Professional Documents
Culture Documents
Chapter I
Chapter I
1. FAULT ANALYSIS
1.1. INTRODUCTION
Fault (short circuit) is any failure which interferes the normal flow
of current.
1
Cont’d
2
Cont’d
4
1.2. FAULT TYPES
most Sevier one, but relatively rare in occurrence, and are the
easiest to analyze.
Rf
e) L-E
f) L-E fault with fault impedance Figure 1.1:Fault types
6
1.3. SYMMETRICAL FAULT ANALYSIS
The simplest model of a three-phase short circuit in a power system is
series-RL circuit. For these calculations, normal single-phase equivalent
circuits may be used as an ordinary network calculation.
1.3.1. Series R-L circuit transients
7
Fig.1.2. Current-voltage wave forms in R-L circuit transient
Cont’d
Consider the series R-L circuit shown in fig 1.2.
Closing of SW at t = 0 represents a first approximation of
three-phase short circuit at the terminals of unloaded
synchronous machine.
For simplicity, assume zero fault impedance; that is, the short
circuit is a solid or "bolted" fault.
The current is assumed to be zero before SW closes &
di(t)
L Ri(t) 2Vsin(wt α) (1.1)
dt
8
Cont’d
Solution for i(t) is
t
i(t) i (t) i (t) 2V sin(t α - θ) sin(α θ)e T
ac dc Z A (1.2)
Where
t
i (t) 2V sin(α θ)e T 1.4
dc Z
Z R 2 (ω L) 2 R 2 (X)2 Ω 1.5
9
θ tan 1 ωL tan 1 X Cont’d
= R 1.6
R
1.7
t
2V sin(t - π ) e T A (1.8)
i(t)
Z 2
10
Cont’d
The rms value of i(t) is
2
-t 2t
I
rms
(t) ac
I (t ) 2 I (t) 2
dc
I
ac
2
2I e T
ac
I ac 1 2e
T
(1.9)
4π
Where K() =
X
per unit (1.11)
1 2e
R
2V V
symmetrical (ac) i ac (t)= sin(ωt+α-θ) Iac =
Z Z
2V
DC offset i dc (t)= sin(α-θ)e -t/T
Z
12
Example 1.1: A bolted short circuit occurs in the series R-L circuit
of Figure 1.2 with V = 20 kV, X = 8Ω, R = 0.8Ω, and with maximum dc
offset. The circuit breaker opens 3 cycles after fault inception.
Determine (a) the rms ac fault current, (b) the rms "momentary"
current at T= 0.5 cycle, which passes through the breaker before it
opens, and (c) the rms asymmetrical fault current that the breaker
interrupts.
SOLUTION
a. From table 1.1
b. From (1.10) and (1.11) with (X/R) = 8/(0.8) = 10 and = 0.5 cycle,
13
1.3.2 Balanced fault calculation in power system
E
The sustained (steady state) fault g (1.14)
I
current. X
d I’’> I’> I
The sub-transient current (I’’ ) is initial symmetrical current which does
not include dc components. To consider dc components some
coefficient value of 1.4 to 1.8 is used. 15
Example 1.2:
1. A three-phase, 50 Hz machine has the stator windings initially open-
circuited, and the field current adjusted so that the terminal voltage is at
rated value (i.e., 1.0 pu)
The machine has the following time constants:
Xd" = 0.15 pu td" = 0.035 sec
Xd' = 0.40 pu td' = 1.0 sec
Xd = 1.20 pu
Determine the sub-transient, transient, and steady state short-
circuit currents
16
Cont’d
17
Cont’d
● The following assumption will be made in practical short
circuit current calculations:
20
Example 1.3
Determine the magnitude of the fault currents in the following system
assuming a three phase short circuit to ground of the lines at point F.
The base current for the line is known to be 836.74 amps.
c) Find the Thevenin equivalent for the single line circuit at the point of the
fault (F).
The Thevenin voltage is given by the open circuit voltage at F. In an open circuit
it is fair to assume that the voltage will be 1.0 pu.
To find the Thevenin impedance make zero the sources and find the equivalent
Impedance looking at the circuit from the fault location 22
Cont’d
Combining the last two impedance in parallel we get the Thevenin impedance
23
*
Cont’d
The maximum fault current is also determine by the impedance (distance)
between the fault and the source.
Example 1.4
A three phase short circuit occurs at point X at 80% of the total line
length. Calculate the fault current with the given information. Base
current of the line is 524.864 amps.
