CG-428 - 04 Real Transformers

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 60

Electrical Principles for

Mechanical Engineering
Unit 428
Lecturer
Mark Clements
Introduction - objectives

 Transformer operation.
 Transformer classification and types.
 Modelling transformers.
 Equivalent circuits.
 Open and short circuit calculations.
 Transformer ratings.

2 20/09/2023 C&G-428
Introduction

 A transformer changes AC electric power at


one voltage level into AC electric power at a
different voltage level via the action of a
magnetic field.
 Two (or more) stationary electric circuits are
connected (coupled) magnetically.
 Electric energy is transferred between two
(or more) electrical systems.

3 20/09/2023 C&G-428
Uses of transformers

 Voltage and current levels are changed


easily.
 Can be used to step up voltage before power
transmission or for inverters.
 Can be used to step down transmission
voltage for further distribution or utilization.

4 20/09/2023 C&G-428
Transformer classification
 Windings:
– Conventional transformers – two windings.
– Autotransformers – one winding.
– Others – more then two windings.
 Phases:
– Single or three phase.
 Step-type:
– Step-up where the primary is the low voltage LV winding.
– Step-down where the primary is the high voltage HV
winding.

5 20/09/2023 C&G-428
Types of transformer
 Many types exist.
 The most popular is the power transformer type.
 Available in power ratings ranging from mW to MW.
 The iron core is laminated to reduce losses due to
eddy currents.
 Laminations are insulated from each other.
 We will examine laminated core transformers
consisting of two windings interlinked by a mutual
magnetic field.

6 20/09/2023 C&G-428
 Laminated iron core transformer diagram.

7 20/09/2023 C&G-428
Primary and secondary windings

 The primary winding is energised by


connecting it to an AC input source.
 The secondary winding supplies energy to
the electrical load.
 The mutual magnetic field transfers the
electrical energy.

8 20/09/2023 C&G-428
Ideal transformers

 These are lossless devices with the following


properties:
 No iron or copper losses.
 No leakage fluxes.
 A core with infinite magnetic permeability and
infinite electrical resistivity.
 Magnetic flux is confined to the core and winding
resistances are negligible.

9 20/09/2023 C&G-428
Ideal transformer properties

 In an ideal transformer with no losses the


relationship between input voltage and
current and output voltage and current is
described below:

10 20/09/2023 C&G-428
Key to abbreviations

 All quantities are AC.

11 20/09/2023 C&G-428
Phase angle in transformers
 We measure apparent power (S) with our meters.
 Need to use phase angle to calculate real power and
reactive power (Q).

12 20/09/2023 C&G-428
Phase angle for primary and secondary

 The phase angle measured from the primary


side of the transformer is the same as the
phase angle for the secondary side of the
transformer.

13 20/09/2023 C&G-428
Load impedance

 The impedance of the load can be calculated


by dividing the secondary voltage by the
secondary current.

14 20/09/2023 C&G-428
Transforming load impedance

 Load impedance is on the secondary


winding.
 It is useful to be able to transfer this
impedance to the primary winding for
calculations.
 The prime (`) symbol represents the
secondary load as seen by the primary
winding and is written as Z`L.

15 20/09/2023 C&G-428
Primary circuit impedance

 The load is transferred to the primary as Z`L.

16 20/09/2023 C&G-428
Primary circuit impedance

17 20/09/2023 C&G-428
Example 1

 A step-down transformer is designed to give


a 24 volt AC output for a 240 V AC input. The
impedance of the load ZL is 35 ohms. What is
this impedance (Z`L) transformed to the
primary?
 k = Vp / Vs = 240/24 = 10.
 k2 = 10 x 10 = 100.
 Z`L = k2ZL = 100 x 35 = 3500 W.
18 20/09/2023 C&G-428
Example 2
 An ideal 100 kVA, 2400/240 V, step-down transformer
is used between a transmission line and a distribution
system. Remember: power in = power out.
1. Determine the turns ratio, k.
2. What value of secondary load impedance will cause
the transformer to be fully loaded?
3. What is the primary current with this load?
4. What is the load impedance referred to the primary?

19 20/09/2023 C&G-428
Example 2 solution

1. Turns ratio k = 2400/240 = 10.


2. Is (max) = Power / Vs. = 100000 / 240 =
416.7 A. Magnitude of load impedance =
Vs / Is = 240 / 416.7 = 0.576 W.
3. Ip = Is / k = 416.7 / 10 = 41.67 A.
4. Load impedance referred to the primary
Z`L = k2 x 0.576 = 57.6 W.

20 20/09/2023 C&G-428
Real transformers – losses part 1

 In real transformers there are losses due to


the primary and secondary windings having
resistance and reactance.
 These are denoted in the diagrams as Rp
and Xp in the primary windings and Rs and Xs
in the secondary windings.
 They appear in series with the current paths.

