Professional Documents
Culture Documents
Masonry Walls
Masonry Walls
There are huge number of stone buildings in the country ranging from
rural houses to Royal places and temples.
In a typical rural stone house, there are thick stone masonry walls
(600mm to 1200mm) built using rounded stones from river beds bound
with mud mort.
These are considered to be robust but are one of the most deficient building
systems from EQ resistance point of view.
However, Inspite of the sesmic features these buildings may not becom
totally free from heavy damage and even collapse in case of major EQ.
• Instead of round stone boulders use shaped stones using chisels and
hammers.
•It is important to provide atleast one band (either lintel or roof band).
4) Control on overall dimensions and heights:--
•The unsupported length of walls between cross-walls should be limited to 5m.
•For longer walls, cross supports raised from the ground level called buttresses
should be provide at spacing not more than 4m.
•In general, stone masonry buildings should not be greater then 2 storey's
when built in cement mortar and should not be greater then 1 storey when
built in lime and mud should not be greater then 1 storey.
ii. In short but very long buildings the damaging effects are many.
iii. In buildings with large plan area, the horizontal seismic forces can be
excessive to be carried by columns and walls.
oMany buildings with an open ground storey intended for parking collapsed
during 2001 Bhuj EQ.
Adjacency of buildings:--
•When two buildings are too close to each other they may pound on each
other during EQ.
Ground vibrations during EQ’s cause inertia forces at locations of mass in the
building.
These forces travel through the roof and walls to the foundation.
Of the three components of a masonry building walls are most vulnerable to
damage caused by horizontal forces due to EQ.
But offers much greater resistance if pushed along its length (storey
direction).
Ground shakes simultaneously in the vertical and two horizontal directions
during EQ. However the horizontal vibrations are the most damaging to the
most damaging to normal masonry buildings.
If the walls are not tied together live a box the loads in their weak direction
tend to topple.
To ensure good seismic performance, all the walls must be joined properly
to the adjacent walls. In this way, walls load in their weak direction can take
the advantage of the good lateral resistance offered by walls loaded in their
strong direction.
Walls also need to be tied to the roof and foundation to preserve their
overall intensity.
To improve EQR of brick masonry:--
Box action is required. This can be done by:
1. Good interlocking of masonry courses at the junctions.
• Burnt bricks are more commonly used, bricks with low porosity must be
used, they are to be soaked in water before use to minimize the
absorption of water from mortar.
•Cement sand mortar with lime is most suitable which provides excellent
workability, stretches without crumbling as low EQ bonds well with the bricks.
• Large, tall, long and unsymmetric buildings perform poorly during EQ.
• Walls transfer loads to each other at their junction(through lintel bands and roof).
• Hence the masonry courses from the walls meeting at corners must have good
interlocking.
•In buildings with flat RC or reinforcement brick roofs, roof bond is not required.
•In buildings with flat timber or CGI sheet roof (corrugated galvanized iron) roof
bands need to be provided.
•Plinth band are used when there is corner about uneven settlement of
foundation soil.
Lintel band:-- During EQ lintel bands are subjected to bending and pulling
actions.
During the EQ shaking, the masonry walls get grouped into three sub units:
i. Spandrel masonry.
ii. Well pier masonry.
iii. Sill masonry.
Consider a hipped roof building with two window openings and one door
opening in a wall.
It has plinth and lintel bands. Since it is a hipped roof a roof band is also
provided.
When the ground shakes inertia forces cause the wall piers to disconnect
from the masonry above and below.
Movement is possible when piers are slender and weight of structure above is
small.
During shaking buildings may slide just under the roof below the lintel band or
at sill level. Some times at plinth level depending on weight of building, lateral
EQ force, area of opening, types of door frames.
Embedding vertical reinforcement bars in the edges of the slender wall piers
and anchoring them in the roof band at the top forces the masonry piers to
under go bending instead of rocking.
In wider wall piers vertical bars enhance their capacity to resist horizontal EQ
loads and delay the X-cracking.
It will help to protect wall from sliding as well as from collapsing in the weak direction.
Sliding is rare, most common damage is diagonal cracking of wall piers and also inlined
cracked at the corners of doors and windows.
The shape of openings distort and it becomes like a rhombus the corners that come
closer develop cracks.
Cracks are wider for wider openings, steel bars provided in the wall all round the
opening restricts these cracks at the corners.
Shotcrete:-- It is a cement mortar (or) cement concrete (CA not > 10mm)
conveyed through a hose and penumatically placed under high velocity on to a
prepared concrete or masonry surface.
Epoxy resins:-- These are excellent binding agents with high tensile strength.
They will be injected in to cracks.
Epoxy mortar:-- For larger void spaces, it is possible to combine epoxy resins
with sand to form epoxy mortar, it will have higher compressive strength, lower
tensile strength and lower young's modulus.
False seiling ----- non brittle like hessian cloth, bamboo matting, foam
substances.
Walls:--
1) By grouting
2) Vertical reinforcement concrete lowering on the two sides.
3) By prestressing.
Grouting:--
2 to 4 number of wholes in a square meter.