Invensys Triconex

Tricon – Trident – TS1131

por Marcio Razera - Invensys/Triconex

Process Systems

Get More from One


Avantis • Foxboro • SimSci-Esscor • Triconex
Process Systems

Invensys Process System

Invensys Confidential 2
Invensys Process Systems
Process Systems

INVENSYS, plc

APV Process Eurotherm Rail Systems Controls


Systems

Consultoria em Segurança Sistemas de Segurança Segurança em Turbo-Máquinas

Invensys Confidential 3
Invensys Value Proposition
Process Systems

“At Invensys Process Systems, everything we do


improves our customers’ return from their
production assets.

We do this by balancing the availability and


utilization of their people, equipment, energy, and
inventories.”

Invensys Confidential 4
Triconex Value Proposition
Process Systems

As part of Invensys Process Systems, everything Triconex


does improves our customer’s return from their production
assets.
We do this by:
Preserving the availability of their plant assets enabling
asset utilization, without compromising safety

Invensys Confidential 5
Business Update
Process Systems

Modules shipped Triconex Growth – 1991 – 2006


30000
250
25000
200
20000
US$ 150
15000
100
10000
50
5000
0
0
2002 2003 2004 2005 2006

Source of data: ARC, Triconex internal

Invensys Confidential 6
Base Instalada Triconex - Brasil
Process Systems
PETROBRAS PETROBRAS
REMAN ( 3 ) LUBNOR (1 )

PETROBRAS MONSANTO (1) DOW (1)


RLAM ( 8 )
RR
PETROBRAS AP ELEKEIROZ (1 )
FAFEN( 1 )

OXITENO NE (1 )
PETROBRAS
REGAP ( 7 ) PA
AM MA
CE
POLITENO (1)
PETROBRAS RN
REDUC (11) PB
PI
PE
BRASKEM (5)
PETROBRAS TO AL
RO SE
RECAP ( 1 )
BA BSC (4)
MT
GO
PETROBRAS
REPLAN (10)
DF MG
ARACRUZ (1 )

PETROBRAS
ES CST (1)
REVAP (11)
MS
SP BAYER (1)
RJ
PETROBRAS
REPAR (5) PR CABIUNAS (1)

SC POLIETILENOS (1)
PETROBRAS
SIX (1) RS
COSIPA (1)

PETROBRAS SOLVAY (9)


REFAP (10 )
VCP (2)

PETROBRAS OPP (5) COPESUL (11) GERASUL(5) FOSFERTIL(1) RHODIA (1 ) OXITENO(1) SHELL(1) PQU (3)
INNOVA (2)
PERÓXIDOS(1) DEGUSSA(1)

Invensys Confidential 7
Reader’s Process Systems
Choice Award

Triconex recebeu
pelo nono ano
consecutivo o
reconhecimento
pelos leitores da
revista Control
Magazine como o
melhor fabricante
de safety and
emergency
shutdown
systems para as Editor’s Choice Award
Triconex’s Trident fault-tolerant control system
indústrias de has been honored by Control Engineering
magazine with an Editor’s Choice award. The
automação de award recognizes products deemed as the most
significant innovations featured in Control
processo Engineering during 2004.

Invensys Confidential 8
Process Systems

SIS Market Trends

Invensys Confidential 9
Process Systems
Desafios do Mercado Atual

Visão Histórica Desafio Atual


’70s –inicio ’90sfinal ’90s - inicio 2000’s 2005 ….

Meta
Produção Otimização Processo Otimização do Negócio
Corporativa

oco Eficiência da Operação Eficiência da Engenharia Eficiência da Planta

vadores  Crescimento Econômico  Pressão Custo  Recuperação Economica


nomicos  Tecnologia/Inovações  Além da Capacidade  Além da Capacidade
 Aquém da Capacidade  Globalização  Globalização mais intensa
 Demanda do Cliente  Requerimentos Internacionais  Aumento dos requerimentos internacionais
 Aumento da Velocidade dos Negócios
 Diminuição do tempo de tomada de decisões
 Tempos maiores de produção sem paradas

2004

Invensys Confidential 10
Process Systems
Desafios do Mercado Atual - SIS

Desafio Atual Desafio Atual - SIS Desafio Atual - SIS

2005 …. 2005 …. 2005 ….

