Professional Documents
Culture Documents
CG-428 - 04 Real Transformers
CG-428 - 04 Real Transformers
CG-428 - 04 Real Transformers
Mechanical Engineering
Unit 428
Lecturer
Mark Clements
Introduction - objectives
Transformer operation.
Transformer classification and types.
Modelling transformers.
Equivalent circuits.
Open and short circuit calculations.
Transformer ratings.
2 20/09/2023 C&G-428
Introduction
3 20/09/2023 C&G-428
Uses of transformers
4 20/09/2023 C&G-428
Transformer classification
Windings:
– Conventional transformers – two windings.
– Autotransformers – one winding.
– Others – more then two windings.
Phases:
– Single or three phase.
Step-type:
– Step-up where the primary is the low voltage LV winding.
– Step-down where the primary is the high voltage HV
winding.
5 20/09/2023 C&G-428
Types of transformer
Many types exist.
The most popular is the power transformer type.
Available in power ratings ranging from mW to MW.
The iron core is laminated to reduce losses due to
eddy currents.
Laminations are insulated from each other.
We will examine laminated core transformers
consisting of two windings interlinked by a mutual
magnetic field.
6 20/09/2023 C&G-428
Laminated iron core transformer diagram.
7 20/09/2023 C&G-428
Primary and secondary windings
8 20/09/2023 C&G-428
Ideal transformers
9 20/09/2023 C&G-428
Ideal transformer properties
10 20/09/2023 C&G-428
Key to abbreviations
11 20/09/2023 C&G-428
Phase angle in transformers
We measure apparent power (S) with our meters.
Need to use phase angle to calculate real power and
reactive power (Q).
12 20/09/2023 C&G-428
Phase angle for primary and secondary
13 20/09/2023 C&G-428
Load impedance
14 20/09/2023 C&G-428
Transforming load impedance
15 20/09/2023 C&G-428
Primary circuit impedance
16 20/09/2023 C&G-428
Primary circuit impedance
17 20/09/2023 C&G-428
Example 1
19 20/09/2023 C&G-428
Example 2 solution
20 20/09/2023 C&G-428
Real transformers – losses part 1
21 20/09/2023 C&G-428
Transformer equivalent circuit with
winding losses only
22 20/09/2023 C&G-428
Real transformers – losses part 2
24 20/09/2023 C&G-428
Transformer equivalent circuit
25 20/09/2023 C&G-428
Refer secondary impedances to the
primary
26 20/09/2023 C&G-428
Transformer equivalent circuit
referred to primary
27 20/09/2023 C&G-428
Determining component values
28 20/09/2023 C&G-428
Open-circuit test
This is carried out with the secondary winding of the
transformer open circuit.
The primary winding is supplied with line (or design)
voltage.
The series elements Rp and Xp are too small
(compared to Rc and Xm) to cause a significant
voltage drop.
Input voltage is therefore dropped only across the
excitation branch of the transformer.
29 20/09/2023 C&G-428
Open-circuit calculations
30 20/09/2023 C&G-428
Open-circuit test for PF
32 20/09/2023 C&G-428
Excitation branch calculations
Ic = Io cos q so Rc = Vp / Ic
Im = Io sin q so Xc = Vp / Im
Now we have values for Xm and Rc.
33 20/09/2023 C&G-428
Short-circuit test
In this test the secondary winding is short-circuited.
The voltage is adjusted until the secondary current
reaches the rated (design) current.
Input voltagesc, currentsc (both apparent) and input
(real) powersc are measured.
Excitation current is negligible since the input voltage
is very low.
Voltage drop is therefore due to the series elements
of the circuit.
34 20/09/2023 C&G-428
Short-circuit calculations
35 20/09/2023 C&G-428
Short-circuit test for PF
37 20/09/2023 C&G-428
Calculation continued
38 20/09/2023 C&G-428
Transformer losses
40 20/09/2023 C&G-428
Open-circuit testing schematic
41 20/09/2023 C&G-428
Equivalent model of open-circuit test
42 20/09/2023 C&G-428
Measured values in OC test
43 20/09/2023 C&G-428
Excitation branch calculations
Ic = Io cos q so Rc = Vp / Ic
Im = Io sin q so Xc = Vp / Im
45 20/09/2023 C&G-428
Equivalent model of short-circuit test
46 20/09/2023 C&G-428
Simplifying the model
48 20/09/2023 C&G-428
Measured quantities for results
49 20/09/2023 C&G-428
Further short-circuit calculations
Now short-circuit reactance can be calculated.
Equivalent leakage reactance (primary side) Xeq =
(Zeq2 – Req2).
Short-circuit power factor PF = Psc / (Vp x Ip).
Xeq and Req are now known.
Divide by k2 to obtain low voltage (lv) equivalent
values for Xeq(lv) and Req(lv).
These values can now be used in the equivalent
transformer model.
50 20/09/2023 C&G-428
Load tests
51 20/09/2023 C&G-428
Efficiency of transformer
52 20/09/2023 C&G-428
Notes on power losses in core
55 20/09/2023 C&G-428
Copper power losses
58 20/09/2023 C&G-428
Load test results
Capacitor Vp Vs Is Wp Ws
0 100V 47.8V 10.09A 550W 492W
150 mF 100.6V 49.4V 10.08V 560W 500W
230 mF 100.2V 50.3V 10.04V 550W 490W
310 mF 100.0V 51.4V 10.01V 532W 470W
59 20/09/2023 C&G-428
Maximum efficiency
60 20/09/2023 C&G-428