25
Cont’d
c) Find the Thevenin Equivalent
Assume the Thevenin voltage is 1.0 pu
Zero the sources to find the Thevenin Impedance
26
Cont’d
27
1.4. Symmetrical Components
unbalanced faults Percentage of total faults
single-line to ground 60-75%
double-line to ground 15-25%
line-to-line faults 5-15%
28
2.4.1 Method of symmetrical component
To solve problems in unsymmetrical conditions of power system,
method of symmetrical component is used. Any unbalanced phasor
of a three-phase system can be resolved in to three-balanced system
of phasors. The balanced sets of sequence components are:
Positive sequence - equal in magnitude and 120o phase
displacement; a, b, c phase sequence as original phasers.
This sequence is always representing by subscript 1 (Va1,
Ia1 etc.)
Negative sequence – equal in magnitude and 120o phase
displacement; a, c, b phase sequence and have subscript 2
(Va2,Ia2, etc)
Zero sequence components - consisting of three phasors
equal in magnitude and with zero phase displacement from
each other and have subscript 0 (Va0,Ia0 etc) .
29
Cont’d
Representative symmetrical components
1. Positive sequence: 2. Negative sequence: 3. Zero sequence
30
1. Positive sequence phasor: 2. Negative sequence phasor:
1.20
1.19
1.21 1.22
31
Relating unbalanced phasors to symmetrical components
1.23
In matrix notation
1.24
32
Cont’d
[A] is known as the symmetrical components
transformation matrix
1.25
1.27
33
Cont’d
In component form, the calculation for symmetrical
components are
1.28
34
Cont’d
Similar expressions exist for voltages
1.29
1.30
1.32
1.33
1.34
35
Example 1.5:
Obtain the symmetrical components of a set of unbalanced currents
Solution:
36
Cont’d
37
Example 1.6:
The symmetrical components of a set of unbalanced voltages are
38
Cont’d
39
Cont’d
Sequence Impedances
40
2.4.2. Augmented network models
41
1. Wye-connected Balanced Loads
Model and governing equations
1.35
1.36
1.37
1.38 42
Cont’d
1.39
1.40
1.41
1.42
43
2. Transmission Line
1.43
1.44
1.45
1.46
1.47
44
Cont’d
1.48
1.49
1.50
1.51
1.52
45
3. Generators
Similar modeling of impedances to sequence impedances
Typical values for common generators
Remember that the transient fault impedance is a function of
time.
Positive sequence values are the same as Xd, Xd’, and Xd”
negative sequence values are affected by the rotation of the rotor.
X2 ~ Xd”
Zero sequence values are isolated from the airgap of the machine.
The zero sequence reactance is approximated to the leakage
reactance.
X0 ~ X L
46
Cont’d
Generator Model:
Zero Sequence
Positive Sequence
Negative Sequence
47
Cont’d
Impedance of Grounded Generators:
1.53
48
4. Transformers
Series Leakage Impedance
The magnetization current and core losses represented by the
shunt branch are neglected (they represent only 1% of the total
load current)
The transformer is modeled with the equivalent series leakage
impedance
49
Cont’d
Wye-delta transformers create a phase shifting pattern for the
various sequences
The positive sequence quantities rotate by +30 degrees
Negative sequence quantities rotate by -30 degrees
Zero sequence quantities can not pass through the transformer
USA standard
Independent of the winding order (D-Y or Y- D)
The positive sequence line voltage on the HV side leads the
corresponding line voltage on the LV side by 30°
Consequently, for the negative sequence voltages the corresponding
phase shift is -30°.
50
Cont’d
Zero-sequence network connections of the transformer depends
on the winding connection
Primary winding - wye / wye-grounded / delta
Secondary winding - wye / wye-grounded / delta
51
Cont’d
52
2.5. Unbalanced Network Faults
Common Unbalanced Network Faults
2.5.1. Single-line-to-ground faults
2.5.2. Double-line-to-ground faults
2.5.3. Line-to-line faults
2.5.1. Single Line to Ground Fault
1.54
1.55
53
1.56
Cont’d
1.57
1.58
1.59
1.60
54
Single Line to Ground Fault with Fault Impedance (Zf):
55
Cont’d
56
2.5.2. Double Line to Ground Fault
1.61
1.62
1.63
57
Cont’d
1.64
1.65
1.66
1.67
58
Cont’d
1.68
1.69
59
2.5.3. Line-to-Line Fault
1.70
1.71
60
Cont’d
1.72
61
Cont’d
1.73
1.74
1.75
1.76
1.77
1.78
62
Cont’d
1.79
1.80
1.81
1.82
63
Example 1.7:
The neutral of each generator is grounded through a current limiting
resistor of 8.333 % on a 100 MVA base
Generators are running at no-load at rated voltage and in phase
All network data is expressed on a 100 MVA base
Find the fault current for 3-phs, 1-phs, L-L, L-L-G bolted faults
64
Positive Sequence Network:
65
Negative Sequence Network:
66
Zero Sequence Network:
67
3-phase fault:
SLG fault:
68
L-L fault:
69
DLG fault:
70