Exide Technologies Net Zero DC Summit Cooling Cost Reduction
Exide Technologies Net Zero DC Summit Cooling Cost Reduction
Company Confidential |
The situation.
Data center cooling equipment are
energy intensive consumers, having a
high OPEX impact.
Company Confidential |
Our topics.
Reducing cooling costs through optimized
UPS battery sizing.
Solutions
Considerations
Q&A round
Company Confidential |
The world
is changing. That’s why
we are
energizing
a new world.
Innovation
Reliability
Sustainability
High performance
Company Confidential |
We are an international player
in energy storage solutions for
135 years
Company Confidential |
We think worldwide:
the international
footprint.
Europe:
4 Automotive plants
6 Industrial plants
3 Recycling plants
2 R&D facilities
Automotive plant
Shanghai
Industrial plant Miami Dubai
R&D facility Hong Kong
Recycling Americas:
Headquarter Sales agents and
Main sales offices distribution partners Kuala Lumpur
Adelaide Brisbane
Perth Sydney
Melbourne
Company Confidential | 6
We cover the entire value chain in-house.
Company Confidential | 7
We have merged local expertise into our strength.
Combining well-known brands with experience, cutting-edge technology
and an unrivaled sales & service network.
CEAC
1888 1890 1897 1898 1910 1945 1969 1972- Energy Solutions set-up
Company transformation
Company Confidential | 8
Exide Technologies.
Worldwide leading group.
10
solutions to empower global demands.
Automotive
75% >20
Production sites
Motion
Operating globally in over
Defense
40
locations worldwide
2
industrial brands are supplied
by Exide
Recycling Produced per year
No.
135
Years of battery and energy
storage experience
Serving
~450
Customer groups around the
globe each year
2
Main R&D facilities
Player in all segments
Company Confidential | 9
The link between cooling cost and battery sizing.
Downsizing cost with battery dimensioning.
Lithium-ion suffers from stress when exposed to heat, so does keeping a cell at a high charge voltage. A battery
dwelling above 30°C (86°F) is considered elevated temperature and for most Li-ion a voltage above 4.10V/cell is
deemed as high voltage. Exposing the battery to high temperature and dwelling in a full state-of-charge for an extended
time can be more stressful than cycling.
“The rate at which chemical reactions proceed,
Table 3 demonstrates capacity loss as a function of temperature and SoC.
increases exponentially as temperature rises.”
Estimated recoverable capacity when storing Li-ion for one year at various temperatures. Elevated temperature
hastens permanent capacity loss. Not all Li-ion systems behave the same.
The law by Svante Arrhenius
Reality
Depends on:
• Battery quality (plate type, thickness and alloy, container, poles, etc.)
• Electrolyte density
• Correct charging voltage + AC ripple
• Temperature
• Discharge rate (ultra-fast/medium/long)
• Usage (stationary, cyclic & D.O.D.)
• Inspection & Maintenance / etc.
Company Confidential |
Run Baby run!
Battery sizing and cooling reduction at higher temperatures.
Example temperature vs. charge voltage Battery life as a function of float voltage
Incorrect charge
compensation
+ Rack
• Improved ventilation/cooling
Example UPS-Application 50k € Battery Comparision
rack vs. cabinet cost
• More equal temperature distribution €8,000
€5,000
+
€4,000
Cabinet €3,000
-
Rack price Cabinet price Installation on Installation on Installation & Installation &
rack cabinet Demonting on Demonting in
• t° at the top is usually higher than at the rack cabinet
bottom
• Charge voltage less correct due to the higher
temperature spread
• Position temperature sensor? 2/3rd height
• Battery clamps often inaccessible for
measurement (more compact)
Company Confidential | Date 15
Spring fever for the battery.
Battery sizing and cooling reduction at higher temperatures.