Otimização do Negócio Otimização do Negócio Padrões Internacionais

Eficiência da Planta Eficiência da Planta IEC61508 / IEC61511

 Recuperação Economica  Maior Disponibilidade  Risco x Consequência x Probabilidade

 Além da Capacidade  Campanhas de produção maiores  Nivel de Integridade ( SIL )

 Globalização mais intensa  Maior tempo de intervalo entre testes  Probabilidade Falha em Demanda

 Aumento dos requerimentos internacionais  Maior Necessidade de Diagnósticos  Separação

 Aumento da Velocidade dos Negócios  Facilidades de Manutenção  Diversidade

 Diminuição do tempo de tomada de decisões  Atendimento aos Padrões Internacionais  Fator Humano

 Tempos maiores de produção sem paradas  Degradação


 Minimum Hardware Fault Tolerant (MHFT)

2004

Invensys Confidential 11
Process Systems

Solução SIS Invensys

Invensys Confidential 12
Muito mais do que somente o SIL
Process Systems

Invensys Confidential 13
Core Competencies
Process Systems

 Certificados  SIL 3 é APENAS o começo


– IEC 61508
– IEC 61131-2
– IEC 61000-4-2, 3, 4, 5
– NFPA 72/96 (F&G)
– NFPA 8501/97 (BMS)
– NFPA 8502/99 (BMS)
– US NRC Nuclear 1E
– Relatório de Restrições Operacionais
 Maximum Process Uptime – Considerações de Segurança

 Fault Tolerant
– Operação mesmo com multiplas falhas
– Manutenção On-line
– Baixa susceptibilidade à espúrios
– Diagnóstico On-Line
– SEM RESTRIÇÔES

 Capacidade de Execução  TUV FS Certified Engineers


– Disponivel mundialmente

Invensys Confidential 14
internet Process Systems

TRICON
de
¨Triconex¨
1

2a
2b

5 4

2 Invensys Confidential 15
1
¨Certificado TUV¨ Process Systems

(Safety Consideration Guide )

Relatório de Restrições Operacionais é


uma parte integral do certificado

Invensys Confidential 16
Invensys SIS - Soluções Process Systems

Trisim/Dysim TS1131 Avantis

Tricon Trident

L L
F
F F

L L P
TMR -SOV T
T
F L F
L

Instrumentos / Posicionadores SIL2/3


Invensys Confidential 17
Invensys SIS - Produtos Process Systems

Serviços
• Project Engineering • Safety Consulting
• Field Services • Training

Software
• Tristation 1131 • DDE Server
• TriLogger • OPC Server (Matrikon)

Hardware Plataformas

TMR Simplex TMC

Invensys Confidential 18
Invensys SIS - Produtos Process Systems

 Duas Plataformas - Tricon e Trident


 Plataforma única de configuração

TRICON TRIDENT

Pontos de E/S 48 - 2.500  48 - 600


Tipos de E/S Todos os Tipos DI, DO, AI, AO, PI

Tipos de Sinal Todos os Tipos 24VCC


Ambiente Sala de Controle, Flexível
Armários tipo “Rittal”
Modularidade  Por chassis  Por baseplate
Invensys Confidential 19
Invensys SIS - Produtos Process Systems

TRIDENT TRICON

Invensys Confidential 20
Comunicações Process Systems

Peer to Peer

TriStation 1131 OPC or


Diagnostic Monitor BPCS
TriLogger, Others

TriStation 1131 Modbus TCP or Modbus Serial


Master/Slave

Invensys Confidential 21
Invensys SIS - Serviços Process Systems

Project Flow
Site Assessm ent or SIL Determ ination
Inspe ction of existin g S IS & docum entatio n
R eco m m endatio n of Im provem ents

SIL Determination
System Requirem ent Specification
D efine S IS requirem ents (functional, integrity levels)

Premier SIL Validation


Conceptual Design & SIL Validation
Consulting D esign to m eet target S IL ensures com plian ce w ith

Services A N S I/IS A S 84.01, IE C -61508 , O S H A , E P A , N F P A ...


D o cum entation of s ystem co nfiguration, I/O , fie ld
equipm ent, redundancy, startu p/shutdow n /s afety
logic definition, etc.

Conceptual Design to Client


for Approval Corporate
Detailed Design Guidelines
Im ple m entation o f C onceptu al D esig n, logic diagram s ,
final engineering decision s on hardw are, operator and
interface design s, requirem ents for tes ting, field
equipm en t installations, etc. Industry
Standards
SIS Im plem entation W ork
F ield w ork , program T ricon, w rite F A T a nd S A T
EPC proc edures , ass em b le sys tem , perform F A T

Com m issioning
S IS installation, training , S A T , s tartup, on-line ...

Premier
Consulting Docum entation
O perator and M ainten ance P rocedures , O n-
Services Line/o ff-Line T est P roc edures , M O C

pcs_flow .vsd

Invensys Confidential 22
Invensys SIS - Serviços Process Systems

 A Invensys Brasil trabalha 1 Site Assessment 6 Projeto Básico

em todo o ciclo de vida de


um projeto de segurança , Competence 7
Projeto
garantindo assim que todas 2 Assessment
Detalhamento

as fases serão executadas e


Hazop/ SIF Review/
baseadas nas melhores 3 SIL Assign 8
Fornecimento
TMR
práticas de engenharia e nas
normas internacionais.
Especificação dos
Supervisão
4 Requerimentos 9 de Montagem
De Segurança
,

Instalação
SIF Device 10 Comissionamento
5 Selection
,
11 Start Up

Operação
12 e Manutenção

Invensys Confidential 23
Process Systems

Mercado & Triconex & Padrões

Invensys Confidential 25
Process Systems

Arquitetura TMR – Triple Modular Redundancy

Invensys Confidential 26
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

2oo3 = Continua operando

Set Point de Alta Pressão

Variável de Processo
Certamente esse sinal
de Alta é um sinal Ruim

Tempo
Config 1oo2 = Shut down 2oo3 = Shut Down
Variável de Processo

Variável de Processo
Set Point de Alta Pressão Set Point de Alta Pressão

Certamente esses sinais

Qual dos sinais ? de Alta são sinais Bons

É o Correto ?

