Qurayyah Combined Cycle Power Plant: GSU 5 Transformer Bushing Failure
Qurayyah Combined Cycle Power Plant: GSU 5 Transformer Bushing Failure
2015
A fire took place due flashover of transformer bushing
Phase A. Root cause was unknow although ABB and
GE were involved in the investigation.
May 2019
Transformer tripped due to Buchholz relay picked up.
Found only acetone in the main tank 15ppm while taruut was
1211ppm and all other gases were high, Hydrogen was
411ppm.
2019
Maximum Limits:
Acetone: 1ppm
Hydrogen: 100ppm
GSU 5 Transformer
Incidents
Incidents in The GSU 5 Transformer
2015 2015 2019
Facts
Type of bushings installed in QCCP transformer are
01 impogrnated (ABB-RTGK) manufactured in Swaziland
MICAFIL (5F6 to Oil).
When the factory test was done, this bushing was not
02 part of the transformer, Ariva used ( Air to Oil) during the
test.
Facts Corona shields normally supplied along with bushing. Ariva used
03 another model supplied by Swiss Widmmen company as
original can’t fit due to congested designed tank of the
transformer, ABB was informed by Ariva about this.
1
Di-section of the bushing
2
Sustain & Adapt Modeling of effect of variable corona shield position to study
the behavior of partial discharge and consequently the
damage it could impose on the bushing.
Pinholes
Aluminum
foils
Pinholes
Modeling the effect of corona positions
3 3D Modeling by ABB.
4 CT Scan by ABB.
Conclusion
Current Rating HV -
418.6 / 557.1 Amps
(ONAN/ONAF)