Professional Documents
Culture Documents
Chapter Two
Chapter Two
Transformer
1
2.1 INTRODUCTION
• A transformer is a static device that changes ac electric power at
one voltage level to ac electric power at another voltage level
through the action of a magnetic field.
It consists.
2
2.2 TYPES OF TRANSFORMERS
5
2.3 PRINCIPLE OF TRANSFORMER ACTION
• The action of a transformer is based on Faraday's law of electromagnetic
induction.
7
Cont….
v p t i s t
a
v s t i p t
In instantaneous quantities
8
Cont….
v p t i s t N p
a
v s t i p t N s
Vp I
In rms quantities
s a
Vs I p
10
Power in an Ideal Transformer
11
Impedance Transformation through a Transformer
12
Example 1
13
Solution to Example 1
14
2.3.2 Theory of Operation of Single-Phase Real Transformers
Leakage flux: flux that goes through one of the transformer windings
but not on the other one
Mutual flux: flux that remains in the core and links both windings15
Cont…
P M LP
S M LS
16
Magnetization Current
1. The magnetization current Im, which is the current required to produce the flux
in the transformer core
2. The core-loss current Ih+e, which is the current required to make up for
17
hysteresis and eddy current losses
Cont….
Excitation current, Io
Magnetization current IM
(current required to produce
flux in the core)
18
2.4 The Equivalent Circuit of a Transformer
The losses that occur in transformers have to be accounted for in
any accurate model of transformer behavior.
1. Copper (I2R) losses. Copper losses are the resistive heating
losses in the primary and secondary windings of the transformer.
They are proportional to the square of the current in the
windings.
2. Eddy current losses. Eddy current losses are resistive heating
losses in the core of the transformer.
3. Hysteresis losses. Hysteresis losses are associated with the
rearrangement of the magnetic domains in the core during each
half-cycle.
4. Leakage flux. The fluxes which escape the core and pass through
only one of the transformer windings are leakage fluxes. These
escaped fluxes produce a self-inductance in the primary and
secondary coils.
19
2.4 .1 The Exact Equivalent Circuit of a Transformer
• Modeling the copper losses: resistive losses in the primary and secondary
the core and lags the applied voltage by 90o. It is modeled by XM.
• Modeling the core loss current: Ih+e is proportional to the voltage applied
to the core and in phase with the applied voltage. It is modeled by RC.
20
Cont….
21
Cont….
22
2.4.2. Approximate equivalent ckt of transformer
23
Example 2.
A 50-kVA 2400:240-V 60-Hz distribution transformer has a leakage
impedance of 0.72 +j0.92 ohm in the high-voltage winding and
0.0070 + j0.0090 ohm in the low-voltage winding. At rated
voltage and frequency, the impedance Z of the shunt branch
(equal to the impedance of Rc and j Xm in parallel) accounting
for the exciting current is 6.32 + j 43.7ohm when viewed from the
low-voltage side. Draw the equivalent circuit referred to (a) the
high-voltage side and (b) the low-voltage side, and label the
impedances numerically.
24
Solution
Referred to (a) the high-voltage side (b) Referred to the low-voltage side.
25
2.5 Determining the Values of Components in the
Transformer Model
• It is possible to experimentally determine the parameters of the
approximate equivalent circuit.
• An adequate approximation of these values can be obtained
with only two tests.
• Open-circuit test
• Short-circuit test
26
Circuit Parameters: Open-Circuit Test
28
Circuit Parameters: Short-Circuit Test
V
R p a 2 Rs j X p a 2 X s sc cos 1 PF
I sc
• Usually the efficiency for a power transformer is between 0.9 to 0.99. The
32
higher the rating of a transformer, the greater is its efficiency.
Example 3
33
Soln
34
2.7. Three-Phase Transformers
• Three phase transformers are used throughout industry to change values of
three phase voltage and current.
• For higher-power applications, three-phase transforms are commonly used.
• The transformers for such circuits can be constructed either as a 3-phase
bank of independent identical transformers or as a single transformer wound
on a single 3-legged core (lighter, cheaper, more efficient).
35
Cont…
36
Three Phase Transformer connection:
There are only 4 possible transformer combinations:
• Delta to Wye (Δ-Y ) - used in commercial, industrial and the most common.
