Professional Documents
Culture Documents
Lecture 14 & 15 System and Equipment Earthing
Lecture 14 & 15 System and Equipment Earthing
Earthing
Introduction
Terminology
In Britain, people have 'earth' and in Northern America
they have 'ground'. They are exactly the same thing,
only different terms are used in different countries.
The subject of earthing may be divided into two.
General Equipment earthing
System neutral earthing
The main objects of earthing are to:
- Reduce the voltage stresses due to switching, lightning,
faults, etc
- Control fault currents to satisfactory values
Introduction
General Equipment Earthing
It is the practice of earthing the metallic frames of
electrical equipment
Purpose - Improve safety to
- operational staff
- the general public
- property in general and
- system electrical equipment
Introduction
System Neutral Earthing
It is the practice of earthing the star-point or neutral of
the electrical power system
OCPDs do not trip because ground fault current is low due to high value
of Rf.
Ungrounded system
fault phase A supplied the currents ICGB and ICGC.
These being capacitive currents, no current flows
when the line capacitance is charged. Hence, an
arcing takes place at the faulted point. During this
period, the line capacitance discharges and capacitive
current once again flows.
This repetitive cycle of charging and discharging
causes intermittent arcing at the point of fault and
also gives rise to abnormal voltages across the healthy
phases due to the capacitance effect.
Ungrounded system
If this ground fault is intermittent or allowed to
continue, the system could be subjected to possible
severe over-voltages to ground, which can be as high
as six to eight times phase voltage. Such over-
voltages can puncture insulation and result in
additional ground faults. These over-voltages are
caused by repetitive charging of the system
capacitance or by resonance between the system
capacitance and the inductance of equipment in the
system. For these reasons, they are being used less
frequently today.
Solidly Grounded Systems
Intentional connection of neutral to ground.
Solved system overvoltage problem of ungrounded
systems
Solidly Grounded Systems
Advantages Disadvantages
Fixed line to ground voltage Unscheduled service interruption
Strong shock hazard to personnel
Permit line-to-neutral loads
Solidly Grounded Systems
Solidly Grounded Systems
Advantages
It is simple and inexpensive in that it requires
no extra equipment. The expense of the earth-
current limiting device such as resistors, reactors,
etc, is eliminated.
The neutral point is held at earth potential
under all operating conditions. Consequently,
the voltage of any conductor to earth under
earth-fault conditions will NOT exceed the
normal phase voltage of the system.
Solidly Grounded Systems
The protection of the system is simplified by
virtue of the fact that the ground fault current
compares in magnitude with inter-phase fault
currents, making detection relatively easier
Hazard voltages are reduced to acceptable levels.
Power frequency, phase-earth overvoltages are
lowest, typically below 1.4 p.u., and this explains
why HV systems are solidly earthed.
Solidly Grounded Systems
Disadvantages
A solidly grounded system produces the greatest
magnitude of fault current when a ground fault
occurs
The increased ground fault current results in
greater influence (interference) on
neighbouring communication circuits.
The increased ground fault current produces
more conductor burning.
It is more pronounce at generation stations.
Impedance Grounded Systems
Impedance Grounded Systems
• Impedance inserted between neutral and
ground.
• Limits fault current, prevents arcing
ground faults.
• Still limits transient overvoltage.
Impedance Grounded Systems
Impedance Grounded Systems
By suitable choice of the ohmic value of the
impedance, the lagging component of the fault
current can be made equal to or more than
the capacity current, so that no transient
oscillation due to arcing grounds can occur.
However, if the ohmic value of the impedance
is sufficiently high so that the lagging current is
less than the capacity current , then the system
condition approaches that of the ungrounded
neutral system with the risk of transient
overvoltages occurring.
High Impedance Grounded
Advantages Disadvantages
Limits Ground Fault current to 10 Amps or less Potential for nuisance alarming
Allows faulted circuit to continue operation Maintenance personnel may ignore first
fault
High Impedance Grounded
High- Impedance grounding helps ensure a ground-
fault current of known magnitude, helpful for relaying
purposes. This makes it possible to identify the
faulted feeder with sensitive ground-fault relays.
Low Resistance Grounded
Limit ground fault current to a high level (25-400A)
in order to operate protective fault clearing relays.
Limits damage to equipment
Prevents additional faults
Provides safety for personnel
Localizes the fault
Arc-Suppression Coil Earthing
(or Resonant Grounding)
Arc-suppression-coil, also called Peterson coil after the
inventor, is an attempt to eliminate the fault current that
could cause the arcing ground condition.