Certamente esse sinal


de Alta é um sinal Ruim

Tempo Tempo
Invensys Confidential 27
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Autospare Autospare

I/O Bus Processador


Leg
Leg Principal
de
de A
Entrada
Saída A
A A.B A
A
Tribus Tribus

Leg
Leg Processador I/O Bus
Principal de
de Saída
B
Entrada B
B
C B
Tribus

Processador Leg
Leg Principal
de de
I/O Bus C
Entrada Saída
B Loopback
C

Módulo de Entrada Módulo de Saída

Invensys Confidential 28
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

 Há dois componentes importantes de software em Cada Processador


Principal do Tricon / Trident, cada um rodando em um Processador
Motorola MPC860 PowerQUICC™ dedicado

– LSX – Executivo do Sistema Trident, responsável pela execução do programa de controle


descarregado pelo software de configuração ( TS 1131 )

– LIOX – Executivo de Entradas/Saídas do Trident, responsável pela comunicação com os


Módulos de E/S do Trident

 Há sempre Três Processadores Principais em um Sistema Tricon /


Trident

Invensys Confidential 30
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

 O firmware LSX é executado em uma CPU MPC860 de 50 MHz


localizada em cada um dos Três Processadores Principais Trident e
efetua as seguintes funções.

– Inicialização do Sistema, sincronização de tempo,


recuperação de erros, votação e controle

– Comunica com os outros membros


da Tríade de Processadores Principais via TriBus

– Execução de programa de controle do Usuário


MPC380
– Controle das E/S locais e remotas

– Comunica com a Estação de Programação TriStation 1131

– Interface aos Módulos Opcionais de Comunicação Local

– Execução de Diagnósticos do Sistema On-Line

Invensys Confidential 31
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

O LSX Vota Todas as Entradas antes de Enviar ao Programa de Controle

Modo de Número de Votação Votação


Operação Pernas Discreta Analógica
Operando

Modo TMR 3 2-de-3 Valor do Meio

Modo Dual 2 2-de-2 Média

Modo Simplex 1 1-de-1 1-de-1

Segurança 0 Desenergizado Não Aplicável

Invensys Confidential 32
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

 O firmware do LIOX roda em uma CPU MPC860 de 50 MHz localizada em cada


um dos Três Processadores Principais Trident e executa as seguintes funções:
– O LIOX é responsável por manter todas informações
sobre os Módulos de E/S e roda todos os diagnósticos
que sejam necessários
– Implementa a lógica necessária ao controle de
todos os Módulos de E/S
– Transfere dados de Entradas e Saídas

– Executa runtime Diagnósticos de E/S

– Se comunica com o LSX


Processador
Principal
 Cada um dos Três Processadores Principais LIOX se Trident
comunica com seu respectivo LSX via Memória compartilhada
– O LIOX lê os Módulos de Entrada e passa os valores para o LSX através da Memória
compartilhada
– O LSX envia as Saídas para o LIOX através da Memória compartilhada

Invensys Confidential 33
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Até agora vimos os componentes de cada Processador Principal


Trident …

Processador
Principal
Trident

… mas como é que o Processador Principal se comunica


com os Módulos de E/S do Trident?

Invensys Confidential 34
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

 O Barrramento LIO define a comunicação entre o LIOX do Processador


Principal Trident’s e os Módulos de E/S do Trident

ASICs Application Specific Integrated Circuits

 O protocolo é serial, síncrono, full-duplex, Ponto-a-Ponto High-Level Data-


Link Control (HDLC) implementado através dos ASICs
 Opera a 2 Mbit/seg

 As mensagens são multi-threaded (o reconhecimento das mensagens não


é requerido antes da transmissão da mensagen seguinte)

Invensys Confidential 35
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Perna A do Trident

No Trident o caminho das Entradas até as Saídas é referido como


Perna…

Invensys Confidential 36
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Pernas A, B e C do Trident

… e no Trident há Três Pernas idênticas, isoladas.

