Professional Documents
Culture Documents
BMS System Presentation
BMS System Presentation
MANAGEMENT
LEVEL(LEVEL#3)
BACnet / Ethernet IP
Salient features:-
32 bit microprocessor
Standalone controller
UL Listed
24MB to 80MB RAM
RANGE of DDC : There are mainly two series of DDC
controller depending upon the I/O arrangement one is fixed
controller & another expandable one. They are known as
Compact Series (Fixed type) & Modular Series (expandable
COMPACT
type) SERIES(Fixed Type) : By the name, it suggests
that this series can not extended beyond the assigned I/O
points..
1 PXC12.D/E.D
2 PXC22.D/E.D
3 PXC36.D/E.D
MODULAR SERIES(Expandable Type) : We can go with higher
no. of I/O in this series. This means we can add-on I/O modules
& integrate the program
1 PXC50.D/E.D
2 PXC100.D/E.D
3 PXC200.D/E.D
3rd PARTY INTEGRATORS :This range facilitate to integrate 3rd
part services with BMS. Example, PLC of any brand can be
brought & integrate to the BMS thru this 3rd party Integrator.
1 PXC00.U
2 PXC00.D/E.D
MANAGEMENT LEVEL # 3:
Level-3 It covers the final building management level window,
comprises of Software & hardware supervisory controllers.
SOFTWARE FOR BMS CONTROL SYSTEM-
Salient features:-
3 level password security
Automatic database save & restore
Alarm & Event log
System diagnostics
Backup of data/Program
Clock Synchronization
History records & Trend logging
Reports & logs etc.
NETWORK/SUPERVISORY CONTROL UNIT(BACnet Router) RANGE -
PXG3.L
PXG3.M
HAND HELD TERMINAL : This enable us to access any one DDC controller
to read, write and modify the parameters on a bus by plugging the POT in
the service port available in any one of the controller.
PXM20
PXM20-E
Display:
High resolution graphic display
(120 x 64 mm, 240 x 128 Pixel)
Sharp and exact texts with various big fonts
High brightness CFL back light
Adjustable display contrast
1 : BUILDING APPLICATIONS:
2 : INPUT-OUTPUT SUMMARY
3 : SYSTEM ARCHITECTURE
1. BUILDING
APPLICATIONS:
Water
Management
Air Filtration
DG System O2 System
System CO2 Removal
monitoring Replenishment System
System
2. INPUT-OUTPUT
SUMMARY:
S No SERVICE DESCRIPTION AI BI AO BO SUBTOTAL
A AIR COOLED CHILLERS & PUMPS(2+3sets) 20 56 0 30 106
B AHUs(Service area-05sets &Office area-09sets) 60 42 23 14 139
C AIR WASHER & SPRAY PUMPS(1+1set) 2 16 0 4 22
D VENTILATION BLOWERS(FAB-2+2sets & EAB-2+2sets) 28 100 16 88 232
E CO2 REMOVAL SYSTEM(1+1set) 70 142 14 64 290
F AIR FILTERATION SYSTEM(1+1set) 12 192 0 168 372
LAN
ETHERNET S/W BACnet / Ethernet IP
BACnet / LonTalk
ROUTER-1
------------- (OB)
DDC-01 DDC-02 DDC-03 DDC-08 --- ---
LIU --- M/C LIU --- M/C
A B
AREA
BACnet / LonTalk AREA
BACnet / LonTalk
ROUTER-2 --- --- ROUTER-1
------------- (O END) M/C --- LIU LIU --- M/C (1 END) -------------
--- ---
DDC-09 M/C --- LIU LIU --- M/C DDC-22