• Wye to Wye (Y-Y) - used rarely, causes harmonics and balancing problems.
• For three-phase Alternating Current (AC) circuits, there is a relationship between line and
DELTA:
(Line voltage) = (Phase Voltage)
(Line current) = (Phase current) * sqrt(3)
37
Delta-Delta connection
38
Delta-Wye connection
39
Wye-Delta connection
40
Wye-Wye connection
41
2.8 Autotransformer & instrument transformer
2.9.1 Autotransformer
• Auto transformer is kind of electrical transformer where primary and secondary
shares same common single winding.
• In Auto Transformer, one single winding is used as primary winding as well as
secondary winding.
• As in an ordinary transformer, the ratio of secondary to primary voltages is equal
to the ratio of the number of turns of the winding they connect to.
• Fig below shows the physical arrangement of autotransformer
43
Cont…
• Hence, the voltage across the portion BC of the winding, will be,
44
Advantages of auto transformers
45
Disadvantages of an Autotransformer
• Does not have the primary to secondary winding isolation of a conventional double
wound transformer. Then autotransformer’s can not safely be used for stepping down
• If the secondary side winding becomes open-circuited, current stops flowing through
the primary winding and stopping the transformer action resulting in the full primary
• If the secondary circuit suffers a short-circuit condition, the resulting primary current
would be much larger than an equivalent double wound transformer due to the
• Since the neutral connection is common to both the primary and secondary windings,
isolation between the two windings. Double wound transformers are sometimes used
46
to isolate equipment from earth.
Application
47
Example 4
• A single-phase auto transformer has a voltage ratio 320 V:250V and supplies a
load of 20 kVA at 250 V. Assuming an ideal transformer, determine the current in
each section of the winding.
• soln
Rating =20 kVA = V1I1 = V2I2.
The current flowing in each section of the transformer is shown in Fig below
48
2.9.2 Instrument transformer
• A device that serves as an input source of currents and voltages
from an electric power system to instruments, relays, meters, and
control device.
• The basic design is that of a transformer with the primary winding
connected to the power system, and the secondary winding to the
sensing and measuring equipment.
49
• A current transformer is a transformer, which produces in its secondary
winding a current, which is proportional to the current flowing in its
primary winding.
• The secondary current is usually smaller in magnitude than the
primary current, and connected in series to the equipment.
• In current transformers the primary usually consists of one or two
turns whilst the secondary can have several hundred turns.
• Figure below shows current transformer Symbols and Simplified
Concepts. t and
e n
urr ols
: C mb s
. 10 Sy pt
re 2 rmer once
u o C
Fig ansf fied
Tr pli
50
m
Cont…
t C.T
en
n gem
a rra
a l
ic
typ
. 11A
2
FIG
51
Voltage transformers
• Voltage or Potential transformer (PT) is a step down transformer
having many primary turns but few secondary turns.
• They are designed to present negligible load to the supply being
measured and have an accurate voltage ratio and phase
relationship to enable accurate secondary connected metering.
• Figure below shows voltage transformer Symbols and
er
Simplified Concepts. orm ts
f
s cep
n
a n
Tr Co
e nt ied
urr plif
2 : C Sim
2.1 nd
re sa
i gu bol
F m
Sy 52
Cont…
53
Generally
The main tasks of instrument transformers are:
• To transform currents or voltages from a usually high value to a
value easy to handle for relays and instruments.
• To insulate the metering circuit from the primary high voltage
system.
• To provide possibilities of standardizing the instruments and
relays to a few rated currents and voltages.
54
2.10 Parallel operation of transformer
• Two or more transformers are connected to the same supply bus bars on the
primary side and to a common bus bar/load on the secondary side.
• Such requirement is frequently encountered in practice.
2. The power demand might have increased over a time. More transformers
3. To ensure improved reliability. Even if one of the transformers gets into a fault or
may be easier to transport smaller ones to site and work them in parallel.
55
Cont……
• Fig. below shows the physical arrangement of two single phase
transformers working in parallel on the primary side.
• Transformer A and Transformer B are connected to input voltage bus bars.
57
OF O
N D TW
E
E T ER
H
T AP
CH
58