Boiler Light Up & Loading
Boiler Light Up & Loading
Clean Up
Internal-foreign material should be removed
from pressure parts.
External-any obstruction to the normal
expansion of unit should be removed.
All personnel and maintenance equipments
should be removed.
Access doors, man holes should be closed.
Working area should be cleared.
Chemical cleaning & Steam
blowing
(For new unit or after major pressure part repair)
Acid cleaning & Alkali Boil-out
Steam blowing - M. S.& R. H. lines should be
blown out to remove scale & foreign matter prior
to setting of DRUM & SH safety valves
Safety valve Setting - Popping pressure & downs
should be adjusted .
Cold Start Up Checks (Controls)
Assumed above activity completed.
Following Auto control system to be checked
Drum level control
DP across feed control valves
Furnace draft control
Total air flow control When CMC
Total fuel control When CMC
P. A.Header pressure control
LDO/HO Pressure Control
LDO/HO atomizing Air /steam pressure control
HO temp control
Mill air flow & temp control
Wind box DP control
Cold Start Up Checks
(INTERLOCKS)
Drum level High - (A) (+) 96mm
Drum level very High (T) (+) 125mm
Drum level Low (A) (-)104mm
Drum level very Low (T) (-)175mm
Furnace Pressure high (A)(+)25mmwcl
Furnace Pressure very high (T) (+)200mmwcl
Furnace Pressure low (A) (-)25mmwcl
Furnace Pressure very low (T)(-)200mmwcl
Continue……………...
Air flow less than 30 % (T)
Air flow less than 40 % (T)
Seal Air pressure low (A) C/M tripping
Furnace temperature 11210 C
Flue Gas Temperature 5380 C Bef Syncronizing)
Flue Gas APH O/L temp 1300 C
LDO/HO pressure low
LDO/HO pressure very low oil gun tripping
Coal Mill DP High 200 mm
Coal Mill temp High 770 C
Wind Box DP should be 40-100mm
APH ON – Drive Fail appears when APH stops
Scanner/Ignitor fans ON
Boiler Aux(Alarm/ Trippings &
interlocks)
ID/FD/PA fans Brg temp A/T 80/850C
ID/FD/PA fans lub oil press low A
ID/FD/PA fans water flow low A
ID/FD/PA motor protection trip
ID/FD/PA fans Motor Winding temp A 1050C
ID/FD/PA fans Lub oil press A/T
APH lub oil pressure low & Standby pump not started on
Auto
APH Brg temp high
If one ID trips then one selected FD/PA fan & lower coal
mills( more than 3 mills )will trip Interconnecting damper
will open.
Sequence of operation
All permits cancelled
Bottom Ash Hopper, seal through filled & overflow
maintained.
Power supply HT/LT Normal
G.S.Water cooling system normal.
Instrument Air/Service Air Pressure Normal.
Oil guns are in position.
Drum level G/Glass in Service.
Drum /Eco vents open
SH drains crack open.
Boiler outlet valves close.
DM water filling system normal.
Drum level normal.
Burner tilt horizontal.
Continue……
Start APH(both top/bottom) lub oil pumps & adjust lub oil
pressure by recalculating valve.
Perform LOP auto pick up trial.
Start APH one by one & open inlet /outlet dampers. Check current
as well as abnormal sound.
Start & Establish lub oil system of ID/FD fan as described above.
Discharge damper of respective fan must be close & Inlet Guide
Vane close.
Start one ID Fan open DD, then set furnace draft for – 5mm wcl
and put ID fan on Auto. Interconnecting damper open
Select FD Fan to be started.
Start one FD Fan as above.
Gradually increase air flow up to 300 T/Hr. Observe Wind box DP.
Put Wind box damper on auto.
PURGE READY PERMISSIVES