1. Collect the 300-400 ml oil sample of transformer oil from the bottom valve of the transformer in a
glass or plastic vessel.
2. Pour the oil sample in oil pot of the machine.
3. Keep the oil pot in open air for 5 Minutes so that air bubble if any gets out. Further,the vessel should
be disturbed to get out of the air bubbles and for homogeneous distribution of impurities.
4. Now put the oil sample in the machine.
5. Increase the KV at the rate of 2 KV/Sec and observe the oil sample through a glass window.
6. Continuously observe the oil sample through an inspection window while increasing the voltage.
7. Note down the KV at which sparking is observed in the oil. The voltage at which sparking observed is
the breakdown voltage of oil.
8. Repeat the step No. 4,5,6 and 7 for the same sample for six times and note down the breakdown KV
in each case.
9. Take the average of BDV values observed in step 7 and 8.
10. If oil BDV value is above 30 KV, transformer oil is good.
APPLICATION
• OTS completely self contained, compact & portable unit giving smooth variable output
voltage from zero to 60/80/100KV for testing the dielectric strength of insulating oil.
• The set has been specially designed for testing the dielectric breakdown Voltage of
insulating liquids as per the directions mentioned in IS 6792.
MANUFACTURERS
MANUFACTURERS:
Top Manufacturers
Function :
• It evaluates the mechanical integrity of the circuit breaker under various
parameters. It operates the circuit breaker under fault current conditions.
Working Principle:
• After the finishing of testing of the breaker, it measures all the parameters of the
breaker and using a set algorithm. It diagnoses the condition of the device under
various conditions.
The CB Analyzer measures the following values:
Timing Measurements
• Timing tests are used to determine the time taken for open (trip), close, close-open,
and reclosing operations.
Motion Measurements
• It is used to reveal the performance by evaluating the velocity of the main contacts
when traveling through the arcing zone .
Vibration Analysis
• It is done using accelerometers which work like microphones to record the sound
when contact gets open and closed.
Page 34 Restricted | © Siemens 2023 | Author | EL TPS AC | 2023-08-27
• Generally, a reference signature is used to analyze the vibrations in the CB. If a reference signature isn’t
available, we get a reference signature from another CB analyzer of the same type. If the curve diverges
above 10 db., and the time shift is above 8 ms the CB is no longer in optimal working condition.
Static Resistance Measurement (SRM)
• Static resistance measurement (SRM) of circuit breaker contacts was developed to assess the resistance of
the main contacts since during this condition the arcing contacts are bypassed.
• The minimum level of DC current that we will be using will be 50A (set by IEC).
• Static contact resistance is measured by injecting a DC current through the breaker and measuring the milli-
voltage drop. A four-wire measurement method is used. The breaker must be in the closed position. It is
recommended to test the contacts at a higher current (80-100A). A higher current will have the ability to
overcome connection issues and oxidation on terminals, whereas a lower current (~50A) may not produce
accurate readings under these conditions
Dynamic Resistance Measurement (DRM)
• Dynamic resistance measurement (DRM) of circuit breaker contacts was developed to assess the condition
i.e., resistance of the arcing contacts without dismantling a breaker.
• This method is a better solution for the limitations faced in static resistance measurement.
• Here 100A DC current is injected through the breaker. We cannot measure the dynamic resistance during
the open-close operation of the contacts since there will be sudden variation in arcing contacts resistance
which is impractical.
Page 35 Restricted | © Siemens 2023 | Author | EL TPS AC | 2023-08-27
• The contact movement is recorded by a linear contact travel sensor where the resistance at each point of
contact can be calculated if the movement is recorded.
• Generally, a sampling frequency e.g., 10kHz is used to measure the dynamic resistance in each time
period. The resistance measurement and the current transfer from arcing to main contacts are recorded
once in 100 microseconds.
• This method is also is used to measure the length of the arcing contacts.
Structural diagram of
Contactor
Connection Diagram
Coil Current
Here we have 2 tests in general i.e., Trip Coil Test and Close Coil Test. We need to analyze the coil currents flowing
through the coils which will be responsible for the opening and closing of the contactor coils.
• Trip Coil Test
The analyzer will measure the time taken by the circuit breaker to trip after applying certain amount of current to the trip
coil (open coil).
• Close Coil Test
The analyzer will measure the time taken by the circuit breaker to close after applying certain amount of current to the
close coil.
Function:
• This instrument is used to measure the insulation integrity of the medium and high
voltage cables.
Working Principle:
Applying a sinusoidal waveform with a frequency typically ranging from 0.01 Hz to 0.1
Hz to the insulation of medium and high voltage cables.
The main purpose of the instrument is to detect any insulation weakness, stress
uniformity, provide preventive maintenance
• The VLF Testing Instrument involves applying a sinusoidal waveform along with very
low frequency which enables testing without causing any excessive stress on the
cable.
• This device can also be used to provide voltage boost, over-voltage protection
and under-voltage protection, step down, measurement (operates like CB) to an
electrical device
• The device is used to evaluate the insulation integrity mainly for Power Cable,
Rotating Machinery such as Generators, Motors etc
• It is the power system device and used to test and assess the
performance of current transformer.
• It measure excitation curve and knee point.
• The CT Analyzer automatically determines all relevant current
transformer values and compares the results with the selected
standard.
Where it is used:
Working principle:
• HV-HIGH VOLTAGE
• HIPOT- high potential or high voltage test
• The HVHI-pot works under the principle of dielectric breakdown, the
point at which an insulator fails to prevent the flow of electricity.
• Hi-pot testing is an important part of electrical safety testing.
• The insulation of the equipment being tested resists the flow of
current, and the amount of current flow is measured.
1. Pot-Tech electronic
2. Vishay Intertechnology
3. Bourns
4. ALPS Alpine
All the instruments have been studied based on their functions, working principle,
applications and manufacturers.