Reporting

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 15

INTRODUCTION

DISTRIBUTION
WIRING LAYOUT
GENERAL IDEA

2
The circles on the markings are the
spots where the utility pole is to be
installed.

Considerations in using a utility poles in


primary:

• Cemented utility pole


• 45 footer utility poles.
• with ranging 60 m – 45 m apart.
• double circuit.
• Conductor sizes is set to be 4/0

3
INTRODUCTION

TOTAL POWER
CONSUMPTION PER
QUADRANTS
ANALYSIS
1.3MW+
P= 1MW+1.4MW+2.
P=
4140A 6MW= 6.3 MW
5535A
P=
P= 10755A P= 1MW+
6120A P= 6570A
3780A 1.6MW+0.6MW
P=
P= 3015A +0.7MW= 3.9
P= P=1718.4 kw
2340A MW
7160A
4495A
1MW + 1.7MW
𝑃=1353.6 𝑘𝑊 + 1.4MW +
5640A 𝑃=2817.6 𝑘𝑊 3.9MW = 8MW
11470A
P= 1.1MW + 1.4
4005A
P= MW + 1.7MW
6975A +2.8MW = 7MW
P=
5805A Total Megawatts
= 25.2 MW

P=
16380A
5
Quadrants Power consumption
1 6.3 MW
2 3.9 MW
3 8 MW
4 7 MW
Total power consumption 25.2

6
7
Example COVERAGE
The wiring layout plan for
distribution lines for one of the
scope areas covering the 6th
and 5th street with it’s
boundaries at Cabingan street,
7th and 4th street.
COVERAGE BLOCK A
BLOCK B

Along with scope of area,


the neighborhood are set
in blocks (A, B and C) for in BLOCK C
depth analysis and other
future interpretation that
needed easier depictions.
QUADRANT 1
Building No. of Ampacity Total
Type Structures rating (A) ampacity
, A)
Households 128 45 5760

Commercial 14 100 1400


Buildings
Total 142 145 7160

(240V)(7160A)
Distribution Transformers to consider

With total structures


of 142 and a kW BLOCK A
44 household
rating of 1718.4kWh, BLOCK B
8 commercial bldg.

the strategy for 56 household


4 commercial bldg.
distribution
transformers for Total
Structures is to be
BLOCK C
determined by each 28 household

blocks of the Covered 2 commercial


bldg.

area with each


corresponding utility
poles.
In depth Power Consumption Analysis per blocks
Location/ No. of Ampacity Total Ampacity
Blocks commercial Rating (A) (A)
bldg.

A 8 100 800 BLOCK B BLOCK A


B 4 100 400
C 2 100 200
Total 14 300 1400

Location/ No. of Ampacity Rating Total Ampacity


Blocks Houses (A) (A)
BLOCK C
A 44 45 1980
B 56 45 2520
C 28 45 1260
Total 128 135 5760
Example in installing Distribution
Transformers for BLOCK A

BLOCK A FISH BONE METHOD ANALYSIS

In Block A, the measured power


consumption is about 1,718.4 kW

the red lines are for the respective blocks


service drops, while the blue lines are for
not the designated blocks.

The measured power and ampacity is then


accredited to what distribution
transformers is to be used selected utility
poles
BLOCK A

Since the ampacity of the Block A is measured to be 2780 A


we need to distribute these using for the transformers while we
step down the voltage. In this case we divide 2780 A until we get
an ampacity lesser Than the primary lines ampacity rating so
melting can be avoided.

If the ampacity rating of the primary lines for 4/0 is 302, we


need to divide the ampacity of 2780 A to match the rating.

2780 A / 10 = 278 A

Therefore the transformers needed to distribute 2780 A is 10

14
Final comments

For installing the distribution transformers for every


blocks, one must keep in mind that the transformers
are also shared by the community area, this detail may
influence the installation of the transformers whether
the capacity of the transformer can support the load
itself because certain areas have more household to
supply its demands than other places. Transformers
are complex electrical equipments themselves and
varies depending on the loads it supplies,