Professional Documents
Culture Documents
Lec13 - LV Circuit Breakers
Lec13 - LV Circuit Breakers
LV / LT Circuit Breakers
Prepared by
Dr. Md. Rezwanul Ahsan
Associate Professor, Dept. of EEE
Lecture Contents
@Rezwan
Circuit Breakers
A Circuit Breaker is an automatically operated electromechanical switch designed to
protect an electrical circuit from damage caused by an overload or a short-circuit.
“A short circuit is an over-current but not an overload”
Basically CB is used to detect fault condition and immediately cut the power supply.
Unlike fuse, which operates once and then has to be replaced; a circuit breaker can
reset to resume normal operation.
@Rezwan
Breaker Ratings
According to the IEC 62271-100, IEC 62271-1 and IEC 60947-2
Plain-break air breakers are used in low voltage and medium voltage up to
15 kV.
For low and medium voltages fuses can be used, but the main disadvantage
is that they must be replaced after fault clearing.
In medium voltage systems minimum oil, SF6 and vacuum breakers are
also being used.
For high voltages minimum oil, SF6 and blast-air breakers are used, but
always with multiple interrupters in series.
The maximum voltage per interrupter is 100 kV for air-blast and SF6
breakers, 170 kV for minimum oil breakers.
@Rezwan
Miniature Circuit Breakers (MCB)
Operation:
The working of a miniature circuit breaker in case of overload and short circuit fault
is, (i) For overload protection, they have a Bi-metallic strip (produces thermal
effect) which causes the circuit to open, and (ii) For short circuit protection, it has
an electromagnetic (produces electromagnetic effect) kind of thing.
Fig. Thermal-magnetic circuit breaker trip latch operation: (a) normal and
(b) overcurrent condition
@Rezwan
Miniature Circuit Breakers (MCB)
Operation:
The thermal operation of the miniature circuit breaker is achieved with a
bimetallic strip. Whenever continuous over electric current flows through
MCB, the bimetallic strip is heated and deflects by bending. This deflection of
bimetallic strip releases the mechanical latch. As this mechanical latch is
attached with the operating mechanism, it causes to open the miniature circuit
breaker contacts.
But during short circuit condition, the sudden rising of electric current causes
electromechanical displacement of plunger associated with tripping coil or
solenoid of MCB. The plunger strikes the trip lever causing an immediate
release of latch mechanism consequently open the circuit breaker contacts.
@Rezwan
Types of MCB based on Tripping Characteristics
The tripping current and operating time of each of the above MCB types are given
in the table below.
@Rezwan
Typical Loads by Tripping Curve - MCB
@Rezwan
Selection of Right MCB
The decision to use Type B, C or D miniature circuit breakers for final circuit
protection in residential, commercial, industrial or public buildings can be based on
a few simple rules. It should be noted that the primary purpose of circuit protection
devices such as miniature circuit breakers and fuses is to protect the cable
downstream of the device. The essential distinction between Type B, C or D
devices is based on their ability to handle surge currents without tripping. These
are, typically, inrush currents associated with fluorescent and other forms of
discharge lighting, induction motors, battery charging equipment, etc.
Type B, C, and D are used for overcurrent protection of cables in
accordance with IEC/EN 60898-1
Type K for the protecting motors and transformers and simultaneous
overcurrent protection of cables with overload tripping based on IEC/EN
60947-2
Type Z for control circuits with high impedances, voltage converter
circuits, and semi cable protection and simultaneous overcurrent protection
of cables with overload tripping based on IEC/EN 60947-2.
@Rezwan
MCB Selection Table
The MCB selection table helps to choose the right MCB for protecting the circuit.
@Rezwan
Selecting the Rating Of MCB at a Particular Circuit
If the proper rating is not selected on a particular circuit, there will be no proper
functions of MCB at overload. Therefore it is very important to select the right
rating of MCB which can be easily calculated as under.
Example
Let’s imagine you have 4 Fans, 1 TV, 4 Tubes, 1 V.C.D., 1 Refrigerator & 1 1.5
Ton Air Conditioner on a particular circuit.
Ref.:
https://studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html
@Rezwan
Molded-Case Circuit Breakers (MCCB)
MCCB is an electromechanical safety device used to protect an electrical circuit
from overload or short circuits. It works by automatically cutting off the power
supply when a fault or overcurrent situation arises, thus preventing any damage to
the electrical system. MCCBs can be used in both low-voltage and high-voltage
systems.
MCCBs are used in high energy requirement regions such as high-power equipment
in industries or for commercial purposes (ranges from 16 A to 3000 A). It is
generally installed on the secondary side of transformer stations (main switch or for
protecting individual branches), in the distribution panel and provide a visible
indication. Unlike an MCB, the trip characteristics of MCCBs are changeable as per
the requirement. Except the mold (covering), the operating principles/working of
MCCB is almost same as MCB. It has the following specifications:
Current rating – Amperes (64 A to 3000 A)
Current Setting Range – Amperes
Short Circuit Rating – Kilo Amperes ( up to 100 kA)
Operating Characteristics – Normal / Current Limiting Type
@Rezwan
Molded-Case Circuit Breakers (MCCB)
Construction:
The molded case or frame is the cushion that keeps all parts of the circuit breaker in
place. It is solidly built from ‘glass polyester’ or ‘thermoset composite resin that
gives a great nonconducting strength despite its compressed size.
A Molded case circuit breaker generally have - a thermal element for overcurrent
and a magnetic element for short circuit release which has to operate faster (same as
MCB). MCCBs are manufactured such a way that end user will not have access to
internal workings of the over-current protection system. Additionally it has an arc
extinguishing device which extinguishes the arc generated upon current interruption.
@Rezwan
Molded-Case Circuit Breakers (MCCB)
Operation / Working Principles:
The MCCB uses a temperature sensitive device (the thermal element) with a current
sensitive electromagnetic device (the magnetic element) to provide the trip
mechanism for protection and isolation purposes. This enables the MCCB to
provide: A. Overload Protection, B. Electrical Fault Protection against short circuit
currents, and C. Electrical Switch for disconnection.
@Rezwan
Molded-Case Circuit Breakers (MCCB)
Operation / Working Principles:
The MCCB uses a temperature sensitive device (the thermal element) with a current
sensitive electromagnetic device (the magnetic element) to provide the trip
mechanism for protection and isolation purposes. This enables the MCCB to
provide: A. Overload Protection, B. Electrical Fault Protection against short circuit
currents, and C. Electrical Switch for disconnection.
@Rezwan
Air Circuit Breakers (ACB)
Working Principle:
Air Circuit breakers normally have two pairs of contacts. The main pair of contacts
carry the current at normal load and these contacts are made of copper. The
additional pair is the arcing contact and is made of carbon.
When the circuit breaker is being opened, the main contacts open first and
during the opening of main contacts the arcing contacts are still in touch with
each other.
As the current gets a parallel low resistive path through the arcing contact
during the opening of main contacts, there will not be any arcing in the main
contact.
The arcing is only initiated when finally the arcing contacts are separated. Each
of the arc contacts is fitted with an arc chute which helps the arc discharge to
move upward due to both thermal and electromagnetic effects.
As the arc is driven upward it enters in the arc chute, consisting of splitters. The
arc in chute will become colder, lengthen and split hence arc voltage becomes
much larger than system voltage at the time of operation of the air circuit
breaker, and therefore the arc is quenched finally during the current zero.
@Rezwan
Air Circuit Breakers (ACB)
@Rezwan
Calculation/ Selection of Circuit Breaker
Classification of CB according to Current Ratings:
MCB 6 A – 63 A
MCCB 64 A – 800 A