How to correct

erroneous I.G press. reading


1. Electronics and connection compartment

The function of Hall IC (A, B, C, D switch) for


Local PCB

- A Switch : The flickered digit can be increased


by "A" switch.
- B Switch : The flickered rank can be shifted
by put Test tool (magnet)
on "B“ switch. (Not over 3 seconds).
Picture 2
- C Switch : The flickered digit can be decreased
by "C" switch.
- D Switch : Register data by "D" switch.
(For reference, switch is reacting on one polarity
of magnet.)

2
2. Local Indicator Setting Procedure

1) Check the value of inert gas pressure on the display.

3
2. Local Indicator Setting Procedure

2) When put magnet on "B" switch over 3 seconds, the operation mode is
changed to parameter mode with indication "C00"

4
2. Local Indicator Setting Procedure

3) Please put the magnet “D” switch.

5
2. Local Indicator Setting Procedure

4) Please try to correct erroneous IG pressure reading by inputting the deviation value
compared with actual temp. reading and then register the changed data with "D“ switch.

6
2. Local Indicator Setting Procedure

5) After correction completely, please put magnet "B" switch over 3 seconds,
the operation mode is displayed again.

7
2. Local Indicator Setting Procedure

TLP-100S Setting code

Setting contents Limit range for setting Data


C00 Pressure correction range -99.9 ~ +99.9 [mbar] 0.00
C01 Level adjustment -1.000 ~ 20.000 [m] 05.000
C02 Average calculation time for level 1 ~ 50 [times] 01
C03 Upper temperature correction range -9.9 ~ +9.9 [°C] or +00.0
[°F]
C04 Middle temperature correction range -9.9 ~ +9.9 [°C] or +00.0
[°F]
C05 Lower temperature correction range -9.9 ~ +9.9 [°C] or +00.0
[°F]