Engineering Application Guide How to read LGMV data of Hydro kit

Title How to read LGMV Data of Hydro kit (Major Check Points_ High temp.)

Summary • description for 31menu bars of LGMV data for hydro kit

Question –
•Please provide the description for 31menu bars of LGMV data for hydro kit

1 Check Water Pump


Answer – 2
Operation during
•As you can see shown below table, you can find the description for 3
product
4
31 menu bars of LGMV data for Hydrokit 5
6
0=off, 1=on
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

View detail 22
23

Hydro kit data 24


25
By double clicking 26
Check Flow S/W
27
Operation during
28
29
product
30
0=off, 1=on
31
Checking Points 7. Start up

How to read LGMV cycle


Outdoor unit
Outdoor unit
actuator data
cycle data

Outdoor unit
Input
sensor data
installation
information

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 2


Checking Points 7. Start up

How to read LGMV cycle (Major Check Points_ medium temp.)

EEV normal boundary : 200~1350 PLS

Check Water Pump


Operation during product
0=off, 1=on

View detail
Hydro kit data
By double clicking

Check in/out water temp difference


: Acquire standard flow amount
condition 5~10 degree

Check Flow S/W


Operation during product
0=off, 1=on

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 3


Checking Points 7. Start up

How to read LGMV cycle (Major Check Points_high temp.)

EEV normal boundary : 200~1350 PLS

Check Water Pump


Operation during product
0=off, 1=on

View detail
Hydro kit data
By double clicking it

Check in/out water temp difference


: Acquire standard flow amount
condition 5~10 degree

Check Discharge temp : 60~100℃

Check Flow S/W


EEV normal boundary : 200~1000 PLS
Operation during product
0=off, 1=on

Check intake temp : 0~50℃

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 4


Checking Points 7. Start up

How to read LGMV cycle (Major Check Points_high temp.)


1. Hydrokit H temp
- Shows what kind of Hydrokit it is
: Hydrokit M temp = Mid temp., Hydrokit H temp = High temp.
It is automatically specified as Hydrokit M temp. or Hydrokit H temp. when LGMV 1
2
is connected. 3
4
2. IDU num 5
6
- Shows Hydrokit numbers : Auto addressed address between OUD and Hydrokit.
7
8
3. temp.selection
9

- Shows Reference selection for temperature control 10


11
(outlet water temp. or Air temp.) 12
13
: Outlet water temp=1, Air temp=0 ※ For more details refer to the link
14
15
4. air/water tqt(Target temperature) 16

- Shows setting values for Target temperature of Outlet water/Air 17


18
: Mid temp : Max = 50℃(122℉), High temp : Max = 80℃(176℉) 19
20
The table on right shows target temperature of Hydrokit #1, #2, and 21

#3 are set as 70 ℃, 50 ℃, and 70 ℃ respectively. 22


23
24
5. Hot water act.(Activation)
25
- Shows status of Hot water mode. (Related #8 on next page, When hot water 26
27
mode is on it can be activated) : 0 = Disable, 1 = Enable 28
29
Table on the right shows “0” due to it’s not activated.
30
31
6. tgt(Target) hot water
- Shows set value for target temperature when how water mode is on
(Table on the right , shows 50 ℃ target value.)
Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 5
Checking Points 7. Start up

How to read LGMV cycle (Major Check Points_high temp.)


7. Water pump
- Shows operating status of Water pump : 0 = Off, 1 = On
1
8. Hot water mode 2
3
- Hot water mode status On or Off
4
(Shows 3way valve’s status for hot water) 5
6
: 0 = Off, 1 = On 7
8
9
9. Hot water temp.(temperature)
10

- Shows current hot water temperature. : Table on the right 11


12
shows -100℃ due to the absence of sensor. 13
14
15
10. inlet temp.(temperature)
16
- Shows incoming water temperature 17
18
Table on right shows #1 Hydrokit : 49.52℃ 19
20
#2 Hydrokit : 49.52℃, #3 Hydrokit : .50.71℃
21
22

11. outlet temp.(temperature) 23


24
- Shows outlet water temperature from Hydrokit. 25
26
: For instance, from right #1 Hydrokit : 49.52℃
27

#2 Hydrokit : : 50.11℃, #3 Hydrokit : : .60.43℃ 28


29
30
12. temp.diff(difference) 31

- Shows temperature difference between inlet and outlet water


: #1 Hydrokit : 0℃, #2 Hydrokit : 0.59℃, #3 Hydrokit : 9.72℃

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 6


Checking Points 7. Start up

How to read LGMV cycle (Major Check Points_high temp.)


13. Error code
- Shows error codes
: Check the attached main Error Code of Hydrokit
1
2
14. Heater mode 3
4
- N/A
5

15. Heatsink temp(temperature) 6


7
- Temperature on INV PCB Heat sink of Hydrokit (High Temp.) 8
9
From Table on right, #1Hydrokit : 32℃, #2 Hydrokit : 38℃,
10

#3 Hydrokit : 75℃ 11
12
16. High press.(pressure) 13
14
- Shows Hydrokit(High temp.) product’s high pressure value in compressor. 15

The range could vary depending on water temperature. 16


17
Normal condition : approximately 1000~2700kPa 18
19
17. Low press.(pressure) 20
21
Shows low pressure value in compressor of Hydrokit (High temp.) product’s. The range
22
could vary depending on water temperature. Normal condition :
23
approximately 300~1000kPa
24
25
18. dis.temp.(discharge temperature) 26
27
- Shows discharge temperature on R134a compressor of
28

Hydrokit (High temp.) 29


30
: From right, #1 Hydrokit : 27℃, #2 Hydrokit : 49℃, 31

#3 Hydrokit : 74℃
(Discharge temperature range could vary depending on Cycle)

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 7


Checking Points 7. Start up

How to read LGMV cycle (Major Check Points_high temp.)

19. Input current


- Shows Input current : Normal condition : 25A and less 1
2
3
4
20. inv.(invertor) Phase VT
5
: Hydrokit(High Temp.) Inverter Phase voltage 6
7
8

21. inv.(invertor) Phase CT 9


10
: Hydrokit(High Temp.) Inverter Phase current 11
12
13
22. comp. TGT(target) 14
15
: Hydrokit(High Temp.) compressor target Hz 16
17
18
23. comp. TRC(Tracer) 19
20
: Hydrokit(High Temp.) compressor current Hz 21
22
23
24. EEV 24
25
- EEV Pulse
26
: Normal condition approx. 200~1350PLS 27
28
29

25. 4way 30
31
- N/A

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 8


Checking Points 7. Start up

How to read LGMV cycle (Major Check Points_high temp.)

26. Hot gas


- N/A 1
2
3
27. Fan heatsink
4

- N/A 5
6
7

28. Sump heat 8


9
- N/A 10
11
12
29. FCU 13
14
- Fan Coil Unit operational status
15
: 0 = Off, 1 = On 16
17
18
30. Flow S/W 19
20
- Flow switch operational status depending on flow 21
22
: 0 = Off, 1 = On
23
24
25
31. Suction temp.(temperature)
26
- Shows suction temperature on R134a compressor of Hydrokit (High temp.) 27
28
: From the table on the right, #1 Hydrokit : 26.10℃ 29
30
#2 Hydrokit : 44.1℃, #3 Hydrokit : 42.60℃
31

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 9


Checking Points 7. Start up

※ Selecting Air temperature,


Additional temperature sensor
needs to be purchased.

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 10


Checking Points 7. Start up

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 11


Checking Points 7. Start up

Hydro Kit Copyright 2012@LG Electronics / AE Company All Rights Reserved 12

You might also like