CET for SPA-ZC 40x Engineering

Overview

This document will in short describe the engineering steps taken during SPA-ZC40x
configuration.

NOTE I: Before starting CET tool the IED configuration have to finalized. AR-file existing.
NOTE II: More detailed information is found from “SPA-ZC400 Installation and Commissioning
Manual”
© Substation Automation Products - 2 -
CET for SPA-ZC 40x Engineering

Configuration Overview
This document concentrates to following part:

REF 541 Import CET for Export Import CET for


.ar file SPA-ZC 40x .CID
IEC61850 OPC Server

Import

Write
SCL Import Create
Read
OPC Save
Picture Editor Process
Write PO List OPCPOLIST.PL
Install P.F.
Objectsaddress
SPA-ZC 40x
Autoconfig
APL. Object
Navigator OPC DA Client
© Substation Automation Products - 3 -

Config tool

Save

.INI
CET for SPA-ZC 40x Engineering

Installation
Install Communication Engineering Tool for SPA-ZC40x.
 Install Connectivity packages
In Win2003Server installation is needed to run from Control panel  Add/remove programs.

Connectivity package manager


Select the products and connectivity packages up to your hardware.
© Substation Automation Products - 4 -
CET for SPA-ZC 40x Engineering

Starting CET Tool


 Start CET tool
 Create a new
project
 And open it
© Substation Automation Products - 5 -
CET for SPA-ZC 40x Engineering

Create new project and import .ar file


 Right click the project name
 Create a new SPA-ZC v2 and a new feeder IED
 Select the correct settings for “Object Properties”
in LD1 level. Correct relay type/version etc.
 In case you are not using Disturbance Recording
upload function disable it.
 Import the .ar file
© Substation Automation Products - 6 -
CET for SPA-ZC 40x Engineering

Import .ar file


 Select the correct .ar file
 The following functions are not
imported automatically. You have
to create them by hand.
 Imported structure look like this.
 Rename SPAZC40x according to
bay/relay name
© Substation Automation Products - 7 -
CET for SPA-ZC 40x Engineering

Object properties for SPA-ZC level


 Change the settings needed in SPA-ZC level, IP address, SNTP Server, Time Zone
 Default Gateway; in case all of your hardware is connected to one network the default gateway
address does not matter. Recommendation is to use the first address of the IP address range. If
you have separate networks use the address of the computer which is the link between networks.
 If you have GPS with SNTP Server functionality you are able to use synchronization
directly from GPS to SPA-ZC.
© Substation Automation Products - 8 -
CET for SPA-ZC 40x Engineering

Bay local/Remote switch


 IEC61850 standard defines bay local remote switch to be single indication. The relays
from FIABB are sending out three different L/R switch states. To receive all them you need
to change the type the of DO “Loc” to DPS.
 Delete the SPS type of DO
 Start DO Wizard to create a new one.
© Substation Automation Products - 9 -
CET for SPA-ZC 40x Engineering

Bay local/Remote switch


 Create data object by type DPS
 Give the address information as right side.
Found from the “Event list” manual of the
relay.
© Substation Automation Products - 10 -
CET for SPA-ZC 40x Engineering

Data sets
 To enable spontaneous data transfer the signal
needs to be included in some of the data sets.
 Open LD0/LLN0/
StatUrg  Trip signals
StatNrml  Positions
MeasFlt  Measurements
 Drag and dropp signals from LD1 to there
© Substation Automation Products - 11 -
CET for SPA-ZC 40x Engineering

Additional signals
 It is recommended to use the Logical Node called GGIO for all the signals created by
hand.
 More information about LNs is found from IEC61850 standard 7-4.
 More information about DOs (Data Objects) and DAs (Data Attributes) is found from
IEC61850 standard 7-3.
© Substation Automation Products - 12 -
CET for SPA-ZC 40x Engineering

Additional signals, Single indication


 If there are some functions, not supported by IEC61850 standard, used in relay
configuration you have to create them manually to SPA-ZC configuration.
 In the following example there are some single indication signals created. The status of
Binary output is read directly.
© Substation Automation Products - 13 -
CET for SPA-ZC 40x Engineering

Additional signals, Single indication


 Address information is found from the
Event list manual of the relay.
© Substation Automation Products - 14 -
CET for SPA-ZC 40x Engineering

Additional signals
 Signals needs to be added to
some data set to be reported
to upper level system.
© Substation Automation Products - 15 -
CET for SPA-ZC 40x Engineering

Additional signals, Single command


 Address information is found from Parameter List
and Event List manuals of the relay.
© Substation Automation Products - 16 -
CET for SPA-ZC 40x Engineering

Downloading configuration
 Target IP is the IP address of the SPA-ZC at the moment.
 Default IP address of SPA-ZC40x: 192.168.2.10
 A new IP is in Object Properties tab on a right side. Each SPA-ZC must have unique
IP.
© Substation Automation Products - 17 -