Invensys Confidential 37
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Perna Perna US Perna DS


O Tribus Opera @ 4
Mbytes/segundo ! A C B

B A C

C B A

• O TriBus usa caminhos de comunicação Upstream e Downstream


• A interface do TriBus é usada para a troca de informação entre os Processadores
Principais e comparar todos os dados recebidos
• Os Dados devem ser votados e todas as discrepâncias corrigidas usando o
critério de maioria
• Tranferências sem perturbação ao processo de transições 3 para 2 e de 2 para 3,
de 2 para 1 e de 1 para 2 são GARANTIDAS!
Invensys Confidential 38
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Pernas A, B e C do Trident

• As Pernas LIO são conectadas entre si por meio de um


Diagnóstico de Barrramento separado, serial, usando o
protocolo HDLC a 3.1 Mbytes/segundo
• Usa Diagnósticos Loopback para mensagens de Integridade

Invensys Confidential 39
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Conecta os Circuítos de Entradas e Saídas dos Módulos até os ASIC’s


e a Arquitetura está completa!

Invensys Confidential 40
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

O Processo Requer Maior Disponibilidade?


Adicione a Opção de Módulos Hot Spare!
O Controle é Transferido sem Perturbação no Evento
de uma Falha no Módulo Primário
Operação de E/S nos Modos 3-3-2-1-0 !

Invensys Confidential 41
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Entrada Digital
FIELD CIRCUITRY -- TYPICAL POINT (1 of 32) INTELLIGENT I/O CONTROLLER(S) TRIPLICATED
I/O BUS

AC/DC Input Circuit Individual Opto-Isolation Intelligent I/O Controller(s)

- +
Input A
Threshold Detect  Proc Bus
Opto-Isolator Mux Xcvr
Individual Point Field Termination

Opto-
Isolator Dual
Port
RAM

- +
Input B
Threshold Detect  Proc Bus
Opto-Isolator Mux Xcvr

Opto-
Isolator Dual
Leg-to-Leg Port
Bridge RAM
Isolation
Rectifier AC Optical
Isolation
- + Smoothing
Input Bus C
Threshold Detect  Proc
Opto-Isolator Mux Xcvr

Opto-
Isolator Dual
Control Signal Port
RAM

Invensys Confidential 42
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Entrada Analógica

Analógica Entradas Circuito -- Sinal INDIVIDUAL ACC INTELLIGENT Triplicadas


Típico Ponto Condicionamento para Cada Perna E/S Controlador(S) Barramento E/S

Bus A
Amp ACC  Proc Xcvr

Isolação/ Hi Ref
Mux
Field Terminaçãos

Filtering
Individual Ponto

Lo Ref

Bus B
Amp ACC  Proc Xcvr

Hi Ref
Mux
Lo Ref

Bus C
Amp ACC  Proc
Xcvr

Hi Ref
Mux
Lo Ref

Invensys Confidential 43
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Saida Digital
TRIPLICATED
I/O BUS INTELLIGENT I/O CONTROLLER(S) FIELD CIRCUITRY -- TYPICAL POINT (16)

A
A Bus
Bus Point
Point Output
Proc
Proc
Xcvr
Xcvr Register
Register Switch
Drive
Circuitry +V

A•B
* *
A B
Output
Switch
Drive
B Bus
Bus Point
Point Circuitry
Proc
Proc
Xcvr
Xcvr Register
Register

B
Output
Switch
Drive
Circuitry
* *
C A•B
C Bus
Bus Proc
Point
Point
Xcvr Proc Register
Xcvr Register
C LD
Output
Switch
Drive
Circuitry
A Voltage
B Loopback
C RTN
Detector
* All output switches are opto-isolated.

Invensys Confidential 44
Disponibilidade = Arquitetura 2oo3 = TMR Process Systems

Saida Analógica
TRIPLICATED INTELLIGENT I/O CONTROLLERS SIGNAL CONDITIONING PER POINT
I/O BUS

A  Proc Selector
A Logic

DAC
Voltage Loopback
Current Loopback

B  Proc Selector
B Logic

DAC
Voltage Loopback
Current Loopback
Output
C Proc Selector Termination
C Logic

DAC
Voltage Loopback
Current Loopback

Invensys Confidential 45
Process Systems

Project Security

Invensys Confidential 46
Process Systems

Project History

Invensys Confidential 47
Process Systems

Project Reports

Invensys Confidential 48
Process Systems

Back Up Project

Invensys Confidential 49
Process Systems

Programação On Line – Emulação

Invensys Confidential 50
Maior Campanha de Produção Process Systems

= Programação Online

 Download ALL
 Download Change

Invensys Confidential 51
Process Systems

Invensys Confidential 52 I
Process Systems

Invensys Confidential 53 I
Process Systems

Invensys Confidential 54 I
Process Systems

Invensys Confidential 55 I
Process Systems

Invensys Confidential 56 I
Process Systems

Invensys Confidential 57 X
Process Systems

Download History

Invensys Confidential 58
Process Systems

Manutenção On Line

Invensys Confidential 59
Maior Campanha de Produção Process Systems

= Manutenção Online
ELCO Connectors for I/O Termination

Power
Terminal Terminal Strip
Strip
#1

1 2 3 4 5 6
Terminal
Strip
#2
TRIBUS

Power
Supply
#1

DUAL
POWER
RAILS

Power Leg A
Supply
Leg B
Comm
#2
Leg C
Bus

Leg A
Leg B
I/O
Leg C
Bus

Right I/O Module*


Main
Processors One Logical Slot
Left I/O Module
A, B, & C
Communication Module

* Either the left module or right module functions as


the active or hot spare module at any particular time.