Arc-suppression coil earthing can be seen as special
reactance earthing, whose inductance can be adjusted to
closely match the network phase-earth capacitances,
depending on the system configurations.
Arc-Suppression Coil Earthing
(or Resonant Grounding)
The inductance of the arc-suppression-coil is adjusted such
that the inductive current due to the coil approximately
neutralizes capacitive current through the total network
capacitance 3C, at the fault.
The resultant earth-fault current is theoretically suppressed
and in any case inadequate to maintain the arc. Hence the
name “ arc suppression coil”.
Arc-Suppression Coil Earthing
(or Resonant Grounding)
Voltage to earth of the faulty phase at the point of fault
becomes zero
Voltage on the healthy phases is increased to 1.732 times
the normal value
A resultant capacity current I-ag equal to three times
the normal line to neutral charging current flows
through the fault. This leads the voltage of the faulty
phase by 90 deg .
Neutral Grounding Device –Definition
Neutral Grounding Device – an impedance device
used to connect the neutral of an electrical system to
ground for the purpose of controlling ground current
and voltage-to-ground.
Earthing in a EHV Substation
1. Objective:
The touch and step potential shall be within
limits under all conditions including fault
condition
Grounding resistance shall be lower.
Effective earthing system shall aim at providing
protection to life and property against dangerous
potentials under fault conditions
Earthing System
Points to be earthed in a substation
The neutral point of each separate system should
have an independent earth, in turn interconnected
with the station grounding mat.
Equipment frame work and other non-current parts
All extraneous metallic frame works not associated
with equipment .
Lightning arrestors should have independent
earths, in turn connected to the station grounding
grid.
Earthing System
Over head lightning screen shall also be connected to
main ground mat.
Operating handles of Isolators with a auxiliary earth mat
underneath, if necessary.
Peripheral fencing
Buildings inside the switch yard.
Transformer Neutrals shall be connected directly to
the earth electrode
Substation Earthing –Design of Earth mat
Design depends upon the following parameters
Durational and magnitude of the fault current
Resistivity of the surface layer of the soil
Resistivity of the soil
Magnitude of current that the human body can safely carry
Permissible earth potential raise that may take place due
to the fault conditions
Shock duration
Material of Earth- mat conductor.
Earth- mat geometry
Transient overvoltage
Lightning protection
Application of protective devices for selective ground fault
protection
Types of load served, such as motors, generators, etc.
EARTH MAT DESIGN
Substation Earthing –
Design of Earth mat
Parameters for the calculation of Maximum
permissible step and touch potential
Fault duration :- Fault clearing time of back up
protection is adopted
Modern protection systems provides for fast acting
back up protection
Considerable saving can be made by optimizing the size
of the conductor of earthing grid by considering lesser
fault duration.
These will change the earth potential raise due to
which Step and Touch potentials arise.
Touch and Step Potentials
Conductor area A = I x t
K
Where
A = area of earth conductor in mm2.
I = short circuit current in KA.
t = duration of short circuit current in seconds.
K factor = 80 for steel.
Cont’d
If mat is made of Flat then
If it is a conductor then
Cont’d
STANDARD FLATS
i) 10 x 6 iv) 40 x 6 vii) 60 x 6
Ii) 20 x 6 v) 50 x 6 viii) 65 x 10
Iii) 30 x 6 vi) 50 x 8 ix) 75 x 10
ROD
40 mm Mild Steel Rod
Ensure connections are tight
Soil Resistivity
As soil resistivity differs with moisture content and, to a
slighter point, with temperature, ideally these
measurements should be made over a period of time
under different weather conditions. If, for some reason,
an actual measurement of resistivity is impractical,
gives approximate values of resistivity for different soil
types. The following values are only approximations and
should be replaced by measured data whenever
possible.
Type of ground Resistivity Ωm
Wet organic soil 10
Moist soil 102
Dry soil 103
Bedrock 104
Measurement of Soil Resistivity
Four Terminal: Four spikes are driven into the ground at equal
intervals. The two outer spikes are connected to current terminals of
earth megger and the two inner spikes to potential terminals of the
megger till a steady value is obtained.
For 3 Terminal Meter (ii) For 4 Terminal Meter
Current Terminal – C or H Current Terminal C1, C2
Potential Terminal – P or U Potential Terminal P1, P2
Earth Terminal – E
4 TERMINAL EARTH TESTER
Maintenance Schedule in at Substations: