Professional Documents
Culture Documents
U08 PPT Mullin EWR9Ce
U08 PPT Mullin EWR9Ce
9 Edition
PowerPoint Slides
to accompany
Unit 8
Service Entrance Equipment
For the Red Seal exam, note that this unit covers
the following RSOS tasks:
● Task B-7
● Task B-11
Unit 8: Objectives
• Define electrical service, supply service, consumer’s
service, overhead service, and underground service
• List the various CEC rules covering the installation
of a mast-type overhead service and an
underground service
Clearance Requirements
• The service conductors must not be less than 1 m
from a window, door, or porch, Rule 6-112 4).
• Normally there must be a clearance of 915 mm
between the point of attachment and the roof.
• This may be reduced if a minimum of 600 mm is
maintained between the roof and the bottom of the
drip loops on the supply conductors.
Panel A breakdown
• This type of panel is listed
by the CSA as a combination
panelboard and as service
equipment.
Methods of Grounding
• Method #1 Field-Assembled Electrode
Figure 8-25
Figure 8-25
Figure 8-25
Bonding
• Bonding must be done at service entrance
equipment.
• Rule 10-604 lists the methods approved for bonding
this equipment.
Figure 8-33 Cartridge-Type Dual-Element fuse is a 250-volt, 100-ampere fuse. (Courtesy of Eaton)
Figure 8-33 The cutaway view shows the internal parts of the fuse. (Courtesy of Eaton)
Circuit Breakers
• Installations in dwellings normally use thermal-
magnetic circuit breakers.
On a continuous overload, a bimetallic element in
such a breaker moves until it unlatches the inner
tripping mechanism of the breaker.
• Momentary small overloads do not cause the
element to trip the breaker.
If the overload is heavy or if there is a short circuit, a
magnetic coil in the breaker causes it to interrupt the
branch circuit instantly.