Invensys Confidential 60
Maior Campanha de Produção Process Systems

= Manutenção Online

Invensys Confidential 61
Process Systems

Tolerância à Falhas & Diagnósticos

Invensys Confidential 62
Maior Campanha de Produção Process Systems

= Tolerância à Falhas

Capacidade do sistema operar por um


determinado periodo de tempo em falha
porém sem comprometer o processo

Não existência de ponto de falha comum

O Trident é Certificado e Pode Detectar Todas


as Falhas Relacionadas à Segurança em 500
mS
Triconex - Full TMR Architecture
O Sistema é certificado TUV para Operar com
Até 64 Falhas em um Único Módulo!

 Response of System faults

“Triple-Modular Redundant (TMR) architecture ensures fault tolerance and


provides error-free, uninterrupted control in the event of single faults and
most of multiple hardware faults of components or transient faults from
internal or external sources”Source: TUV Report to Certification Report-No.: 968/EZ 101.01/02
Date: 2002-03-12

Invensys Confidential 63
Maior Campanha de Produção Process Systems

= Tolerância à Falhas
Nuisance TÜV Time
TÜV Approved TÜV Class Trip Rate Restrictions after
Configuration Operating Mode Approval for Fault Detection
w/Restrictions* Safety High | Low (Degraded )

1oo2 2-0 AK 5 AK6  N/A Certified


3-2-1-0
Mode of Operation!
2oo2 Not Approved Not Approved  N/A
Unrestricted
1oo2D/2oo4D 2-1-0 AK5  72 Hours / Operation in
Dual Mode!
Immediate (note
1)
1oo2D 2-0 AK6  Immediate /
1 Hour (note 2)
2oo4D 2-0 AK 5 AK6  Fail Safe
3-2-1-0 AK5 Dual Mode - Unrestricted
2oo3D Triconex  Single Mode - 72 hs

2oo3D Triconex 3-2-0 AK6  Dual Mode - Unrestricted


Single Mode - 1 h

(1) Max 72 Hrs upon diagnosed fault. Any miscompare requires immediate shutdown
(2) Immediate shutdown upon diagnosed fault or miscompare. AK6 does not allow operation on single
channel. One hour if immediate shutdown is dangerous.
Invensys Confidential 64
Maior Tempo de Intervalo entre testes Process Systems

= Diagnósticos
 Como os Módulos de E/S do Sistema Utilizam HDLC via ASICs, ao invés de
Microprocessadores, a Cobertura de Diagnósticos é Aumentada Até a
Percentagem Mais Elevada Reconhecida pela IEC 61508

Pela IEC:
– Referência de Diagnósticos por Perna Baseada em Microprocessadores
 Cobertura de Diagnóstico Máxima de 90%
– Diagnósticos de Comparação Perna-a-Perna Baseada em Microprocessador
 Cobertura de Diagnóstico Máxima de 99%
– Diagnósticos Gerais de Lógica (incluindo FPGAs)
 Cobertura de Diagnósticos para Referência 99.0%
 Cobertura de Diagnósticos para Comparação 99.9%

É por esse motivo que o Trident/Tricon tem certificação TUV para Funções de
Segurança
mesmo operando com múltiplas falhas!

Invensys Confidential 65
Maior Tempo de Intervalo entre testes Process Systems

= Diagnósticos

 Conforme a IEC 61508, caso múltiplos diagnósticos e diversificados estejam em


uso o fator de Cobertura de Diagnóstico melhora em um fator de 10 vezes
 A Triconex usa tanto referência como Diagnósticos de Comparação e com
diferentes tipos de hardware!
 É por isso que o sistema é certificado pela TUV com 99.0 – 99.9% de Cobertura
de Diagnóstico!

Invensys Confidential 66
Maior Tempo de Intervalo entre testes Process Systems

= Diagnósticos
 Alguns Diagnósticos:
– Scan failure
– Memory faults
– Microprocessor faults
– Communication faults
– I/O interface or addressing faults
– Application program and hardware
layout consistency
– I/O module faults
– Voted signal discrepancy
– Load power or fuse faults
– Power supply faults
– Over temperature conditions
– "stuck-on" on discrete input or
output
– "stuck-off" - open circuit failure of a
discrete output
– Stuck At

Invensys Confidential 67
Maior Tempo de Intervalo entre testes Process Systems

= Diagnostic Panel

Invensys Confidential 68
Maior Tempo de Intervalo entre testes Process Systems

= SOE ( Sequencia de Eventos )

Invensys Confidential 69
Process Systems

Degradação

Invensys Confidential 70
Process Systems

Como a Arquitetura
Quad se Compara
com o Trident?

• Somente a CPU do
Processador Principal é
Quad !