21 20/09/2023 C&G-428
Transformer equivalent circuit with
winding losses only

22 20/09/2023 C&G-428
Real transformers – losses part 2

 Other losses occur due to the magnetizing


branch of the transformer model.
 These are core or iron losses, Rc and
magnetizing reactance, Xm.
 The current flowing through these is known
as the magnetizing branch current, Io.
 These are placed in parallel with the primary
winding.
23 20/09/2023 C&G-428
Transformer equivalent circuit

 An equivalent circuit for a transformer can


now be drawn that shows current losses due
to the core (iron) losses and the magnetizing
reactance.

24 20/09/2023 C&G-428
Transformer equivalent circuit

25 20/09/2023 C&G-428
Refer secondary impedances to the
primary

 Recall that secondary impedances can be


transferred to the primary side of the
transformer.
 This is done by multiplying all impedances by
k2 and redrawing them on the primary side of
the transformer and appointing these
quantities the prime (`) symbol.

26 20/09/2023 C&G-428
Transformer equivalent circuit
referred to primary

27 20/09/2023 C&G-428
Determining component values

 The values of the components shown in the


equivalent circuit can be experimentally
determined using two tests.
 Open-circuit test.
 Short-circuit test.

28 20/09/2023 C&G-428
Open-circuit test
 This is carried out with the secondary winding of the
transformer open circuit.
 The primary winding is supplied with line (or design)
voltage.
 The series elements Rp and Xp are too small
(compared to Rc and Xm) to cause a significant
voltage drop.
 Input voltage is therefore dropped only across the
excitation branch of the transformer.

29 20/09/2023 C&G-428
Open-circuit calculations

 As all the voltage drop can be attributed to


the excitation branch, the values of Xm and Rc
can now be calculated.
 The first item to calculate is the power factor,
PF = q.
 This is the ratio of real power to apparent
power.

30 20/09/2023 C&G-428
Open-circuit test for PF

 Input apparent voltageoc, apparent currentoc


and real poweroc are measured.
 Open-circuit power factor can now be
calculated.
 Apparent poweroc = Apparent voltageoc x
apparent currentoc.
 PF = cos q = Real power/ apparent power =
Poc / (Voc x Ioc)
31 20/09/2023 C&G-428
Calculations

 Knowledge of q allows calculation of Ic and Im.

32 20/09/2023 C&G-428
Excitation branch calculations

 Ic = Io cos q so Rc = Vp / Ic
 Im = Io sin q so Xc = Vp / Im

 Now we have values for Xm and Rc.

33 20/09/2023 C&G-428
Short-circuit test
 In this test the secondary winding is short-circuited.
 The voltage is adjusted until the secondary current
reaches the rated (design) current.
 Input voltagesc, currentsc (both apparent) and input
(real) powersc are measured.
 Excitation current is negligible since the input voltage
is very low.
 Voltage drop is therefore due to the series elements
of the circuit.

34 20/09/2023 C&G-428
Short-circuit calculations

 As all the voltage drop can be attributed to


the total series impedances, the series
impedance can now be calculated.
 The first item to calculate is the power factor,
PF = q.
 This is the ratio of real power to apparent
power.

35 20/09/2023 C&G-428
Short-circuit test for PF

 Input apparent voltagesc, apparent currentsc


and real powersc are measured.
 Short-circuit power factor can now be
calculated.
 Apparent powersc = Apparent voltagesc x
apparent currentsc.
 PF = cos q = Real power/ apparent power =
Psc / (Vsc x Isc)
36 20/09/2023 C&G-428
Calculations

 For the short-circuit test, total series


impedance is Zsc.
 Zsc = Vsc / Isc
 Resistance of the transformer R is given by
dividing the short-circuit power by the short
circuit current.
 R = Psc / Isc.

37 20/09/2023 C&G-428
Calculation continued

 With knowledge of the transformer’s total


resistance, its impedance can be calculated.

 We now have the copper losses of the


transformer and approximate equivalent
resistance and reactance.

38 20/09/2023 C&G-428
Transformer losses

 The tests carried out show that the copper


losses of a transformer are dependant on
current.
 The iron losses of the transformer are
dependent on voltage.
 Total transformer losses are dependent on
volts and amperes, volt-ampere (VA).
 This is why transformers are rated in kVA.
39 20/09/2023 C&G-428
Open-circuit testing

 Carried out to determine the no-load losses or


iron (core) losses.
 No current flows in the secondary windings so
the primary winding current is ignored.
 Current flowing (Io) is in the excitation branch of
the transformer known as the no-load current.
 No-load current is typically 2 – 10% of the rated
full-load current.

40 20/09/2023 C&G-428
Open-circuit testing schematic

41 20/09/2023 C&G-428
Equivalent model of open-circuit test

42 20/09/2023 C&G-428
Measured values in OC test

 Primary voltage (Vp) and current (Ip) (AC) and


real power Poc consumed.
 Allows OC phase angle q to be calculated.
 q = Real power/ apparent power
= Poc / (Vp x Ip)

43 20/09/2023 C&G-428
Excitation branch calculations

 Ic = Io cos q so Rc = Vp / Ic
 Im = Io sin q so Xc = Vp / Im

 Now we have values for Xm


and Rc.
 These values can be
added to the transformer
model.
44 20/09/2023 C&G-428
Short-circuit testing
 Carried out to determine the copper losses at full load.
 Actually measures the equivalent impedance of the
transformer’s primary AND secondary windings
together.
 In practice the primary winding voltage is low, about 5
to 10% of the normal rated voltage.
 In this case Ic is then also small and so is ignored.
 The wattmeter therefore is mainly measuring the
winding (copper) power loss (I2R).

45 20/09/2023 C&G-428
Equivalent model of short-circuit test

46 20/09/2023 C&G-428
Simplifying the model

 Rp and Xp are the primary winding resistance and


reactance.
 Rs and Xs are the secondary winding resistance and
reactance.
 These can be modelled by an equivalent impedance Zeq,
composed of the series resistances (Rp and Rs) and
reactances (Xp and Xs).
 Zeq = Req plus Xeq.
 All impedance is “as seen” from the primary winding.
47 20/09/2023 C&G-428
Simplified short-circuit test model

48 20/09/2023 C&G-428
Measured quantities for results

 Wattmeter measures the real power loss (Psc)


due to resistance only.
 Ip and Vp are the AC primary measurements.
 All calculations are as referred to the primary
side of the transformer.
 Equivalent resistance Req = Psc / Ip2
 Equivalent impedance Zeq = Vsc / Isc

49 20/09/2023 C&G-428
Further short-circuit calculations
 Now short-circuit reactance can be calculated.
 Equivalent leakage reactance (primary side) Xeq =
(Zeq2 – Req2).
 Short-circuit power factor PF = Psc / (Vp x Ip).
 Xeq and Req are now known.
 Divide by k2 to obtain low voltage (lv) equivalent
values for Xeq(lv) and Req(lv).
 These values can now be used in the equivalent
transformer model.
50 20/09/2023 C&G-428
Load tests

 Testing the transformer under load conditions


allows the efficiency to be calculated.
 A resistor and a capacitor are used as the
loads on the secondary side of the
transformer.

51 20/09/2023 C&G-428
Efficiency of transformer

 Real transformers have copper and core


power losses, dissipated as heat.
 These are iron (Pi) and copper (Pc) losses.
 Power output = power input – losses.
 Power input = power output + iron losses +
copper losses.

52 20/09/2023 C&G-428
Notes on power losses in core

 The core loss Pi remains constant from no load


to full load as the flux in the core remains
constant.
 Copper losses Pc are dependent upon the
square of the current and the resistance of the
primary and secondary windings (I2R) .
 Thus copper losses increase as the square of
the current and iron losses remain constant
regardless of the load.
53 20/09/2023 C&G-428
Terms used when calculating efficiency

 Vs – Secondary terminal voltage.


 Is – Full load secondary current.
 Cosqs – power factor of the load.
 Req(lv) – equivalent resistance referred to
secondary winding (low voltage).
 Pi – Iron losses = hysteresis losses + eddy
current losses.
 Pc – Full load copper losses = Is2Req(lv).
54 20/09/2023 C&G-428
Calculating efficiency
 Efficiency, η = Power output / Power input.
 η = Power output / (Power output + iron losses +
copper losses).
 η = Vs Is cosqs / (Vs Is cosqs + Pi + Pc).
 cosqs = Ws / (Vs x Is).
 You will need the results of the open and short-circuit
tests to supply resistance values to allow Pi & Pc to
be calculated.

55 20/09/2023 C&G-428
Copper power losses

 Pc – Full load copper losses = Is2Req(lv).


 From SC test, you have a value for Req(lv).
 My average value for Req(lv) was 0.255W.
 Current in secondary was measured in load test
as Is. (see Load test results)
 Calculate the 4 values of Pc using the formula
above.
 My results were approx 25W.
56 20/09/2023 C&G-428
Iron power losses

 Pi – Iron losses = hysteresis losses + eddy current


losses.
 Core resistance calculated in OC tests as Rc.
 Power lost Pi = Vp2 / Rc.
 My average value for Rc was 330W.
 Voltage across primary was measured in load test as
Vp. (see Load test results)
 Calculate the 4 Pi values using the formula above.
 My results were approx 330W.
57 20/09/2023 C&G-428
Measuring efficiency

 In load tests, two wattmeters are used, one on


the primary (Wp), one on the secondary (Ws), so
the power dissipated can be directly measured.
 Actual efficiency, η = Wp / Ws.
 Typical results for load tests using a resistor and
a set of capacitors are shown on next slide.

58 20/09/2023 C&G-428
Load test results

Capacitor Vp Vs Is Wp Ws
0 100V 47.8V 10.09A 550W 492W
150 mF 100.6V 49.4V 10.08V 560W 500W
230 mF 100.2V 50.3V 10.04V 550W 490W
310 mF 100.0V 51.4V 10.01V 532W 470W

59 20/09/2023 C&G-428
Maximum efficiency

 The efficiency of a transformer will be


maximum when the copper or variable losses
are equal to iron or constant losses.
 η = Vs Is cosqs / (Vs Is cosqs + 2Pi ).

60 20/09/2023 C&G-428

You might also like