC Trip
17th of Dec. 2022 (01:07:06 AM)
1. During the start-up of unit 12 at
1:07:06 am, SFC was tripped at the
instant of starting of the washing
stage.
2. Infeed Circuit Breaker 1 feedback
signals not plausible had appeared
on HMI.

3. The feedback signals (closing &


opening ) of the Circuit Breaker of
the excitation system had been lost.
4. The Circuit Breaker of the excitation
is not responding to be racked out
due to the interlock mechanism
inside the breaker itself. 
5. the breaker was tested more than
times in case (Test mode &
connected mode), and all alarm
signals were gone.
Author | Department 3
YYYY-MM-DD Restricted © Siemens Energy, 2020
Alarms on HMI

 After troubleshooting and


tracking the event
sequence, it was observed
that:

1- the infeed Circuit breaker


opened signal was gone.

2- the infeed Circuit breaker


closed signal was gone.

Author | Department 4
YYYY-MM-DD Restricted © Siemens Energy, 2020
Alarms on HMI

3- After one second, the starting


frequency converter is prepared.

4- Because of the feedback circuit


breaker of the excitation system
does not identify the actual status
position of the breaker (closing or
opening signals), the excitation fault
(Chanel 1 & Chanel 2 ).

5- Starting Frequency Converter is


locked

Author | Department 5
YYYY-MM-DD Restricted © Siemens Energy, 2020
Trend 1 : Trip Case
 The Sequence of Signals :

1- The speed was decreased to


1.8 HZ.

2- Starting Frequency Converter Prepared


speed
will run the washing process Block
(prepared signal ).

3- Because of the circuit breaker


Excitation ON
can’t identify the actual status
position of the breaker, SFC is
Excitation Current
blocked.

Author | Department 6
YYYY-MM-DD Restricted © Siemens Energy, 2020
Trend 2: Healthy Case :
 The Sequence of Signals :

1- The speed was decreased to


1.8 HZ.
Prepared

2- Starting Frequency Converter


will be prepared for the process.
speed Block

3- The Excitation ON signal is


(Active ). Excitation ON Excitation Current

4- AVR will draw the excitation


current.

5- The SFC blocked Signal is not


found.

Author | Department 7
YYYY-MM-DD Restricted © Siemens Energy, 2020
Open-loop/closed-loop control channel 1
Connection cabinet +12CJT21
Digital inputs

 Infeed Circuit Breaker Status


( open & closed )

Closed signal

open signal
Author | Department 8
YYYY-MM-DD Restricted © Siemens Energy, 2020
ET 200 Module

 In the Trip case, the feedback


signal from the (open &
closed) position at Excitation
Circuit Breaker was not
reaching the controller
GA-K16-K03.

- Led 1 Closed Signal

- Led 5 Open Signal

Author | Department 9
YYYY-MM-DD Restricted © Siemens Energy, 2020
Infeed Circuit Breaker1

 In an opportunity outage:

1- Check on all terminals at (X5,


X6, and X7 ).

2-After tightening on all


terminals at (X5, X6 , X7 ),
check the signals on HMI.

CH1
CH2

Author | Department 10
YYYY-MM-DD Restricted © Siemens Energy, 2020
Excitation Circuit Breaker Signals connector

3- Check on the interlock


mechanism inside the breaker.

4-check on the excitation Circuit


Breaker in (Test mode & connected
mode ).

Author | Department 11
YYYY-MM-DD Restricted © Siemens Energy, 2020
Many thanks for your time!

Published by Siemens Energy


Nashaat Nasr
Mahmoud Mohamed
Senior EL maintenance ENG.
Egypt | Middle East | Operations and Maintenance
Al Burullus 4800MW CCPP
Mobile: +2 01278692724
Mobile: +2 01278692721
Nashaat.Nasr@siemens-energy.com
Mahmoud.Mohamed@siemes-energy.com

siemens-energy.com

Author | Department 12
YYYY-MM-DD Siemens Energy is a registered trademark licensed by Siemens AG. Restricted © Siemens Energy, 2020