Professional Documents
Culture Documents
Power Quality
Power Quality
Power Quality
BTEE 413
This few milliseconds is enough time for the digital 1’s and
0’s inside to get confused, and data gets lost or corrupted.
And so the lost energy from the sag may not be enough to
shut down the device, but only enough to confuse the
digital components.
Following from the “confusion” of the digital components,
a lock-up may result.
Since the device switch is still on, as soon as the sag is over
and the voltage has returned to nominal, the system turns
back on, or restarting occurs.
1.4.3: Possible Solutions to Voltage
24
Sags and Swells
Since sags and swells are closely dependent on the wiring or system
impedance, a possible solution to remedy these types of
disturbances is to increase the wire size of the distribution path.
The increasing in wire size also decreases the impedance,
ultimately reducing the magnitude of the disturbance.
If these steps are not possible, then you must introduce an energy
storage device or a form of voltage regulator to maintain
voltage stability and protect equipment.
Products that (i) provide longer ride-through times such as
enhanced power supplies, (ii) regulate the voltage such as tap-
switching power conditioners, or (iii) switch to temporary back-
up power like an SPS, will suffice
1.5: Overvoltage and Undervoltage
25
n 2
I rms In
n 1
1.6.5: Total Harmonic Distortion
33
Current waveform
Spectrum
1.6.7: Effect of load symmetry on
37
harmonics
Symmetrical loads are those that the current half-waves are
equal and opposing
f (t ) f (t )
Assuming: that the distorted current contains a second
harmonic, it is possible to write, for example:
I (t ) I (t )
The RHS of the two equations above can be true, IF and
ONLF IF, I2 = 0 (i.e., the amplitude of the second
harmonic term is zero)
1.6.7: Effect of load symmetry on
39
harmonics (3)
In fact, the same reasoning can be extended to all even order
harmonics.
And so for the case of symmetrical loads, the even order
harmonics are zero or automatically suppressed.
In short, SYMMETRY SUPPRESSES EVEN-ORDER
HARMONICS.
Since the majority of loads connected to the power network are
symmetrical
The even order harmonics are zero or will be automatically
suppressed
Consequently, ONLY THE ODD ORDER HARMONICS
WOULD BE CONSIDERED in the treatment of harmonics in
power networks connected to symmetrical loads
1.6.8: Effect of balance loading on
40
harmonics
Consider a symmetrical, balanced, non-linear 3-phase load
(balance: has phase lag of 120 deg.)
Assume that the currents drawn by this load include the third
harmonic
Then the third harmonic currents of each of the phases “a”,
“b”, and “c” can be written as:
I a 3 I 3 sin 3(t )
2
I b3 I 3 sin 3 t I 3 sin( 3t 2 ) I a 3
3
4
I c 3 I 3 sin 3 t I 3 sin( 3t 4 ) I a 3
3
I a 3 I b3 I c3
1.6.8: Effect of balanced loading on
41
harmonics (2)
Consequently:
For balanced loading, the third order harmonic currents of
all three phases are equal.
1.6.8.1: Symmetrical, balanced nonlinear 3-
42 phase loads WITHOUT neutral
Spectrum
Spectrum
The problematic harmonics are the 3rd, 9th, 15th, etc., which
are called triplen harmonics, because the currents add up
in the neutral conductor (this fact will be shown
mathematically in later slide)
Because they add up in neutral, they can cause the
conductor to heat and burn, a potential fire hazard and
voltage imbalance
Phase-to-neutral nonlinear loads having switch-mode power
supplies generate them.
These power supplies draw current only at the peak of the
voltage sine wave.
1.6.9.1: Effect of triplen harmonics on non-
47 linear single-phase balanced loads
If the loads are non-linear,
the phase currents are non-sinusoidal and
therefore contain harmonics, particularly of orders which are
multiples of 3
The currents are
I r 3 I 3 sin 3(t )
2
I s 3 I 3 sin 3 t I 3 sin( 3t 2 ) I r 3
3
4
I t 3 I 3 sin 3 t I 3 sin( 3t 4 ) I r 3
3
I r 3 I s3 I t 3
1.6.9.1: Effect of triplen harmonics on non-
48 linear single-phase balanced loads (2)
From the deduction, the third harmonic currents in all 3
phases are identical.
Since the current in the neutral is equal to the sum of the
currents in the phases, the harmonic component of order 3
of the neutral current is equal to the sum of the components
of the order 3, that is,
I n3 I i I r 3 I s 3 I t 3
3I r 3
And so for balanced single-phase loads, the third harmonic
component of the neutral current is 3 times the third
harmonic component of the phase current.
1.6.9.1: Effect of triplen harmonics on non-
49 linear single-phase balanced loads (3)
Generally:
for balanced single-phase loads, the harmonic
currents of orders which are a multiple of 3 are in
phase and add up arithmetically in the neutral
conductor
Therefore, because of the adding up, the THIRD
HARMONIC CURRENTS are called ZERO-
SEQUENCE CURRENTS, circulating in phase in
all three phases
the fundamental components and harmonics of orders
which are non-multiples of 3, on the other hand,
rather cancel one another out.
1.6.9.2: Waveform of Phase and Neutral
50 Currents of Triplen Harmonics
I 3 I 3 I3
I3
I 3
1.6.9.1: Effect of delta-star transformer
55
on third harmonics (2)
Assume each of the non-linear loads at the secondary
star-side generates a third order harmonic current .
An equivalent harmonicI 3 current of will be generated
I
at the primary delta-side, that is, confined inside
3 the
delta winding.
Consequently:
For a delta-star transformer supplying identical
non-linear loads, third-order harmonic currents
are confined in the delta winding and NOT
transmitted to the network.
1.6.10.2: Effect of star-connection on
56
third harmonics
The line voltage is given as VAB VA VB
For the third harmonic component, the line voltage is
1. Derating of equipment
2. Segregation of polluting loads
the polluting loads must be identified and separated
from the sensitive loads, for example, by powering
them from separate sources or from dedicated
transformers.
3. Oversizing of neutrals (by say 200%), switchgears and
capacitors
4. Using separate neutral conductors (instead of a
common neutral).
1.6.11.2: Modifying the installations
68
(2)
5. Special protective devices – that are sensitive to
harmonics
6. Employing K-rated transformers.
K-rated transformers are specially-designed
transformers that have been developed to accommodate
the additional heating caused by harmonic currents.
7. Installing special transformers
There are several types of transformer connections which
can cancel harmonics.
For example, the traditional delta-wye transformer
connection will trap all the triplen harmonics (3rd, 9th, 15th,
21st, etc) in the delta winding
1.6.12.3: Filtering the harmonics
69