20°C 10 years
30°C 5 years
80% (no EOL)
40°C 2,5 years
by Svante Arrhenius
Determination of average
Step 3 Eurobat “10-12 long life category” & E.O.L. = min. 2 battery swaps
Theoretical Impact Life 10
(desired) temperatures Temperatures below 20°C are indicated as 20°C (no impact on average battery life)
Jan Feb Mar Apr May June July Aug Sep Oct Nov Dez Av. T° AGM/GEL
1 2 3 4 5 6 7 8 9 10 11 12 Year
Jan Feb Mar Apr May June July Aug Sep Oct Nov Dez Av. T° AGM/GEL
1 2 3 4 5 6 7 8 9 10 11 12 Year
Eurobat “>12 years very long life – 20 years” & E.O.L. = no battery swap
Temperatures below 20°C are indicated as 20°C (no impact on average battery life)
Theoretical Impact Life 20
Marathon PowerCycle + Catalyst
Jan Feb Mar Apr May June July Aug Sep Oct Nov Dez Av. T° AGM/GEL
1 2 3 4 5 6 7 8 9 10 11 12 Year
If Then But
all conditions in the step-by- a 10-12 long life battery a >12 very long life (or longer) battery provides a lifetime
step plan have been met can be used in a high which best meets the cooling cost reduction requirement.
(battery correctly described temperature environment,
acc. Eurobat / E.O.L. sizing / but lifetime is potentially too Ex. Scenario
• continuous 25°C & 3 months at 30, 32 & 35°C = 1 battery swap (using >12 years Eurobat)
charge- vs. temperature short (depends on the • continuous 27° = 1 battery swap (using >12 years Eurobat)
• using a 20 years – catalyst/carbon LAB = no swap
compensation etc.). expectation).
Company Confidential |
No technology is better than one that is constantly improving.
The new Sprinter Pure Power. Your ace that protects your data 24/7.
Paves the way to the future with the most advanced pure lead AGM technology
offering the highest power.
15-20%
space saving
20%
higher lifetime
20%
more power at
high-rate discharges
Catalyst in each cell, for an extended design life, especially at high temperature
High surface active carbon additives for high cycle life and fast recharge
Carbon Boost
High-purity lead
PSoC operation
Long life (15 years calendar life and > 5000 cycles)
Powerful (up to 300 kW per cabinet for 11.5 minutes, operation voltage up to 544V)
Efficient (high energy efficiency 98%, active balancing allows to operate old and new
modules together
Scalability due to modularity (up to 15 cabinets in parallel, ≈ 4.5MW for 11.5 minutes)
Easy replacement of modules, does work also with one defect module
• Eurobat classified batteries, from renowned manufacturers, are not necessarily more
expensive.
• Eurobat ">12 Very Long Life" batteries are usually proportionally more expensive than
"10-12 Long Life" batteries.
• Newest generation of advanced pure lead batteries Eurobat ">12 Very Long Life“ are even
more performing than classic VRLA "10-12“ counterpart models (smaller footprint due to higher
volumetric power density & not necessarily more expensive than “10-12” batteries).
Potential more-costs if any, are to be compared to the savings: Sustainability:
• Cooling equipment • Recyclability of nearly 100%, less production required,
circular economical aspect, less energy consuming,
• Cooling / energy cost per year/ total (up to 4% per °C or 1,8°F)
Spalte2 contributing to lower PUE etc..
IT equipment
Cooling
Power Supply
Distribution Losses
Lighting
• Data center expectations and needs are getting more and more diverse and
are rapidly evolving.
• No "one size fits all" anymore
Company Confidential |
Time is changing.
Lifetime is extending.
Key take-aways.
All about reducing cooling cost through optimized
UPS battery sizing:
We transform the future of energy storage and enable the net-zero conversion.
We see ourselves as a partner of todays and tomorrow industries and
communities to drive their electrification.
The Data Center industry can prepare itself for a more sustainable-driven
ecosystem whilst at the same time reducing rocketing energy costs by adopting
Exide Technologies' cutting-edge solutions.