INTRODUCTION OF NTPC
largest power generating company of India. A public sector company-1975. NTPC has installed capacity of 29,394 MW. 15 coal based power stations (24,395 MW) 7 gas based power stations (3,955 MW) 4 power stations in Joint Ventures (2, 294MW). It plans to be a 75,000 MW company by 2017.
SSB MODAL
Godavari basin
Coal Bed Methane reserves estimated to be between
GAS TURBINE
GAS TURBINE IS A HEAT ENGINE
THE PROCESS INCLUDEES
COMPRESSION: of working medium(air) taken from atmosphere in a compressor COMBUSTION:increase working medium of temp. by constant pressure ignition of fuel in combustion chamber EXPANSION:of the product of combustion in a turbine.
2.
3. 4 5.
Auraiya
Kawas Dadri Jhanor-Gandhar Rajiv Gandhi CCPP Kayamkulam Faridabad Total (Gas)
Uttar Pradesh
Gujarat Uttar Pradesh Gujarat Kerala Haryana
6.
7.
3,955
4/27/2012
DEMAND PROJECTIONS
Year Electrical Energy Requirement at Power Station Bus Bars (GWh) Annual Peak Electric Load at Power Station Bus Bars (MW)
2011-12
968659
1392066
2016-17
2021-22
1914508
4/27/2012
MW MW MW MW MW
4/27/2012
713
14-A
Installed capacity: China vs. India (In GW) China 217.2 India 138
316
338
132
96.2
104.9 81.7 87.1 65.8 42.6 30.2 1.8 1.6 1980 1980 1985 1985 1990 1990 1995 1995 2000 2000 2002 2007
10
96.2
63.6
1950 1950
4/27/2012
GENERATOR DETAILS:1.
2. 3.
4.
5. 6.
Gas turbine generator : 134 MVA - 4 Nos Steam turbine generator : 140 MVA - 2 Nos Air cooled, 3000 RPM, 2 pole, double star. Alsthom, France make. 11.5 kV generator terminal voltage. Four coolers in the generator for cooling the air.
Generator photo
1) RATED VOLTAGE = 11.5 KV 2) RATED CURRENT =6740 AMPS 3) POWER FACTOR = 0.8 4) EXCITATION VOLTAGE.=209 V DC 5) EXCITATION CURRENT. =1500 amps 6) GENERATOR COOLING =AIR COOLED.
1.
2. 3. 4. 5.
A diesel generator is the combination of a diesel engine with an electrical genertor. emergency power-supply if the grid fails. Its capacity is 3MW speed 1500 rpm shell type core.
SWTICHYARD
main parts of switchyard in NTPC 1. TRANSFORMER 2. ISOLATOR 3. CIRCUIT BREAKER 4. WAVE TRAP 5. LIGHTING ARRESTOR 6. CURRENT TREANSFORMER 7. POTENTIAL TRANSFORMER 8. BUS BAR
TRANSFORMERS
Generator transformer Three Phase, 140 MVA, Fuji make. Delta Star, neutral solidly grounded. Welded tank construction. Oil forced air forced cooling. NVTC for voltage control (off load). 9 cooling fans for each unit, 3 for each phase & 3 pumps for circulating oil.
1. 2. 3. 4. 5. 6.
Generator transformer
TRANSFORMER TYPES
STATION TRANSFORMER
LIGHTING TRANSFORMER
1. 2. 3. 4. 5.
Station transformer Three Phase, 24 MVA, Fuji make. Delta Star, neutral solidly grounded. Welded tank construction. Oil natural air natural cooling. OLTC for 6.6 kV Bus voltage control
TYPES OF ISOLATOR
BUS ISOLATOR LINE ISOLATOR TRANSFORMER ISOLATING SWITCH
Wave Trap:To prevent high frequency signals from entering other zones.
Lighting transformers Resin cast dry type transformer. Delta star for providing neutral point to the lighting supplies. Also reduces the fault level on the lighting bus.
one Low Pressure Turbine. HP turbine =single flow horizontal split type with 13 stages the LP turbine =double flow horizontal split type with 5 blades at each side. 6 bearing although from High Pressure Turbine to generator. The output megawatt of Steam Turbine is 116.6Mw at 11KV.
6.6 kV Protections Station transformer protections Motor protections Transformer protections 220 kV Protections Line protections Busbar protection Breaker failure protection
TRANSFORMER PROTECTION
TRANSFORMER DIFFRENTIAL
PROTECTION THREE PHASE OVER CURRENT RELAY REATH FAULT RELAY BUCHHOLZ RELAY
Generator Differential Protection Generator Stator earthfault protection 100% Generator Stator earthfault protection 95% Generator rotor earth fault protection
Zones of protection
Generator Protn. Transformer Protn. Line Protn. Transformer Protn.
Busbar Protn.
Station transformer protections 1. Three phase Overcurrent protection. 2. Earthfault protection. 3. Restricted earth fault protection. Motor protection 1. IDMT over current protection 2. Earthfault protection Transformer protection 1. IDMT over current protection 2. Earthfault protection
Line protections
1. Main I Distance protection (21-1) 2. Main II Distance protection (21-2)
6. Fault locator