• Dois Módulos Processador


Principal, cada com dois
processadores centrais

• A Arquitetura do Módulo E/S


é composta de dois (2)
Módulos Simplex

• Segundo a TUV, sem que haja


uma
Supervisão Constante de
Operador
uma falha de um Módulo de
E/S resulta em:
• Parada do Grupo de
Processo
ou
Parada do Sistema
Invensys Confidential 71
Gerenciamento de Falhas no Trident
Uma Arquitetura Projetada para Aumento da Disponibilidade
Sob Múltiplos Cenários de Falhas Process Systems

Sem Falhas. Módulos do


Sistema em Operação Ilimitada
Trident Sistema Quad

 E/S em Modo TMR  E/S em Modo Dual

Invensys Confidential 72
Gerenciamento de Falhas no Trident
Uma Arquitetura Projetada para Aumento da Disponibilidade
Sob Múltiplos Cenários de Falhas Process Systems

Primeira Falha em Um Ponto em Sistema


Não Supervisionado Continuamente por Operator
Trident Sistema Quad

 Ponto Marcado como  Ponto Marcado como


Dual Smplex

 Módulo Marcado  Módulo Parado


como Dual
 Conforme TUV:
 Certificação TUV:
Parada do Grupo de
Operação Ilimitada Processo!
do Sistema ! ou
Parada do Sistema!

Invensys Confidential 73
Gerenciamento de Falhas no Trident
Uma Arquitetura Projetada para Aumento da Disponibilidade
Process Systems
mesmo sob Múltiplos Cenários de Falhas

Segunda Falha em Outros Pontos

Trident Sistema Quad

 Segundo Ponto  Ambos os Módulos


Marcado como Dual Parados!

 Módulo Continua Dual


 Conforme TUV:
Certificação TUV:

Operação Ilimitada do Grupo de Processo


Sistema ! Já Parado!
ou
Sistema Já Parado
desde a Primeira
Falha!

Invensys Confidential 74
Gerenciamento de Falhas no Trident
Uma Arquitetura Projetada para Aumento Process Systems
da Disponibilidade Mesmo Sob Múltiplos Cenários de Falhas

Muitas Falhas em Diferentes Pontos

Trident Sistema Quad

 Pontos Falhos  Ambos os Módulos Já


Marcados como Parados!
Dual

 O Módulo continua
Dual  Conforme TUV:

 Certificação TUV: Grupo de Processo


Já Parado!
Ainda Operação ou
Ilimitada do Sistema ! Sistema Já Parado
desde a Primeira
Falha!

Invensys Confidential 75
Gerenciamento de Falhas no Trident
Uma Arquitetura Projetada para Aumento Process Systems
da Disponibilidade Mesmo Sob Múltiplos Cenários de Falhas

Segunda Falha em um Ponto Já Falho

Trident Sistema Quad

 Ponto é Marcado como  Ambos os Módulos Já


Simplex Parados!

 Módulo é Marcado
como Simplex
 Conforme TUV:
 Certificação TUV:
Grupo de Processo
Tempo de Operação do Já Parado!
Sistema Restrito a 72 ou
Hrs !
Sistema Já Parado
desde a Primeira
Falha!

Invensys Confidential 76
Gerenciamento de Falhas no Trident
Uma Arquitetura Projetada para Aumento Process Systems
da Disponibilidade Mesmo Sob Múltiplos Cenários de Falhas

Terceira Falha em um mesmo Ponto

Trident Sistema Quad

 Pontos são Marcados Esse tipo de


como Zero degradação é
impossível em um
 Módulo é Marcado Sistema com
como Zero Arquitetura Quad!

 Conforme TUV:

Sistema Parado!

Invensys Confidential 77
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
Se TMR=3, Dual=2, Simplex=1 e Parado=0

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

# de Canais Controlando Aquele Ponto

Nível de Degradação do Sistema =

Soma de Todos Níveis de Degradação de Ponto


Número de Pontos do Sistema

Invensys Confidential 78
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
Exemplo: Sistema = Um Módulo

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

3+3+3+3 … = 96

Nível de Degradação do Sistema =

96
=3
32

Invensys Confidential 79
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
Exemplo: Sistema = Um Módulo

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

2+2+2+2 … = 64

Nível de Degradação do Sistema =

64
=2
32

Invensys Confidential 80
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
QMR – Melhor Caso – Falha do Primeiro Ponto Pára Perna Inteira

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

1+1+1+1 … = 32

Nível de Degradação do Sistema =

32
=1
32

Invensys Confidential 81
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
Trident – Pior Caso – Falha do Primeiro Ponto Afeta Somente Aquele Ponto

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

3+2+3+3 … = 95

Nível de Degradação do Sistema =

95
32 = 2.97

Invensys Confidential 82
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
QMR – Melhor Caso – Falha do Segundo Ponto Pára Módulo Inteiro

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

0+0+0+0 … = 0

Nível de Degradação do Sistema =

0
=0
32

Invensys Confidential 83
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
Trident – Pior Caso – Falha do Segundo Ponto Afeta Somente Aquele Ponto

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

3+2+3+2 … = 94

Nível de Degradação do Sistema =

94
= 2.94
32

Invensys Confidential 84
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa
Trident – Pior Caso – Falha do Terceiro Ponto Afeta Somente Aquele Ponto

Arquitetura do Sistema de Segurança

Nível de Degradação do Ponto =

2+2+3+2 … = 93

Nível de Degradação do Sistema =

93
= 2.91
32

e assim em diante ….

Invensys Confidential 85
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa

 Na Realidade, conforme a
um Sistema Trident com
Módulo de 32 Pontos pode
suportar até 64 Falhas antes de
fazer um Shutting-Down

Nível de Degradação do Ponto =

2+2+2+2 … = 64

Nível de Degradação do Sistema =

32
= 1.0
32

Invensys Confidential 86
Manuseio de Falhas no Trident
Degradação Gradual Process Systems
TMR – Dual – Simplex - Zero

Avaliação Quantitativa

4
System Degradation Level

Trident
2
Quad
1

0
0 1 2 3
Faults

Invensys Confidential 87
Process Systems

TRIDENT TRIPLE MODULAR REDUNDANT (TMR) CONTROLLER


Sample
CONFIGURATION DATA
Number of 32 point Digital Input Modules/ Safety Function (nsf) 1 Mean Time to Repair- Online (MTTRot) 8 Hours

Number of 32 point Analog Input Modules/ Safety Function (nasf) 1 Periodic Offline Test Interval (TI) 8760 Hours

Number of 6 point Pulse Input Modules/Safety Function (npisf) 1

Number of 16 point Digital Output Modules/ Safety Function (msf) 1 Common Cause Beta Factor (Beta) 2.0%

Number of 4 point Analog Output Modules/ Safety Function (masf) 1

MODULE FAILURE RATES


Total Fraction Safe Diagnostic Safe Safe Dangerous Diagnostic Dangerous Dangerous
Failure Safe Failure Coverage Detected Undetected Failure Coverage Detected Undetected
Rate Failures Rate Safe Failure Rate Failure Rate Rate Dangerous Failure Rate Failure Rate
Main Processor 2.13626 0.9522 2.0340 0.9577 1.94790 0.08614 0.10222 0.9994 0.102160 0.0000573
Digital Input Module Leg (32pt) 2.43754 0.9952 2.4257 0.9884 2.39762 0.02810 0.01182 0.9956 0.011770 0.0000517
Digital Input Common Processing 0.67306 0.9824 0.6612 0.9817 0.64914 0.01210 0.01182 0.9956 0.011770 0.0000517
Digital Input Circuit 0.05514 1.0000 0.0551 0.9909 0.05464 0.00050 0.00000 1.0000 0.000000 0.0000000
Analog Input Module Leg (32pt) 2.28527 0.7058 1.6131 0.9965 1.60734 0.00571 0.67222 0.9999 0.672160 0.0000555
Analog Input Common Processing 0.55535 0.9766 0.5423 0.9936 0.53886 0.00347 0.01302 0.9957 0.012960 0.0000555
Analog Input Circuit 0.05406 0.6189 0.0335 0.9979 0.03339 0.00007 0.02060 1.0000 0.020600 0.0000000
Pulse Input Module Leg (6pt) 1.45651 0.8265 1.2039 0.9929 1.19537 0.00850 0.25264 0.9904 0.250224 0.0024140
Pulse Input Common Processing 0.90322 0.7986 0.7213 0.9972 0.71927 0.00203 0.18192 0.9932 0.180678 0.0012380
Pulse Input Circuit 0.09222 0.8722 0.0804 0.9866 0.07935 0.00108 0.01179 0.9834 0.011591 0.0001960
Digital Output Module Leg (16pt) 4.76886 0.5873 2.8008 0.9967 2.79163 0.00921 1.96802 1.0000 1.967967 0.0000517
Digital Output Common Processing 0.53803 0.9901 0.5327 0.9955 0.53030 0.00238 0.00535 0.9903 0.005300 0.0000517
Digital Output Switches 0.19832 0.5361 0.1063 0.9970 0.10600 0.00032 0.09200 1.0000 0.092000 0.0000000
Analog Output Module Leg (4pt) 0.97096 0.8766 0.8512 0.9977 0.84923 0.00196 0.11978 0.9971 0.119427 0.0003490
Analog Output Common Processing0.97096 0.8766 0.8512 0.9977 0.84923 0.00196 0.11978 0.9971 0.119427 0.0003490
Power Supplies 1.00000 1.0000 1.0000 1.0000 1.00000 0.00000 0.00000 1.0000 0.000000 0.0000000
Note: 1) All failure rates are in failures per million hours.
2) Total failure rates were computed by using Bellcore Issue 6 failure rate data.

FAIL - TO - FUNCTION
PFDavg 7.836E-07
Safety Availability 99.999922%
Invensys Confidential 88
Process Systems

TRIDENT TRIPLE MODULAR REDUNDANT (TMR) CONTROLLER


Sample
CONFIGURATION DATA
Number of 32 point Digital Input Modules (n) 1 Mean Time to Repair- Online (MTTRot) 8 Hours

Number of 32 point Analog Input Modules (na) 1 Periodic Offline Test Interval (TI) 8760 Hours

Number of 6 point Pulse Input Modules (npi) 1

Number of 16 point Digital Output Modules (m) 1 Common Cause Beta Factor (Beta) 2.0%

Number of 4 point Analog Output Modules (mao) 1

Number of Dual Power Supplies (l) 1

MODULE FAILURE RATES


Total Fraction Safe Diagnostic Safe Safe Dangerous Diagnostic Dangerous Dangerous
Failure Safe Failure Coverage Detected Undetected Failure Coverage Detected Undetected
Rate Failures Rate Safe Failure Rate Failure Rate Rate Dangerous Failure Rate Failure Rate
Main Processor 2.13626 0.9522 2.0340 0.9577 1.94790 0.08614 0.10222 0.9994 0.102160 0.0000573
Digital Input Module Leg (32pt) 2.43754 0.9952 2.4257 0.9884 2.39762 0.02810 0.01182 0.9956 0.011770 0.0000517
Digital Input Common Processing 0.67306 0.9824 0.6612 0.9817 0.64914 0.01210 0.01182 0.9956 0.011770 0.0000517
Digital Input Circuit 0.05514 1.0000 0.0551 0.9909 0.05464 0.00050 0.00000 1.0000 0.000000 0.0000000
Analog Input Module Leg (32pt) 2.28527 0.7058 1.6131 0.9965 1.60734 0.00571 0.67222 0.9999 0.672160 0.0000555
Analog Input Common Processing 0.55535 0.9766 0.5423 0.9936 0.53886 0.00347 0.01302 0.9957 0.012960 0.0000555
Analog Input Circuit 0.05406 0.6189 0.0335 0.9979 0.03339 0.00007 0.02060 1.0000 0.020600 0.0000000
Pulse Input Module Leg (6pt) 1.45651 0.8265 1.2039 0.9929 1.19537 0.00850 0.25264 0.9904 0.250224 0.0024140
Pulse Input Common Processing 0.90322 0.7986 0.7213 0.9972 0.71927 0.00203 0.18192 0.9932 0.180678 0.0012380
Pulse Input Circuit 0.09222 0.8722 0.0804 0.9866 0.07935 0.00108 0.01179 0.9834 0.011591 0.0001960
Digital Output Module Leg (16pt) 4.76886 0.5873 2.8008 0.9967 2.79163 0.00921 1.96802 1.0000 1.967967 0.0000517
Digital Output Common Processing 0.53803 0.9901 0.5327 0.9955 0.53030 0.00238 0.00535 0.9903 0.005300 0.0000517
Digital Output Switches 0.19832 0.5361 0.1063 0.9970 0.10600 0.00032 0.09200 1.0000 0.092000 0.0000000
Analog Output Module Leg (4pt) 0.97096 0.8766 0.8512 0.9977 0.84923 0.00196 0.11978 0.9971 0.119427 0.0003490
Analog Output Common Processing0.97096 0.8766 0.8512 0.9977 0.84923 0.00196 0.11978 0.9971 0.119427 0.0003490
Power Supplies 1.00000 1.0000 1.0000 1.0000 1.00000 0.00000 0.00000 1.0000 0.000000 0.0000000
Note: 1) All failure rates are in failures per million hours.
2) Total failure rates were computed by using Bellcore Issue 6 failure rate data.

FAIL - SAFE
MTTFspurious 710.8 Years
Availability 99.99987%

Invensys Confidential 89
10 Truths about SIS
Process Systems

 1) SIL é uma medida de segurança , mas não tem impacto na disponibilidade


operacional
 2) A qualidade de um Sistema Instrumentado de Segurança ( SIS ) tem um impacto
direto na performance da planta.
 3) Muitas empresas podem fornecer um Sistema de Segurança , mas poucas podem
realmente atender às suas reais necessidades
 4) A norma IEC61511 dita que os usuários de um SIS devem mostrar competência
em aplicações “functional safety”
 5) Seu Sistema Instrumentado de Segurança deve proteger sua planta durante todo
o seu ciclo de vida.
 6) Você não tem que escolher entre um SIS independente e um BPCS integrado,
você pode ter os dois .
 7) Os Sistemas de Segurança Duais ( 1oo2 ) não custam menos que um TMR ( Triple
Modular Redundant 2oo3 ) , normalmente custam mais .....
 8) Os manuais de Restrições Operacionais e Considerações de Segurança devem
ser solicitados e atentamente vistoriados
 9) A implementação e a instalação do SIS é tão importante quanto o produto.
 10) A Manutenção de um SIS é mais do que simplesmente coletar dados.

Invensys Confidential 90
Process Systems

Obrigado